Automatic Processing of Single-phase Grounding Fault in Distribution Network Based on Fault Phase Grounding

被引:0
|
作者
Liu J. [1 ,2 ]
Zhang Z. [1 ,2 ]
Li Y. [2 ]
Rui J. [3 ]
机构
[1] School of Automation and Information Engineering, Xi'an University of Technology, Xi'an
[2] State Grid Shaanxi Electric Power Research Institute, Xi'an
[3] Anhui Onesky Electric Technology Company Limited, Hefei
基金
中国国家自然科学基金;
关键词
Arc extinction; Distribution network; Fault-phase grounding; Neutral point non-effective grounding; Service restoration; Single-phase grounding fault isolation; Single-phase grounding fault line selection; Single-phase grounding fault location;
D O I
10.7500/AEPS20190730008
中图分类号
学科分类号
摘要
To solve the problem of single-phase grounding fault processing for neutral point non-effective grounding in distribution network, an automatic processing scheme for single-phase grounding faults in distribution network based on fault-phase grounding approach is proposed. The automation system consists of a fault-phase grounding arc-extinguishing line selection device in the substation and fault-phase grounding start-up protection devices deployed to the feeder switches. By adopting the fault-phase grounding method to achieve the reliable arc-extinguishing of single-phase grounding faults, the characteristics of zero-sequence voltage and zero-sequence current variations before and after the fault-phase grounding disconnection are used to achieve the line selection, location and isolation of permanent single-phase grounding fault and power restoration of sound district. By analyzing the variations of zero-sequence voltage and zero-sequence current of the system before and after the fault-phase grounding disconnection, a single-phase grounding line selection and location criterion based on the fundamental zero-sequence current ratio before and after the fault-phase grounding disconnection is constructed. The key technical problems, such as the start-up criterion for single-phase grounding fault processing, the detecting of the fault-phase grounding disconnection moment, and the necessity of throwing in a resistance to the neutral point before the fault-phase grounding disconnection are discussed in detail. Combined with an example, the proposed processing process for single-phase grounding fault is explained and experimental verification is carried out. The results show the feasibility and effectiveness of the proposed method. © 2020 Automation of Electric Power Systems Press.
引用
收藏
页码:169 / 177
页数:8
相关论文
共 20 条
  • [1] YAO Huannian, CAO Meiyue, The resonant grounding in electric power system, (2009)
  • [2] XU Bingyin, XUE Yongduan, FENG Guang, Et al., Discussion on several problems of earthing fault protection in distribution network, Automation of Electric Power Systems, 43, 20, pp. 1-7, (2019)
  • [3] QI Zheng, YANG Yihan, Analysis of technology of fault line selection for single-phase-to-earth faults in neutral point non-effective grounded system, Automation of Electric Power Systems, 28, 14, pp. 1-5, (2004)
  • [4] TANG Jinrui, YIN Xianggen, ZHANG Zhe, Et al., Survey of fault location technology for distribution networks, Electric Power Automation Equipment, 33, 5, pp. 7-13, (2013)
  • [5] SUONAN Jiale, LI Zongpeng, WANG Li, Et al., Fault line selection in distribution networks based on parameter identification method in frequency domain, Automation of Electric Power Systems, 36, 23, pp. 93-97, (2012)
  • [6] XUE Yongduan, LI Tianyou, LI Weixin, Et al., A novel method of transient analysis and faulty section location for single-phase earth fault in non-effectively earthed network, Automation of Electric Power Systems, 38, 23, pp. 101-107, (2014)
  • [7] SONG Guobing, LI Guang, YU Yeyun, Et al., Single-phase earth fault section location based on phase current fault component in distribution network, Automation of Electric Power Systems, 35, 21, pp. 84-90, (2011)
  • [8] GUO Linhui, LIU Yadong, WANG Peng, Et al., Single-phase grounding fault recognition in distribution networks based on phase-space reconstruction and average conductance characteristics, Automation of Electric Power Systems, 43, 7, pp. 192-198, (2019)
  • [9] DONG Xinzhou, WANG Jun, SHI Shenxing, Principle and algorithm of traveling waves based single-phase-to-ground protection for distribution lines, Proceedings of the CSEE, 33, 10, pp. 154-160, (2013)
  • [10] FAN Shuxian, XU Bingyin, ZHANG Qingzhou, A new method for fault line selection in distribution system with arc suppression coil grounding with square-wave signal injection, Automation of Electric Power Systems, 36, 4, pp. 91-95, (2012)