A study on variation of properties of silicone rubber by swelling

被引:0
作者
Choe J.-W. [1 ]
Nam S.-H. [1 ]
Kim J.-G. [2 ]
机构
[1] Energy R and D Team, Product and Solution Research Center, LS Cable and System Ltd.
[2] Dept. of Electrical Engineering, Kyungpook National University
关键词
Insulating Oil; Outdoor Termination; Silicone Rubber; Swelling;
D O I
10.5370/KIEE.2019.68.9.1124
中图分类号
学科分类号
摘要
In order to build underground the transmission line, it is necessary to install outdoor terminations that connect overhead transmission lines and underground power cables. The inside of the outdoor termination is filled with insulating oil and a stress relief cone made of silicone rubber is assembled at the end of outer semiconducting layer. Insulating oil is heated to lower viscosity prior to injection, which requires additional equipments and more time. It is necessary to examine the influence of impregnated silicone rubber on the use of low-viscosity insulating oil that can be injected without heating. In this paper, we investigated how much silicone rubber swells depending on the viscosity of three different insulating oils. The mechanical and electrical properties such as tensile strength, elongation, volume resistivity, relative permittivity, etc., of the fully swollen silicone rubber were measured. In addition, the chemical analyzes of the fully swollen silicone rubber through FTIR and TGA were performed. Copyright © The Korean Institute of Electrical Engineers
引用
收藏
页码:1124 / 1128
页数:4
相关论文
共 10 条
[1]  
Orella J., Barriocanal M., Cabero R., Undergrounding and reorganization of the electrical system of the city of madrid, Jicable 07, pp. A2-A5, (2007)
[2]  
Son J., A Study on the Efficient Relocation Process of the Converting Overhead Transmission Lines to Underground Transmission Lines, pp. 6-7, (2014)
[3]  
Accessories for HV Cables with Extruded Insulation, (2001)
[4]  
Weinlein A., Peters U., Laage U., Memmer H., Worldwide experiences and challenges with EHV XLPE cable projects 330 kV to 500 kV, Jicable, 15, (2015)
[5]  
Oono K., Kaneko S., Takaoka I., Development of Dry Type Outdoor Termination for 66-110kV XLPE Cable, (2007)
[6]  
Physical Test Methods for Vulcanized Rubber, (2018)
[7]  
Underground Power Cable System, (2002)
[8]  
Abe K., Maeda T., Shimonaka T., Umemura T., A swelling characteristics of PET in oil, Proc. Of Conference on Electrical Insulation and Dielectric Phenomena Annual Report, pp. 753-758, (1992)
[9]  
Standard Test Methods for DC Resistance or Conductance of Insulating Material, (2007)
[10]  
Standard Test Methods for AC Loss Characteristics and Permittivity (Dielectric Constant) of Solid Electrical Insulation, (1998)