Crossflow microsand filtration in cooling tower systems to control fouling in heat exchanger devices

被引:1
|
作者
Ashok, Vaishali [1 ]
Absalan, Faezeh [1 ]
Silverwood, Alain [2 ]
Robert, Etienne [3 ]
Claveau-Mallet, Dominique [1 ]
Bedard, Emilie [1 ]
机构
[1] Polytech Montreal, Civil Geol & Min Engn Dept, Montreal, PQ, Canada
[2] Xylem Water Solut & Water Technol, Washington, DC USA
[3] Polytech Montreal, Mech Engn Dept, Montreal, PQ, Canada
来源
JOURNAL OF BUILDING ENGINEERING | 2024年 / 95卷
关键词
Side stream filtration; Building energy; HVAC; Clogging; BIOFILTRATION; CORROSION;
D O I
10.1016/j.jobe.2024.110167
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In the context of global warming, there is a growing need for high-performance heat, ventilation and air conditioning systems. Fouling is a challenge, affecting heat exchanger operational and energetic performance. Side stream filtration can be used to improve water quality by reducing particle concentration in the system. The aim of this study was to assess a crossflow microsand filtration unit's efficacy in reducing fouling within an 81-plate heat exchanger, in an in-situ cooling tower circuit. A pilot heat exchanger without filtration was operated under similar conditions. After 3 years of continuous operation, visual inspection of the full-scale heat exchanger plates operating with filtration showed minimal accumulation. Pairs of facing plates (7) were scraped and rinsed to collect total solids accumulated on surfaces. Samples were resuspended and analyzed for solids and metal concentration measurements. Low average values of total volatile solids (45 mu g/cm2) and total solids (93 mu g/cm2) were indicative of a low biofilm formation. X-ray diffraction revealed the presence of calcite associated to water hardness. Low levels of iron and copper were detected despite slightly corrosive water. In contrast, the pilot heat exchanger exhibited higher deposit accumulation of total volatile solids (90 mu g/cm2) and total solids (110 mu g/cm2) after only 12 weeks of operation. These findings underscore the role of side stream filtration in reducing particle deposition and biofouling potential in full-scale cooling tower systems. Crossflow microsand filtration is a promising avenue to control fouling in building cooling tower systems, which could contribute in improving the building's energetic performance.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Fouling mitigation in a heat exchanger: High cycles of concentration for a cooling-tower application
    Cho, YI
    Kim, WT
    Cho, D
    EXPERIMENTAL HEAT TRANSFER, 2006, 19 (02) : 113 - 128
  • [2] Oscillatory Fouling in Condensers in Cooling Tower Systems
    Li, Wei
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2020, 12 (02)
  • [3] Data-driven cooling tower optimization: A comprehensive analysis of energy savings using microsand filtration
    Lefebvre, Xavier
    Ashok, Vaishali
    Claveau-Mallet, Dominique
    Robert, Etienne
    Bedard, Emilie
    APPLIED THERMAL ENGINEERING, 2025, 258
  • [4] Effectiveness of crossflow plate heat exchanger for indirect evaporative cooling
    Stoitchkov, NJ
    Dimitrov, GI
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (06): : 463 - 471
  • [5] Hydrothermal stress coefficient: A novel model for predicting heat exchanger fouling in cooling systems
    DeWittDick, DB
    Hays, GF
    Beardwood, ES
    HEAT TRANSFER - BALTIMORE 1997, 1997, (214): : 311 - 316
  • [6] Use of electronic anti-fouling technology with filtration to prevent fouling in a heat exchanger
    Department of Mechanical Engineering and Mechanics, Drexel University, Philadelphia, PA 19104, United States
    Int. J. Heat Mass Transf., 19 (2961-2966):
  • [7] Use of electronic anti-fouling technology with filtration to prevent fouling in a heat exchanger
    Cho, YI
    Fan, CF
    Choi, BG
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1998, 41 (19) : 2961 - 2966
  • [8] Modeling oscillatory fouling in enhanced tubes in cooling tower systems
    Jie Wu
    Zhengjiang Zhang
    Lin Cheng
    Wei Li
    Zhiming Xu
    Heat and Mass Transfer, 2011, 47 : 563 - 569
  • [9] Modeling oscillatory fouling in enhanced tubes in cooling tower systems
    Wu, Jie
    Zhang, Zhengjiang
    Cheng, Lin
    Li, Wei
    Xu, Zhiming
    HEAT AND MASS TRANSFER, 2011, 47 (05) : 563 - 569
  • [10] Cooling tower fill fouling control in a geothermal power plant
    Yu, FP
    Ginn, LD
    McCoy, WF
    CORROSION REVIEWS, 1999, 17 (3-4): : 205 - 217