An experimental study on improving the thermal environment of data centers by optimizing fan wall arrangement

被引:1
|
作者
Wu, Li [1 ]
Mao, Ruiyong [1 ]
Zhang, Jun [1 ]
Li, Chao [1 ]
Gan, Jin [2 ]
Zhou, Jiri [3 ]
Zhang, Zujing [1 ]
机构
[1] Guizhou Univ, Coll Civil Engn, Guizhou Prov Key Lab Rock & Soil Mech & Engn Safet, Guiyang 550025, Peoples R China
[2] Guizhou Prov Architectural Design & Res Inst Co LT, Guiyang 550081, Peoples R China
[3] China MCC5 Grp CORP LTD, MCC5 Tower, 9 Wuye Rd, Chengdu 610000, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2024年 / 96卷
基金
中国国家自然科学基金;
关键词
Fan wall cooling technology; Data centers; Thermal environment; Airflow distribution; Air supply system; AIR-FLOW; MANAGEMENT; PERFORMANCE;
D O I
10.1016/j.jobe.2024.110421
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
For a fan-wall data center, a large number of fans can be installed on one side of the server room to facilitate the introduction of outdoor cold air into the server room for effective heat dissipation, thereby accomplishing the objective of energy conservation. However, fewer researches are currently available on optimizing the fan array layout of fan-wall data centers to improve the thermal environment. This study aims to explore the impact of fan array layout parameters, including the area, distance, and height of the fan array, on the cooling efficiency of server rooms through both single-factor experiments and orthogonal experiments. The results indicate that: (1) In a fan-wall cooling system, racks closest to the fan wall have high temperature fluctuations and less orderly airflow organization. (2) The optimization of the fan array layout in a data center is primarily influenced by the height, area and distance of the fan array. (3) For a DC, the fan array layout, with an area of 4320 cm2, a distance of 81 cm, and a height of 18 cm, can achieve optimal conditions and effectively enhances the overall thermal performance of the rack. By optimizing the layout of the fan array, a more efficient combination of parameters for air distribution can be achieved, providing a reference for the arrangement and layout of fan arrays in actual engineering applications.
引用
收藏
页数:17
相关论文
共 50 条
  • [11] Experimental Study of Airflow Designs for Data Centers
    Tsuchiya, Takashi
    Suwa, Yoshihide
    Ooka, Ryozo
    JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING, 2014, 13 (02) : 491 - 498
  • [12] A Simulation Study of Factors Affecting Cooling Performance of a Fan Wall-Cooled Data Center
    Wei, Ling
    Bi, Zhaoyang
    Chen, Tailian
    PROCEEDINGS OF ASME 2023 17TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, ES2023, 2023,
  • [13] Effects of airflow on the thermal environment and energy efficiency in raised-floor data centers: A review
    Jin, Chaoqiang
    Bai, Xuelian
    Yang, Chao
    SCIENCE OF THE TOTAL ENVIRONMENT, 2019, 695
  • [14] Improving the indoor thermal environment in lightweight buildings in winter by passive solar heating: An experimental study
    Kou, Fangcheng
    Shi, Shaohang
    Zhu, Ning
    Song, Yehao
    Zou, Yu
    Mo, Jinhan
    Wang, Xin
    INDOOR AND BUILT ENVIRONMENT, 2022, 31 (09) : 2257 - 2273
  • [15] An experimental study on the indoor thermal environment in prefabricated houses in the subtropics
    Wang, Yan
    Wang, Lei
    Long, Enshen
    Deng, Shiming
    ENERGY AND BUILDINGS, 2016, 127 : 529 - 539
  • [16] Experimental study on dynamic thermal environment of passenger compartment based on thermal evaluation indexes
    Zhang, Liang
    Qi, Liangkui
    Liu, Jianhua
    Wu, Qingqing
    SCIENCE PROGRESS, 2020, 103 (03)
  • [17] Study on Improving Thermal Environment of College Dormitory in Chongqing
    Ou, Hongyin
    Liu, Fang
    Song, Qinglong
    Yu, Longxing
    PROGRESS IN ENVIRONMENTAL SCIENCE AND ENGINEERING, PTS 1-4, 2013, 610-613 : 2849 - 2853
  • [18] Experimental study and evaluation of the thermal environment for sleeping
    Liu, Yanfeng
    Song, Cong
    Wang, Yingying
    Wang, Dengjia
    Liu, Jiaping
    BUILDING AND ENVIRONMENT, 2014, 82 : 546 - 555
  • [19] The thermal behavior of Trombe wall system with venetian blind: An experimental and numerical study
    He, Wei
    Hu, Zhongting
    Luo, Bingqing
    Hong, Xiaoqiang
    Sun, Wei
    Ji, Jie
    ENERGY AND BUILDINGS, 2015, 104 : 395 - 404
  • [20] Optimization air-conditioning system and thermal management of data center via fan-wall free cooling technology
    Zhang, Jun
    Mao, Ruiyong
    Li, Chao
    Lan, Jiang
    Yi, Xiaoyan
    Zhang, Zujing
    APPLIED THERMAL ENGINEERING, 2023, 234