In-situ test and numerical investigation on the long-term performance of deep borehole heat exchanger coupled heat pump heating system

被引:3
作者
Liu, Bin [1 ,2 ]
Wang, Jiangfeng [1 ]
Li, Hongyan [1 ,2 ]
Liu, Jian [3 ]
Wang, Pengtao [1 ,2 ]
Cai, Wanlong [4 ]
Sun, Xianpeng [5 ]
Chen, Chaofan [6 ,7 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
[2] Sinopec Green Energy Geothermal Dev Co Ltd, Xianyang 712000, Peoples R China
[3] SINOPEC Star Petr Co Ltd, Beijing 100083, Peoples R China
[4] Xi An Jiao Tong Univ, Sch Human Settlements & Civil Engn, Xian 710049, Peoples R China
[5] North West Agr & Forestry Univ, Coll Hort, Xianyang 712100, Peoples R China
[6] Tech Univ Bergakad Freiberg, Geotech Inst, D-09599 Freiberg, Germany
[7] UFZ Helmholtz Ctr Environm Res, Permoserstr 15, D-04318 Leipzig, Germany
基金
中国国家自然科学基金; 中国博士后科学基金;
关键词
Deep borehole heat exchanger (DBHE); Field test; Performance evaluation; Long-term sustainability; Heat pump; FIELD-TEST; EFFICIENCY; SUSTAINABILITY; SIMULATION; CAPACITY; MODEL;
D O I
10.1016/j.csite.2024.104855
中图分类号
O414.1 [热力学];
学科分类号
摘要
Given the substantial initial investment required by the drilling and implementation of the Deep Borehole Heat Exchanger (DBHE), it becomes imperative to quantitatively evaluate its long-term performance and sustainability. This work introduces a pilot DBHE project in Xi'an, along with the 500-h in-situ monitored data, which is used to validate the 3D numerical model established and simulated in the OpenGeoSys (OGS) software. Based on the validated model, a series of extended scenarios are executed to evaluate the influence of design and operational parameters on the long-term performance and sustainability of the DBHE system. The results show that the drilling depth is the most significant factor that influences long-term performance. On the contrary, pipe diameter and inner pipe thermal conductivity have a very limited impact. A comprehensive evaluation is suggested to determine operational flow rates in real projects while considering the energy consumption by the circulation pump. Moreover, the heat extraction performance and energy analysis of the DBHE coupled with a geothermal heat pump under intermittent operation are also investigated. With a fixed daily heating demand, a longer daily operating time results in lower circulating temperature drops, which is advantageous for the heat pump's energy efficiency in long-term operation.
引用
收藏
页数:18
相关论文
共 50 条
  • [41] Experimental and numerical investigation on a new type of heat exchanger in ground source heat pump system
    Liu, Xichen
    Xiao, Yimin
    Inthavong, Kiao
    Tu, Jiyuan
    ENERGY EFFICIENCY, 2015, 8 (05) : 845 - 857
  • [42] Effects of building load characteristics on heating performance of the medium-deep U-type borehole heat exchanger coupled heat pumps: A coupled dynamic simulation
    Huang, Shuai
    Lin, Duotong
    Dong, Jiankai
    Li, Ji
    APPLIED ENERGY, 2025, 377
  • [43] Simulation-based analysis of a ground source heat pump system using super-long flexible heat pipes coupled borehole heat exchanger during heating season
    Wang, Xiaoyuan
    Wang, Yinfeng
    Wang, Zhi
    Liu, Yuxuan
    Zhu, Yuezhao
    Chen, Haijun
    ENERGY CONVERSION AND MANAGEMENT, 2018, 164 : 132 - 143
  • [44] Evaluation of the long-term performance of the deep U-type borehole heat exchanger on different geological parameters using the Taguchi method
    Jiang, Jinghua
    Wang, Fenghao
    Yang, Xiong
    Zhang, Yuping
    Deng, Jiewen
    Wei, Qingpeng
    Cai, Wanlong
    Chen, Chaofan
    JOURNAL OF BUILDING ENGINEERING, 2022, 59
  • [45] Heat Transfer Performance Analysis of Medium-Deep Coaxial Borehole Heat Exchanger: Combination of Heat Extraction Operation Test and Numerical Simulation
    Li, Jiangbo
    Lei, Yanzi
    Li, Lei
    Chen, Sihao
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2025, 17 (01)
  • [46] Numerical investigation on the heating performance of a transcritical CO2 vapor-injection heat pump system
    Peng, Xu
    Wang, Dingbiao
    Wang, Guanghui
    Yang, Yushen
    Xiang, Sa
    APPLIED THERMAL ENGINEERING, 2020, 166 (166)
  • [47] Study on the Long-Term Performance and Efficiency of Single-Well Circulation Coupled Groundwater Heat Pump System Based on Field Test
    Zhu, Ke
    Zeng, Yifan
    Wu, Qiang
    Xu, Shengheng
    Tu, Kun
    Liu, Xiaoxiu
    FRONTIERS IN EARTH SCIENCE, 2021, 9
  • [48] Numerical and experimental study of a closed loop for ground heat exchanger coupled with heat pump system and a solar collector for heating a glass greenhouse in north of Tunisia
    Awani, S.
    Kooli, S.
    Chargui, R.
    Guizani, A.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 76 : 328 - 341
  • [49] Numerical investigation on heat extraction performance of a downhole heat exchanger geothermal system
    Shi, Yu
    Song, Xianzhi
    Li, Gensheng
    Li, Ruixia
    Zhang, Yiqun
    Wang, Gaosheng
    Zheng, Rui
    Lyu, Zehao
    APPLIED THERMAL ENGINEERING, 2018, 134 : 513 - 526
  • [50] Effects of the total borehole length and of the heat pump inverter on the performance of a ground-coupled heat pump system
    Naldi, Claudia