Overview of LCC-HVDC Transmission System Equivalent Technology Based on Dynamic Phasor

被引:0
|
作者
Wang B. [1 ]
He X. [1 ]
机构
[1] State Key Lab of Control and Simulation of Power Systems and Generation Equipments, Tsinghua University, Haidian District, Beijing
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2024年 / 44卷 / 01期
基金
中国国家自然科学基金;
关键词
commutation failure; dynamic phasor; equivalent calculation; HVDC;
D O I
10.13334/j.0258-8013.pcsee.221488
中图分类号
学科分类号
摘要
Based on the AC bus at the receiving end of the inverter side converter station, the single end equivalence of the LCC-HVDC transmission system is of great significance for the optimal design of relay protection, stability control and DC control and protection. To obtain the high accuracy and real-time of calculation at the same time, the dynamic phasor model is used as an important way to realize the double terminal equivalence of LCC-HVDC transmission line at the expense of low simulation accuracy. However, there are still many problems in the single terminal equivalence of LCC-HVDC transmission system. To solve this problem, this paper analyzes the application value, requirements and difficulties of LCC-HVDC transmission system equivalence based on dynamic phasor, reviews the existing research status and existing problems from four factors in the equivalence calculation model, such as early trigger angle calculation, commutation overlap angle calculation, commutation failure discrimination and its influence on switching function and signal modulation, and puts forward follow-up research suggestions. ©2024 Chin.Soc.for Elec.Eng.
引用
收藏
页码:58 / 71
页数:13
相关论文
共 47 条
  • [1] DONG Xinzhou, TANG Yong, BU Guangquan, Confronting problem and challenge of large scale AC-DC hybrid power grid operation[J], Proceedings of the CSEE, 39, 11, pp. 3107-3118, (2019)
  • [2] LI Yan, TENG Yun, Security and stability analysis method for AC/DC UHV power system cascading failure based on improved risk assessment[J], High Voltage Engineering, 44, 11, pp. 3743-3750, (2018)
  • [3] ZHANG Xiaohua, XU Wei, WU Feng, Intelligent method for characteristic event tracing and prediction of cascading failures in AC/DC hybrid power grid[J], Automation of Electric Power Systems, 45, 10, pp. 17-24, (2021)
  • [4] LI Wenbo, ZHU Yuanzhen, LIU Yutian, Search model and correlation analysis for cascading failures in AC/DC hybrid power system[J], Automation of Electric Power Systems, 42, 22, pp. 59-68, (2018)
  • [5] SUN Huadong, CHEN Shuyong, CHANG Xiaopeng, A tracing algorithm of thevenin equivalent parameters for power systems with large disturbance[J], Proceedings of the CSEE, 32, 22, pp. 126-132, (2012)
  • [6] WANG Bin, LI Zhizhong, DONG Xinzhou, Real-time rapid simulation method for transient response of LCC-HVDC based on dynamic phasor method[J], Proceedings of the CSEE, 41, 5, pp. 1608-1617, (2021)
  • [7] SHAN Junru, LIU Chongru, LI Huan, Closed-loop dynamic phasor simulation model of LCC-HVDC considering phase-locked loop and commutation failure [J], Proceedings of the CSEE, 41, 9, pp. 3046-3055, (2021)
  • [8] QIU Xiaoyan, LI Xingyuan, WANG Jian, Power system equivalent in real time and voltage stability analysis[J], Power System Technology, 28, 7, pp. 7-9, (2004)
  • [9] TANG Yong, YI Jun, Calculation method for thevenin equivalent parameters based on time domain simulation[J], Proceedings of the CSEE, 30, 34, pp. 63-68, (2010)
  • [10] LI Weixing, MOU Xiaoming, LI Zhimin, Analysis and thoughts on the thevenin equivalent parameters for power systems[J], Proceedings of the CSEE, 32, S1, pp. 28-34, (2012)