Line Loss Anomaly Perception Method Based on MIC-IF Algorithm for Photovoltaic Low-Voltage Transformer Area

被引:0
|
作者
Zhang, Penghe [1 ]
Yang, Yining [1 ]
Song, Runan [1 ]
Wang, Bicheng [1 ]
Sheng, Jinhao [2 ]
Zhao, Bo [2 ]
机构
[1] China Elect Power Res Inst, Beijing 100192, Peoples R China
[2] Beijing Informat Sci & Technol Univ, Sch Automat, Beijing 100192, Peoples R China
来源
IEEE ACCESS | 2024年 / 12卷
关键词
Transformers; Photovoltaic systems; Electricity; Low voltage; Anomaly detection; Accuracy; Mathematical models; Anomaly perception; ensemble learning; line loss rate; maximal information coefficient; photovoltaic low-voltage transformer area;
D O I
10.1109/ACCESS.2024.3437368
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The topology and line parameters of low-voltage transformer area are often difficult to obtain, and distributed photovoltaic (PV) access makes the distribution grid's power flow characteristic changes, which leads to high difficulty in recognizing line loss anomalies in transformer areas. To address the above problems, a method for perceiving line loss anomaly in PV transformer area called MIC-IF is proposed. Based on this algorithm, the feature vectors of each transformer area are constructed by combining several operation indicators and line loss rate, and it is considered that the outlier vectors correspond to the transformer areas with abnormal operation states. After completing the judgment of the cause of anomalies, PV energy theft detection is carried out for areas in which the PV power generation is anomalous based on RUSBoost algorithm. Finally, the results of analysis are summarized and the conclusion on anomaly perception is obtained. The effectiveness of the proposed method is verified based on data from 20 simulation transformer areas, and the results show that the accuracy and F1-socre of MIC-IF reach 0.95 and 0.89, respectively, and are higher than the comparison algorithm. The detection framework takes into account the PV access and does not rely on line parameters, with high interpretability and accuracy, providing a certain reference for engineering applications.
引用
收藏
页码:108145 / 108153
页数:9
相关论文
共 7 条
  • [1] Calculation of Line Loss in Low-voltage Transformer District Based on BP Network Model Optimized by LM Algorithm
    Liu, Li-ping
    Li, Bai-qing
    Li, Ya
    Yi, Jun
    Zhang, Jian
    Wang, Qi
    2016 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE (EPEC), 2016,
  • [2] Assessment of Line Loss Rate in Low-Voltage Transformer District Based on BP Network Model Optimized by LM Algorithm
    Liu, Li-ping
    Li, Ya
    Li, Bai-qing
    Wang, Ze-zhong
    Tian, Shi-ming
    2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [3] SENSORLESS COMMUTATION METHOD FOR LOW-VOLTAGE BLDC MOTORS BASED ON UNFILTERED LINE VOLTAGE
    Mahdiyoun Rad, Shahin
    Azizian, Mohammad Reza
    Hejri, Mohammad
    ADVANCES IN ELECTRICAL AND ELECTRONIC ENGINEERING, 2019, 17 (01) : 1 - 12
  • [4] Power estimation method of low-voltage distributed photovoltaic generation based on similarity aggregation
    Chen, Xinhe
    Li, Shufeng
    Wang, Fangsheng
    Li, Jiping
    Tang, Chenghong
    ENERGY REPORTS, 2021, 7 : 1344 - 1351
  • [5] An Identification Method for Asymmetric Faults With Line Breaks Based on Low-Voltage Side Data in Distribution Networks
    Zichang, Li
    Yadong, Liu
    Yingjie, Yan
    Peng, Wang
    Xiuchen, Jiang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (06) : 3629 - 3639
  • [6] Information Fusion Method of Power Internet of Things Based on Low-Voltage Power Line and Micro-Power Wireless Communication
    Li, Wen-Jing
    Zhang, Nan
    Liu, Zhu
    Wang, Jian-Feng
    Guo, Yong-Shan
    Lv, Dongdong
    IEEE ACCESS, 2022, 10 : 89959 - 89969
  • [7] Monthly Probability Theoretical Line Loss Calculation Method of Low Voltage Distribution Network Based on Simultaneous Power and Electricity
    Feng, Yunzhao
    Long, Liangyu
    Qian, Jiayue
    IEEE ACCESS, 2023, 11 : 145792 - 145800