Mechanically ventilated classrooms in central Italy's heritage school buildings: Proposal of archetypes and CO2 prediction models

被引:0
|
作者
Summa, Serena [1 ]
Remia, Giada [2 ]
Di Perna, Costanzo [2 ]
Stazi, Francesca [1 ]
机构
[1] Univ Politecn Delle Marche, Dept Sci & Engn Matter Environm & Urban Planning, Ancona, Italy
[2] Univ Politecn Delle Marche, Dept Ind Engn & Math Sci, Ancona, Italy
关键词
Classroom archetypes; Controlled mechanical ventilation; User behaviour; CO2 predictive model; INDOOR AIR-QUALITY; CARBON-DIOXIDE GENERATION; PERFORMANCE; EXPOSURE; POLLUTION; CHILDREN; COMFORT;
D O I
10.1016/j.buildenv.2024.111963
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study proposed a typological analysis to identify the archetypes of classrooms equipped with controlled mechanical ventilation (CMV) in Italy and an experimental campaign on 58 typical classrooms to identify the main indoor microclimatic characteristics and CO2 concentrations. From the analyses carried out, general information was gathered on the heating systems and the main energy and acoustic improvements carried out in the schools. The typological analysis identified four different types of mechanical ventilation systems installed in three different classroom archetypes: wide, square and deep, with percentages of window area of 25%, 30% and 40 % respectively. The field measurement campaign showed that, in terms of CO2 concentration, mechanical ventilation was effective in the winter period, while in the mid-season and summer periods, natural ventilation was predominant due to the opening of windows by the occupants. Furthermore, in the case of manual control, incorrect use of the machine by the occupants, who reported noise-related problems or insufficient user training, resulted in CO2 levels above the recommended limits. Multivariate regressions developed for schools equipped with CMVs predicted maximum and average CO2 concentrations as a function of minimum and maximum indoor and outdoor temperatures with a significance (R2, correct) of 76 % and 83 % respectively.
引用
收藏
页数:14
相关论文
共 3 条
  • [1] Estimating Air Change Rate in Mechanically Ventilated Classrooms Using a Single CO2 Sensor and Automated Data Segmentation
    Du, Bowen
    Reda, Ibrahim
    Licina, Dusan
    Kapsis, Costa
    Qi, Dahai
    Candanedo, Jose A.
    Li, Tianyuan
    ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2024, 58 (42) : 18788 - 18799
  • [2] An investigation on CO2 concentration based on field survey and simulation in naturally ventilated Nepalese school buildings during summer
    Shrestha, Mishan
    Rijal, H. B.
    Kayo, Genku
    Shukuya, Masanori
    BUILDING AND ENVIRONMENT, 2022, 207
  • [3] Mean Age of Air in Natural Ventilated Buildings: Experimental Evaluation and CO2 Prediction by Artificial Neural Networks
    Buratti, Cinzia
    Palladino, Domenico
    APPLIED SCIENCES-BASEL, 2020, 10 (05):