A single-ended high-impedance fault protection scheme for hybrid HVDC transmission lines based on coordination of control objective

被引:1
|
作者
Ma, Ruizhi [1 ]
Chen, Yu [1 ]
Wen, Minghao [1 ]
Han, Ke [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Technol, Wuhan 430074, Peoples R China
基金
中国国家自然科学基金;
关键词
Hybrid HVDC; High-impedance fault; FRT; Single-ended protection; Coordination of converter control objective; GRIDS;
D O I
10.1016/j.ijepes.2024.110187
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Hybrid HVDC transmission technology advancement has led to significant progress. A reliable and effective DC line protection scheme is crucial for DC transmission systems. The traditional protection schemes suffer from insufficient sensitivity and reliability during high-impedance faults on DC lines. To address the issue, this study introduces a hybrid HVDC line single-ended protection scheme based on the coordination of converter control objectives. In the fault-ride-through(FRT) stage, different control strategies and objectives are applied to the converter based on the fault pole and fault direction identification results. Internal and external faults are discerned by calculating measured voltage with the coordination of the converter control objective. This approach maintains heightened sensitivity to high-impedance DC line faults. Moreover, it operates independently of double-ended communication and demands a low sampling rate. Extensive simulation results robustly substantiate the efficacy of the proposed protection scheme.
引用
收藏
页数:10
相关论文
共 26 条
  • [1] A Whole-Line Fast Protection Scheme for HVDC Transmission Line Based on Single-Ended Boundary Energy
    Yang Y.
    Tai N.
    Xie W.
    Zheng X.
    Ma J.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2023, 38 (09): : 2403 - 2417
  • [2] Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
    Shu, Hongchun
    Wang, Shixin
    Lei, Shunguang
    PROTECTION AND CONTROL OF MODERN POWER SYSTEMS, 2023, 8 (01)
  • [3] Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band
    Hongchun Shu
    Shixin Wang
    Shunguang Lei
    Protection and Control of Modern Power Systems, 2023, 8
  • [4] Single-ended protection scheme for three-terminal hybrid DC transmission system based on refractive coefficients
    Wu, Chuanjian
    Li, Kuan
    Li, Chenhao
    Zhang, Yan
    Zhang, Xiaodong
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2024,
  • [5] Adaptive Single Ended Protection Scheme for parallel Transmission Lines
    Mourad, Dina
    Shehab Eldin, E. H.
    2017 NINETEENTH INTERNATIONAL MIDDLE-EAST POWER SYSTEMS CONFERENCE (MEPCON), 2017, : 1208 - 1215
  • [6] A Distributed High-Impedance Fault Detection and Protection Scheme in DC Microgrids
    Yadegar, Meysam
    Zarei, Seyed Fariborz
    Meskin, Nader
    Blaabjerg, Frede
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (01) : 141 - 154
  • [7] Single-ended Protection Scheme for Multi-terminal Hybrid DC Lines Based on Initial Current Traveling Wave Phase
    Dai Z.
    Niu B.
    Qiu H.
    Xi X.
    Han Z.
    Wei S.
    Gaodianya Jishu/High Voltage Engineering, 2024, 50 (02): : 649 - 659
  • [8] Distributed Parameters Model for High-impedance Fault Detection and Localization in Transmission Lines
    Torres, V.
    Maximov, S.
    Ruiz, H. F.
    Guardado, J. L.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2013, 41 (14) : 1311 - 1333
  • [9] High impedance fault protection in transmission lines using a WPT-based algorithm
    Mahari, Arash
    Seyedi, Heresh
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 67 : 537 - 545
  • [10] Single-Ended Remote Backup Protection Based on Fault Distance Factor of Traveling Wavefront
    Zhang, Chenhao
    Yan, Jifei
    Song, Guobing
    IEEE TRANSACTIONS ON POWER DELIVERY, 2025, 40 (02) : 1143 - 1157