Investigation of Partial Discharge Transformation Characteristics in Polyimide (PI) Insulations under High-Frequency Electric Stress

被引:1
|
作者
Ayubi, Bilal Iqbal [1 ]
Zhang, Li [1 ]
Zhou, Shengrui [1 ]
Wang, Yiwei [1 ]
Zou, Liang [1 ]
机构
[1] Shandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
基金
中国国家自然科学基金;
关键词
partial discharge (PD); polyimide (PI); high-frequency insulation; high-frequency power transformers (HFPTs); plasma model; TEMPERATURE; SIMULATION; PRESSURE;
D O I
10.3390/polym16172450
中图分类号
O63 [高分子化学(高聚物)];
学科分类号
070305 ; 080501 ; 081704 ;
摘要
This research delves into the primary issue of polyimide (PI) insulation failures in high-frequency power transformers (HFPTs) by scrutinizing partial discharge development under high-frequency electrical stress. This study employs an experimental approach coupled with a plasma simulation model for a ball-sphere electrode structure. The simulation model integrates the particle transport equation, Poisson equation, and complex chemical reactions to ascertain microscopic parameters, including plasma distribution, electric field, electron density, electron temperature, surface, and space charge distribution. The effect of the voltage polarity and electrical energy on the PD process is also discussed. The contact point plays a pivotal role in triggering partial discharges and culminating in the breakdown of PI insulation. Asymmetry phenomena were found between positive and negative half-cycles by analyzing the PD data stage by stage. A significant number of PDs increased at every stage and the PD amplitude was higher during the negative cycle at the initial stage, but in later stages, the PD amplitude was found to be higher in the positive half-cycle, and scanning electron microscopy (SEM) revealed that the maximum damage occurred near the contact point junction. The simulation results show that the plasma initially accumulates the electron density near the contact point junction. Under the action of the electric field, plasma starts traveling at the PI surface outward from the contact point. Before the PD activity, all parameters have higher values in the plasma head. The microscopic parameters reveal maximum values near the contact point junction, during PD activities where significant damage takes place. These parameter distributions exhibit a decreasing trend over time as when the PD activity ends. The model's predictions are consistent with the experimental data. The paper lays the foundation for future research in polymer insulation design under high-frequency electrical stress.
引用
收藏
页数:18
相关论文
共 41 条
  • [1] Partial Discharge Characteristics of Polyimide Under the High-Frequency Multilevel Stepped Waveform
    Shao, Ruitao
    Jiang, Jun
    Chen, Wu
    Shen, Zhibang
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2025, 32 (02) : 1113 - 1122
  • [2] Molecular dynamics and finite element analysis of partial discharge mechanisms in polyimide under high-frequency electric stress
    Ayubi, Bilal Iqbal
    Zhang, Li
    Wang, Guan
    Wang, Yiwei
    Zhou, Shengrui
    POLYMER DEGRADATION AND STABILITY, 2025, 234
  • [3] Study on Temperature-Frequency Partial Discharge Characteristics of Polyimide under High Frequency Electrical Stress Based on Improved Variational Modal Decomposition Denoising
    Xu H.
    Zhang L.
    Ayubi B.I.
    Zou L.
    Wang G.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2023, 38 (03): : 565 - 576
  • [4] High-Frequency Partial Discharge Characteristics of Solid-State Transformer Interturn Multilayer Insulation Under Repetitive Electrical Stress
    Li, Zhihui
    Han, Yaoxuan
    Xie, Zengqi
    Ren, Hanwen
    Li, Qingmin
    Wang, Zhongdong
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2024, 71 (10) : 13331 - 13340
  • [5] Partial Discharge Analysis in High-Frequency Transformer Based on High-Frequency Current Transducer
    Jiang, Jun
    Zhao, Mingxin
    Zhang, Chaohai
    Chen, Min
    Liu, Haojun
    Albarracin, Ricardo
    ENERGIES, 2018, 11 (08)
  • [6] Partial Discharge Features for Power Electronic Transformers Under High-Frequency Pulse Voltage
    Jiang, Jun
    Zhang, Bendong
    Li, Zhi
    Ranjan, Prem
    Chen, Jiawei
    Zhang, Chaohai
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (02) : 845 - 853
  • [7] Influence Mechanism of Temperature on Partial Discharge Characteristics of Composite Insulation Interface Under High Frequency Electrical Stress
    Li Z.
    Xie Z.
    Ren H.
    Dong Z.
    Li Q.
    Wang Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (22): : 8965 - 8976
  • [8] Partial Discharge Investigation under Low Air Pressure and Variable Frequency for More-electric-aircraft
    Jiang, Jun
    Zhang, Bendong
    Li, Zhi
    Zhang, Chaohai
    Ranjan, Prem
    Zhag, Xiang
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (05) : 1793 - 1801
  • [9] Insulation Failure Mechanism of Polyimide Under High-Frequency Electrical Stress: A Synergistic Analysis of Aging Experiments and Molecular Dynamics Simulations
    Wang, Yiwei
    Xu, Huangkuan
    Ayubi, Bilal Iqbal
    Zhou, Shengrui
    Zhang, Li
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2025, 32 (01) : 246 - 253
  • [10] Modeling of High-Frequency Current Transformer Based Partial Discharge Detection in High-Voltage Cables
    Hu, Xiao
    Siew, Wah Hoon
    Judd, Martin D.
    Reid, Alistair J.
    Sheng, Bojie