Generalized Composite Load Mode of Distribution Network Considering Battery Energy Storage System

被引:0
作者
Qu X. [1 ]
Li X. [2 ]
Sheng Y. [1 ]
Xiao J. [1 ]
Xu Z. [1 ]
机构
[1] School of Electrical Engineering, University of South China, Hengyang
[2] School of Electrical and Information Engineering, Hunan University, Changsha
来源
Gaodianya Jishu/High Voltage Engineering | 2020年 / 46卷 / 02期
关键词
Battery energy storage system; Generalized composite load model; Generalized load; Load modeling; Power system;
D O I
10.13336/j.1003-6520.hve.20200131013
中图分类号
学科分类号
摘要
We studied the generalized composite load model for distribution network containing a battery energy storage system (BESS) to participate in power grid simulation, expounded the simulation mathematical model of BESS, and established a BESS simulation platform based on MATLAB/Simulink. Through the simulation analysis of transient operation characteristics of BESS, we put forward and verified a load-oriented BESS equivalent model, and then proposed a generalized composite load model of distribution network considering BESS, which is composed of the BESS equivalent model and the classical composite load model in parallel. Finally, the validity and parameter value stability of the proposed generalized integrated load model are verified by multi-scenario simulation analyses. © 2020, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:490 / 499
页数:9
相关论文
共 22 条
  • [1] Cai J., Xu Q., Yuan X., Et al., Configuration strategy of large-scale battery storage system orienting wind power consumption based on temporal scenarios, High Voltage Engineering, 45, 3, pp. 993-1001, (2019)
  • [2] Jin W., Xu S., Zhang D., Et al., Application and response time test of MW-level battery energy storage system used in PV power station, High Voltage Engineering, 43, 7, pp. 2425-2432, (2017)
  • [3] Yang X., Dong D., Li X., Et al., Active power coordinated control strategy of peak load shifting for energy storage, Power System Technology, 42, 8, pp. 2551-2561, (2018)
  • [4] Li S., Li X., Huang J., Et al., Capacity configuration of lithium titanate battery in whole grid frequency regulation based on rate characteristic, High Voltage Engineering, 44, 1, pp. 145-151, (2018)
  • [5] Li X., Deng T., Huang J., Et al., Battery energy storage systems self-adaptation control strategy in fast frequency regulation, High Voltage Engineering, 43, 7, pp. 2362-2369, (2017)
  • [6] Li W., Wu F., Duan J., Et al., Decouple control strategy of dynamic active power and reactive power for storage energy-type power compensation system, High Voltage Engineering, 41, 7, pp. 2165-2172, (2015)
  • [7] Wei X., Li X., Qian J., Et al., Power system transient stability emergency control method assisted by energy storage, Transactions of China Electrical Society, 32, 18, pp. 286-300, (2017)
  • [8] Sun B., Yang S., Liu Z., Et al., Optimall bi-level configuration method for battery energy storage system assisting AGC of single thermal power unit, Automation of Electric Power Systems, 43, 8, (2019)
  • [9] Implementation of the first distribution side energy storage power station in Quzhou, Zhejiang Province
  • [10] Operation of the first energy storage device on the distribution network side of China Southern Power Grid