Short-circuit current of a hydropower plant with consideration of constant switching and fault arc voltages

被引:0
作者
Brankovic, Darko [1 ]
Schuerhuber, Robert [1 ]
机构
[1] Graz Univ Technol, Inst Elect Power Syst, Graz, Austria
关键词
arcs (electric); fault currents; IEC standards; IEEE standards; short-circuit currents; synchronous machines; DELAYED CURRENT ZEROS; MODEL; ANSI; SIMULATION;
D O I
10.1049/gtd2.13297
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The correct generator circuit breaker (GCB) dimensioning is essential for the safe and reliable operation of a power plant or generation system. The dimensioning is usually based on standardized calculation methods according to standards (IEC standard 60909-0, IEC/IEEE standard 62271-37-013, IEEE Std C37), often supplemented by selected transient calculations. A non-systematic approach can often be observed here, which does not adequately take into account significant influencing variables or operating states of the generator. This article therefore systematically examines various parameters that influence the short-circuit current components of the generator and are relevant for the dimensioning of the generator circuit-breaker: short-circuit angle, operating point, impedance ratios, phase clearing, switching arc, and fault arc. The results of the current parameters most relevant to the dimensioning of the GCB were then compared for different calculation methods. Special attention was paid to the effect of the switching and fault arc, which were modelled as a constant arc voltage, and its effect on the short-circuit currents is systematically recorded. This work aims to summarize all relevant variables that influence the generator short-circuit current and are relevant for the dimensioning of the GCB and to present the different results based on a short-circuit calculation according to the standard and transient calculation to create a basis for a proper dimensioning of the generator circuit breaker. This paper makes several key contributions, including providing a comprehensive summary of influential factors in evaluating short-circuit current for accurate and reliable GCB dimensioning. It uniquely represents all relevant short-circuit parameters across the entire operating range of the synchronous machine, demonstrating the impact of switching arc voltage on maximum fault clearing time for various switch technologies. Additionally, it analyses the influence of switching and fault arcs on short-circuit current from the perspective of GCB dimensioning. image
引用
收藏
页码:3476 / 3486
页数:11
相关论文
共 43 条
[1]  
BERIZZI A, 1993, IAS 93, PTS 1-3, P1420, DOI 10.1109/IAS.1993.299168
[2]  
Bonfert K., 1962, Betriebsverhalten der Synchronmaschine Bedeutung der Kenngrssen fr Planung und Betriebe elektrischer Anlagen und Antriebe
[3]  
Brinkhoff R., 1978, ELEKTRIZITTSWIRTSCHA, V77, P22
[4]  
Browne T.E., 1984, ELECT ENG ELECT, V21
[5]   Delayed current zeros due to out-of-phase synchronizing [J].
Canay, IM ;
Braun, D ;
Koppl, GS .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1998, 13 (02) :124-132
[7]  
Canay M., 1974, BROWN BOVERI REV, V61
[8]  
Canay M., 1969, BROWN BOVERI REV
[9]  
Cassie A., 1939, Cigre Reports, V102, P588
[10]  
CASTELLIDEZZA F, 1994, EUR T ELECTR POW, V4, P213