Study on the cycle performance of salt solution-storage-based heat pump

被引:0
|
作者
Chang M. [1 ]
Wang L. [1 ]
Yuan J. [1 ]
Cao Y. [1 ]
机构
[1] Institute of Building Energy and Thermal Science, Henan University of Science and Technology, Henan, Luoyang
来源
Huagong Xuebao/CIESC Journal | 2023年 / 74卷
关键词
coefficient of performance; economy; energy storage; heat pump; salt solution; thermodynamics;
D O I
10.11949/0438-1157.20221620
中图分类号
学科分类号
摘要
In order to solve the problem of electricity demand peak and valley in heating period, a solution-based energy-stored heat pump (SEHP) is proposed, which is composed of compression heat pump subsystem and salt solution subsystem with energy storage and release to realize thermal storage and thermal grade improvement. The multi-layer liquid storage units are used to optimize the design of salt solution storage tank to improve the energy storage density. Based on the thermodynamic model of the new cycle, the effect of key operating parameters on the performance of SEHP are studied, and its economy makes comparisons with that of the air-source energy-stored heat pump (AEHP) and the air-source heat pump (ASHP). The results show that the comprehensive heating coefficient of performance (CCOP) of the new cycle is lower than that of AEHP and ASHP, but its energy storage density (ESD) and economy are better than those of the two conventional heat pumps. At 300 kW heating load, although CCOP of SEHP is 4.76% lower than that of AEHP, ESD of SEHP is 2.2 times higher than that of AEHP, while the annual cost of AEHP is 1.46% and 29.00% lower than that of AEHP and ASHP respectively. © 2023 Chemical Industry Press. All rights reserved.
引用
收藏
页码:329 / 337
页数:8
相关论文
共 30 条
  • [1] Mahmoud M, Ramadan M, Naher S, Et al., The impacts of different heating systems on the environment: a review, Science of the Total Environment, 766, (2021)
  • [2] Hasnain S M., Review on sustainable thermal energy storage technologies(Part Ⅱ): Cool thermal storage, Energy Conversion and Management, 39, 11, pp. 1139-1153, (1998)
  • [3] Zhang X L., Air Conditioning Cold and Heat Storage Technology, (2006)
  • [4] Qu S L, Ma F, Ji R, Et al., System design and energy performance of a solar heat pump heating system with dual-tank latent heat storage, Energy and Buildings, 105, pp. 294-301, (2015)
  • [5] Dincer I, Dost S, Li X G., Performance analyses of sensible heat storage systems for thermal applications, International Journal of Energy Research, 21, 12, pp. 1157-1171, (1997)
  • [6] Xin Y Z, Song S P, Qu Z G., Application of air-source heat pump and water chiller coupled with water energy storage system to a project, Heating Ventilating & Air Conditioning, 52, 1, pp. 24-29, (2022)
  • [7] Qi Y S, Yue Y L, Liu T Y, Et al., Application analysis of combined ground-source heat pump and water energy storage systems, Heating Ventilating & Air Conditioning, 40, 5, pp. 94-97, (2010)
  • [8] Gong X X., The running technical and economic analysis of sewage-source heat pump+water storage system, (2015)
  • [9] Gil A, Medrano M, Martorell I, Et al., State of the art on high temperature thermal energy storage for power generation (Part 1): Concepts, materials and modellization, Renewable and Sustainable Energy Reviews, 14, 1, pp. 31-55, (2010)
  • [10] Zhang X L, Wang W, Li Z W, Et al., Experimental study of a phase change material and combined thermal energy storage with heat recovery, Chinese Journal of Refrigeration Technology, 32, 2, pp. 15-18, (2012)