Analyzing the Progressive Collapse of a 230 KV Power Transmission Line Tower Structure and Investigation of the Effect of Environmental Factors

被引:0
|
作者
Ferdowsi, Farideh [1 ]
Hashemi, Seyed Shaker [1 ]
Sadeghi, Kabir [2 ]
Dashti, Rahman [3 ]
机构
[1] Persian Gulf Univ, Dept Civil Engn, Mahini St,POB 75169-13817, Bushehr, Iran
[2] Near East Univ, Dept Civil Engn, Mersin 10, Lefkosa 99138, Turkiye
[3] Persian Gulf Univ, Dept Elect Engn, Mahini St,POB 75169-13817, Bushehr, Iran
关键词
Progressive collapse; electrical power transmission tower; nonlinear dynamic analysis; wind and ice loads; LARGE-DEFORMATION ANALYSIS; FAILURE;
D O I
10.1142/S0219455425502219
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Electricity transmission lines constitute a vital element in any electrical power system. Nevertheless, the progressive collapse of these structures caused by accidental events and cascade failure can lead to a wide range of failures, including total collapse. The failure of power transmission line structures due to extreme wind and ice loads poses a substantial challenge for electrical power distribution companies globally. In this study, the progressive collapse behavior of a 230-kV electrical power transmission line in Fars Province, Iran was evaluated utilizing the alternative load path method within a nonlinear dynamic analysis framework. Finite element models of a tangent electricity tower (DC0), a terminal tower (DC90), and the conductors of the transmission line were created and simulated using SAP2000 software. The investigation focused on the impact of removing the legs of the transmission tower, and the simulation analyzed the progressive collapse behavior under various loading conditions, including wind load, snow-induced freezing, and simultaneous wind and ice load. By employing the nonlinear dynamic analysis of the progressive collapse, the stresses developed in the structural elements were evaluated, and the damaged elements were identified. The results demonstrated that following the failure of one leg, the tangent and terminal towers remained stable under gravitational loads. However, under extreme winds at a 90 degrees angle, the failure of a leg resulted in significant damage to the towers. Further assessment of the tangent and terminal towers revealed that the terminal tower exhibited higher strength compared to the tangent tower. This was evident in the lower dispersion of displacements and a reduced number of damaged elements observed in the terminal tower when one leg was removed.
引用
收藏
页数:26
相关论文
共 30 条
  • [21] Progressive collapse analysis of long-span transmission tower-line system under multi-component seismic excitations
    Tian, Li
    Ma, Ruisheng
    Pan, Haiyang
    Qiu, Canxing
    Li, Wenfeng
    ADVANCES IN STRUCTURAL ENGINEERING, 2017, 20 (12) : 1920 - 1932
  • [22] Tower foundation selection and economic comparison of 110kV transmission line in plain area of South Hebei Power Grid
    Ren Yaning
    Gao Fan
    Zhang Deguang
    Shen Xiangliang
    Yin Siyuan
    2020 3RD INTERNATIONAL CONFERENCE ON COMPUTER INFORMATION SCIENCE AND APPLICATION TECHNOLOGY (CISAT) 2020, 2020, 1634
  • [23] The Effect Analysis of Strain Rate on Power Transmission Tower-Line System under Seismic Excitation
    Tian, Li
    Wang, Wenming
    Qian, Hui
    SCIENTIFIC WORLD JOURNAL, 2014,
  • [24] Electromagnetic environment influence factors of quadruple-circuit transmission line with 1 000 kV/500 kV dual voltage on the same tower and optimization measures analysis
    Huang, Xueliang
    Wang, Yu
    Wen, Feng
    Gaodianya Jishu/High Voltage Engineering, 2015, 41 (11): : 3642 - 3650
  • [25] Wind-induced collapse analysis of long-span transmission tower-line system considering the member buckling effect
    Tian, Li
    Pan, Haiyang
    Qiu, Canxing
    Ma, Ruisheng
    Yu, Qiqi
    ADVANCES IN STRUCTURAL ENGINEERING, 2019, 22 (01) : 30 - 41
  • [26] Study on Environmental Impact Calculation of 500kV UHV AC Transmission Line Power Frequency Electric Field
    Wang, Zhining
    Chen, Zhang
    PROCEEDINGS OF THE 2016 5TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND ENVIRONMENT ENGINEERING (ICSEEE 2016), 2016, 63 : 770 - 774
  • [27] Influence of Coupling Factors on Mechanical Property of High Voltage Transmission Tower-line Structure Under Ice Loading
    Zhao M.
    He B.
    Feng W.
    Wang Y.
    Feng L.
    Wang C.
    2018, Chinese Society for Electrical Engineering (38): : 7141 - 7148
  • [28] Research on Calculation of Bearing Force of Composite Insulation Cross Arm Pressure Rod of 220kV Power Transmission Line Pole Tower
    Xing, Haijun
    Zhu, Binrong
    Zhu, Minjie
    Wang, Xingjie
    Zhang, Zhijun
    Chen, Bin
    2020 6TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY, ENVIRONMENT AND CHEMICAL ENGINEERING, PTS 1-5, 2020, 546
  • [29] Analyzing the Characteristics of Faults in a Transmission Line and High Voltage Capacitor Banks in a 115-kV-Power System Using Discrete Wavelet Transform
    Chiradeja, Pathomthat
    Ngaopitakkul, Atthapol
    IEEE ACCESS, 2022, 10 : 86765 - 86781
  • [30] Investigation of power regimes of Southern Eectrical Networks of 110 kV in case of disconnecting of the high voltage electric transmission line of 400 kV of Moldavian condensed power plant (MCPP) - Vulcaneshty
    Postolaty, V. M.
    Bicova, E. V.
    PROBLEMELE ENERGETICII REGIONALE, 2009, (01): : 25 - 41