An Experimental Study on Behavior of Power Conditioning System for Photovoltaic Power Generation System Connected to End of Distribution Line

被引:0
作者
Yamanaka H. [1 ]
Yamaguchi M. [1 ]
Matsuura I. [1 ]
Shimizu H. [1 ]
机构
[1] Polytechnic University of Japan, 2-32-1, Ogawanishi-machi, Kodaira
关键词
distribution system; output power limit value; photovoltaic power generation; power conditioning system;
D O I
10.1541/ieejpes.144.349
中图分类号
学科分类号
摘要
Reverse power flow from a photovoltaic power generation system to distribution system is limited below a certain limit value. The behavior of a power conditioning system (PCS) for large capacity photovoltaic power generation system when the output power approached the output power limit value was experimentally estimated. Under the condition, the PCS became uncontrollable. It was pointed out that this phenomenon was caused by maximum power point tracking (MPPT) control of the PCS. Furthermore, some methods to avoid the uncontrollable condition of PCS were shown. © 2024 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:349 / 355
页数:6
相关论文
共 9 条
  • [1] Ishikawa K., Taniguchi H., Suzuki H., Ota Y., Mizuno Y., Fundamental Voltage Characteristics in Power System with a Large Penetration of Photovoltaic Generation, IEEJ Trans. PE, 134, 1, pp. 2-8, (2014)
  • [2] Iioka D., Technical Issues of Voltage Regulation in Distribution System with Large Reverse Power Flow from Photovoltaic Systems and its Solutions, IEEJ Trans. PE, 140, 6, pp. 441-444, (2020)
  • [3] Matsumura T., Yukita K., Goto Y., Tsukamoto M., Tatewaki K., Yokomizu Y., Ishii Y., Ishikawa H., Matsuo A., Iwatsuki H., Iioka D., A Study on Rising and Reducing Process of Receiving-end Voltage due to Introduction of Large PV Systems into Distribution Power System, IEEJ Trans. PE, 138, 1, pp. 23-29, (2018)
  • [4] Tanaka T., Kawahara K., Harimoto T., Oono Y., Soeda M., Kawasaki R., Goto T., Kubuki M., Influence of Reverse Power Flow on System Voltage in Distribution Network with Large Penetration of Photovoltaics, The 2017 Annual Conference of Power and Energy Socienty, IEE Japan, 187, (2019)
  • [5] Iwatsuki H., Ishikawa H., Matsuura I., Shimizu H., Matsumura T., Takewaki K., Yokomizu Y., Study on Voltage Stability Limit of 6.6 kV Distribution System by Reverse Power Flow from a Group of Photovoltaic Generators, Proc. CIRED 2019 Conference, 624, (2019)
  • [6] Tsusaka A., Tsukamoto M., Isobe Y., Nakao T., Matsumura T., Yukita K., Goto Y., Yokomizu Y., Iioka D., Shimizu H., Iwatsuki H., Kunii Y., Uenishi H., Ishikawa H., Fukae T., Mineta Y., Kanazawa Y., Maximum Allowable Output Power and Optimum Capacity of PV Generator in Power Distribution System under Constant Output Power Control of Power Conditioning System, IEEJ Trans. EEE, 16, pp. 392-401, (2021)
  • [7] Shimizu H., Yamaguchi M., Yamanaka H., Experimental Condition Setting for Performance Verification of Power Conditioning System in Large Scale Photovoltaic Power Generation System Connected to Distribution Line, The 2022 Annual Meeting of The IEEJ, 6-225, pp. 6-225, (2022)
  • [8] Shimizu H., Matsuura I., Kawada Y., Matsumura T., Yukita K., Goto Y., Tatewaki K., Yokomizu Y., Iioka D., Ishii Y., Ishikawa H., Matsuo A., Iwatsuki H., Experimental Investigation on Behavior of Power Conditioning System in Case of Large Photovoltaic System Introduction at End of Distribution Line, 2018 National Convention Record IEE Japan, 6-276, pp. 6-276, (2018)
  • [9] pp. 168-172, (2019)