Effects of conductor eccentric icing on quad-bundle conductor galloping

被引:0
|
作者
Wu C. [1 ,3 ]
Ye Z. [1 ,2 ]
Yan B. [3 ]
Yang X. [1 ,2 ]
Zhang B. [1 ,2 ]
Lü Z. [1 ,2 ]
机构
[1] State Grid Henan Provincial Electric Power Research Institute, Zhengzhou
[2] State Grid Key Lab of Power Transmission Line Galloping Prevention and Control Technology, Zhengzhou
[3] College of Aerospace Engineering, Chongqing University, Chongqing
来源
关键词
Eccentric icing; Galloping; Numerical simulation; Quad-bundle conductor;
D O I
10.13465/j.cnki.jvs.2020.01.005
中图分类号
学科分类号
摘要
The variation laws of lift, drag and torque coefficients of a quad-bundle conductor with typical crescent icing were obtained with wind tunnel tests. A numerical simulation method for iced conductor galloping considering effects of eccentric icing was proposed based on the FE software ABAQUS, and the correctness of the method was verified with examples. The user self-defined subroutine UEL in ABAQUS was used to program an aerodynamic load element, and realize the numerical simulation method for iced conductor galloping considering effects of eccentric icing. The proposed method and the traditional numerical simulation one were used to contrastively analyze galloping characteristics of a quad-bundle conductor with typical crescent icing. The results showed that the proposed method can be used to accurately describe the torsional feature of the iced conductor motion; after considering effects of eccentric icing, displacement and torsional angle amplitudes of the iced quad-bundle conductor obviously increase and its vibration mode is more complex; it is necessary to consider effects of eccentric icing when studying galloping of iced conductor. © 2020, Editorial Office of Journal of Vibration and Shock. All right reserved.
引用
收藏
页码:29 / 36
页数:7
相关论文
共 17 条
  • [1] Zhao B., Cheng Y., Wang J., Et al., Theoretical analysis and countermeasures on the galloping of iced overhead transmission lines in Hubei in early 2015, Journal of Vibration and Shock, 36, 10, pp. 93-97, (2017)
  • [2] Gurung C.B., Yamaguchi H., Yukino T., Identification and characterization of galloping of Tsuruga test line based on multi-channel modal analysis of field data, Journal of Wind Engineering and Industrial Aerodynamics, 91, 7, pp. 903-924, (2003)
  • [3] Dyke P.V., Laneville A., Galloping of a single conductor covered with a D-section on a high-voltage overhead test line, Journal of Wind Engineering, 96, pp. 1141-1151, (2008)
  • [4] Zhang Q., Popplewell N., Shah A.H., Galloping of bundle conductor, Journal of Sound and Vibration, 234, 1, pp. 115-134, (2000)
  • [5] Li L., Chen Y., Xia Z., Et al., Nonlinear numerical simulation study of iced conductor galloping, Journal of Vibration and Shock, 30, 8, pp. 107-111, (2011)
  • [6] He Z., Zhao G., A finite element for 3D free vibration analysis of bundled power lines with weight hammers, Engineering Mechanics, 20, 1, pp. 102-105, (2003)
  • [7] Lou W., Jiang X., Yang L., Galloping of iced bundle conductors in 3D fluctuating wind field, Journal of Vibration and Shock, 35, 22, pp. 1-9, (2016)
  • [8] Zhou K., Hao S., Liu J., Et al., Influence of conductor structure and loads on galloping of a transmission line, Journal of Vibration and Shock, 31, 1, pp. 116-120, (2012)
  • [9] Liu C., Zhu K., Liu B., Et al., Dynamic tension of iced conductor galloping, Journal of Vibration and Shock, 31, 5, pp. 82-86, (2012)
  • [10] Yan Z., Li Z., Yang Z., Finite element modeling of transmission line galloping based on 6-DOFs nodes, Journal of Vibration and Shock, 30, 8, pp. 112-117, (2011)