An Alternative Reinforcement Learning (ARL) control strategy for data center air-cooled HVAC systems

被引:0
|
作者
Lu, Ruyuan [1 ]
Li, Xin [1 ]
Chen, Ronghao [1 ]
Lei, Aimin [2 ]
Ma, Xiaoming [1 ]
机构
[1] Peking Univ, Sch Environm & Energy, Shenzhen 518055, Peoples R China
[2] Vertiv Tech Co Ltd, Shenzhen 518055, Peoples R China
关键词
Reinforcement learning (RL); Deep deterministic policy gradient (DDPG); Proximal policy optimization (PPO); Air-cooled HVAC systems; Data center; ENERGY; INTERNET; COMFORT;
D O I
10.1016/j.energy.2024.132977
中图分类号
O414.1 [热力学];
学科分类号
摘要
Energy efficiency of data center is of great concern globally due to their large amount of energy consumption and the foreseeable growth in the demand of digital services in the future. Advanced control strategies are needed to reduce energy consumption. However, the optimization of data center HVAC control is a challenge task due to the complexity of the thermal dynamic models of buildings and uncertainties associated with both server loads and outdoor temperature. In this paper, we propose a new control strategy called Alternately- Reinforcement Learning-control(ARL), which realizes the alternating control of RL and proportional, integral and derivative (PID) for optimizing the control of air-cooled HVAC systems in data centers. The control object of the ARL is the speed set of the compressor and the condensing fan, and the control goal is to minimize energy consumption while maintaining temperature stability. The applied RL algorithm is Deep deterministic policy gradient (DDPG) and Proximal policy optimization (PPO). We pre-train the ARL strategy in offline environment firstly and deploy it in real data center environment for online testing. The test results show that the ARL has significant advantages in maintaining temperature stability while reducing energy consumption, and the PPO algorithm performs better than the DDPG algorithm. Compared with the PID algorithm, the PPO algorithm can save energy by 5.27%, and the temperature control effect can be improved by 3.27%,which indicates the feasibility of the ARL for implementation in real data centers.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Deep Reinforcement Learning for Tropical Air Free-cooled Data Center Control
    Duc Van Le
    Wang, Rongrong
    Liu, Yingbo
    Tan, Rui
    Wong, Yew-Wah
    Wen, Yonggang
    ACM TRANSACTIONS ON SENSOR NETWORKS, 2021, 17 (03)
  • [2] Retrofitting of an air-cooled data center for energy efficiency
    Kuzay, Mustafa
    Dogan, Aras
    Yilmaz, Sibel
    Herkiloglu, Oguzhan
    Atalay, Ali Serdar
    Cemberci, Atilla
    Yilmaz, Cagatay
    Demirel, Ender
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 36
  • [3] Quantitative comparison of alternative control schemes for air-cooled condensers
    Luyben, WL
    AICHE JOURNAL, 2006, 52 (02) : 611 - 622
  • [4] Reinforcement Learning for Control of Building HVAC Systems
    Raman, Naren Srivaths
    Devraj, Adithya M.
    Barooah, Prabir
    Meyn, Sean P.
    2020 AMERICAN CONTROL CONFERENCE (ACC), 2020, : 2326 - 2332
  • [5] An air-cooled system with a control strategy for efficient battery thermal management
    Chen, Kai
    Zhang, Zhenli
    Wu, Bingheng
    Song, Mengxuan
    Wu, Xiaoling
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [6] A data-driven subspace predictive control method for air-cooled data center thermal modelling and optimization
    Li Z.
    Wang H.
    Fang Q.
    Wang Y.
    Journal of the Franklin Institute, 2023, 360 (05) : 3657 - 3676
  • [7] Control-oriented modeling and optimization for the temperature and airflow management in an air-cooled data-center
    Qiu Fang
    Jiakang Zhou
    Shi Wang
    Yaonan Wang
    Neural Computing and Applications, 2022, 34 : 5225 - 5240
  • [8] Control-oriented modeling and optimization for the temperature and airflow management in an air-cooled data-center
    Fang, Qiu
    Zhou, Jiakang
    Wang, Shi
    Wang, Yaonan
    NEURAL COMPUTING & APPLICATIONS, 2022, 34 (07): : 5225 - 5240
  • [9] ASHRAE's Data Center Thermal Guidelines- Air-Cooled Evolution
    Quirk, David
    Davidson, Tom
    Schmidt, Roger
    ASHRAE Journal, 2022, 64 (05) : 54 - 60
  • [10] ASHRAE's Data Center Thermal Guidelines- Air-Cooled Evolution
    Quirk, David
    Davidson, Tom
    Schmidt, Roger
    ASHRAE JOURNAL, 2022, 64 : 54 - 58