Impedance boundary analysis of distributed generation system based on VSG control

被引:0
|
作者
Chen J. [1 ]
Li Z. [1 ]
Zhang Q. [2 ]
Cai X. [2 ]
Xiong K. [2 ]
机构
[1] College of Information Science and Technology, Donghua University, Shanghai
[2] School of Electronic Information and Electrical Engineering, Shanghai Jiao Tong University, Shanghai
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2019年 / 47卷 / 21期
基金
中国国家自然科学基金;
关键词
Power decoupling; Power transmission limit; Small signal stability; System load change; Virtual impedance;
D O I
10.19783/j.cnki.pspc.181413
中图分类号
学科分类号
摘要
To solve the issue of operational stability of a distributed generation system controlled by Virtual Synchronous Generator (VSG) method when it is integrated into distributed grid, a method to determine the impedance boundaries of a grid-connected VSG controlled converter is proposed. And the impedance boundary conditions are deduced which can satisfy the power control performance, stability limit, system load allowable range and small signal stability of the grid-connected converter at the same time. A configuration method of virtual impedance is then proposed which makes the system have both good dynamic control performance and stability. The Matlab/Simulink simulation results verify the effectiveness of the system impedance boundary and the virtual impedance configuration method. Some results of experimental cases are also given. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:30 / 40
页数:10
相关论文
共 26 条
  • [11] Liu F., Zhang X., Shi R., An output impedance decoupled control strategy for high power microgrid inverter, Automation of Electric Power Systems, 39, 15, pp. 117-125, (2015)
  • [12] Wu K.D., Wu J.C., Jou H.L., Et al., Simplified control method for parallel-connected DC/AC inverters, IEEE Proceedings-Electric Power Application, 153, 6, pp. 787-792, (2006)
  • [13] Zhang Q., Peng C., Chen Y., Et al., A control strategy for parallel operation of multi-inverters in microgrid, Proceedings of the CSEE, 32, 25, pp. 126-132, (2012)
  • [14] He J., Li Y.W., Analysis, design, and implementation of virtual impedance for power electronics interfaced distributed generation, IEEE Transactions on Industry Applications, 47, 6, pp. 2525-2538, (2011)
  • [15] Tao L., Cheng J., Wang W., Et al., Methods of parameter design and optimization in virtual synchronous generator technology, Power System Protection and Control, 46, 12, pp. 128-135, (2018)
  • [16] Kong J., Jiang X., Wu J., Et al., Damping configuration of the virtual synchronous generator using gradient factor estimation, Power System Protection and Control, 46, 9, pp. 103-109, (2018)
  • [17] D'arco S., Suul J.A., Fosso O.B., Small-signal modelling and parametric sensitivity of a virtual synchronous machine, 2014 Power Systems Computation Conference (PSCC), pp. 1-9
  • [18] Wu H., Ruan X., Yang D., Et al., Modeling of the power loop and parameter design of virtual synchronous generators, Proceedings of the CSEE, 35, 24, pp. 6508-6518, (2015)
  • [19] Alipoor J., Miura Y., Ise T., Power system stabilization using virtual synchronous generator with alternating moment of inertia, IEEE Journals & Magazines, 3, 2, pp. 451-458, (2014)
  • [20] Wu X., Shen C., Iravani R., Feasible range and optimal value of the virtual impedance for droop- based control of microgrids, IEEE Transactions on Smart Grid, 8, 3, pp. 1242-1251, (2017)