An experimental study on improving the thermal environment of data centers by optimizing fan wall arrangement

被引:1
|
作者
Wu, Li [1 ]
Mao, Ruiyong [1 ]
Zhang, Jun [1 ]
Li, Chao [1 ]
Gan, Jin [2 ]
Zhou, Jiri [3 ]
Zhang, Zujing [1 ]
机构
[1] Guizhou Univ, Coll Civil Engn, Guizhou Prov Key Lab Rock & Soil Mech & Engn Safet, Guiyang 550025, Peoples R China
[2] Guizhou Prov Architectural Design & Res Inst Co LT, Guiyang 550081, Peoples R China
[3] China MCC5 Grp CORP LTD, MCC5 Tower, 9 Wuye Rd, Chengdu 610000, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2024年 / 96卷
基金
中国国家自然科学基金;
关键词
Fan wall cooling technology; Data centers; Thermal environment; Airflow distribution; Air supply system; AIR-FLOW; MANAGEMENT; PERFORMANCE;
D O I
10.1016/j.jobe.2024.110421
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
For a fan-wall data center, a large number of fans can be installed on one side of the server room to facilitate the introduction of outdoor cold air into the server room for effective heat dissipation, thereby accomplishing the objective of energy conservation. However, fewer researches are currently available on optimizing the fan array layout of fan-wall data centers to improve the thermal environment. This study aims to explore the impact of fan array layout parameters, including the area, distance, and height of the fan array, on the cooling efficiency of server rooms through both single-factor experiments and orthogonal experiments. The results indicate that: (1) In a fan-wall cooling system, racks closest to the fan wall have high temperature fluctuations and less orderly airflow organization. (2) The optimization of the fan array layout in a data center is primarily influenced by the height, area and distance of the fan array. (3) For a DC, the fan array layout, with an area of 4320 cm2, a distance of 81 cm, and a height of 18 cm, can achieve optimal conditions and effectively enhances the overall thermal performance of the rack. By optimizing the layout of the fan array, a more efficient combination of parameters for air distribution can be achieved, providing a reference for the arrangement and layout of fan arrays in actual engineering applications.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Experimental study on improving thermal management of fan-wall data center by setting baffles in cold aisle
    Mao, Ruiyong
    Wu, Li
    Zhang, Zujing
    Wu, Hongwei
    Gan, Jin
    Zhou, Jiri
    Xu, Hongli
    ENERGY AND BUILDINGS, 2025, 328
  • [2] Experimental and numerical study on the thermal environment of a data center
    Tang, Yu
    Bai, Xuelian
    Jin, Chaoqiang
    Fu, Yusen
    Mao, Wangxin
    Xu, Xin
    BUILDING AND ENVIRONMENT, 2022, 212
  • [3] Experimental and numerical investigation on thermal performance of data center via fan-wall free cooling technology
    Lan, Jiang
    Zhang, Zujing
    Liang, Xing
    Wu, Hongwei
    Wang, Gang
    Mao, Ruiyong
    APPLIED THERMAL ENGINEERING, 2023, 228
  • [4] Design and Thermal Environment Analysis of a Decentralized Cooling System with Surface-Mount Heat Pipe Exchangers on Servers in Data Centers
    Yuan, Xiaolei
    Zhou, Xuetao
    Liang, Yumin
    Pan, Yiqun
    Kosonen, Risto
    Lin, Zhongping
    BUILDINGS, 2022, 12 (07)
  • [5] Thermal Environment Analysis and Improvement on Isolated Cold Aisle Data Centers
    Su, Lin
    Huang, Zhilin
    Dong, Kaijun
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2020, 12 (04)
  • [6] Improving Thermal Performance in Data Centers Based on Numerical Simulations
    Guo, Yinjie
    Zhao, Chunyu
    Gao, Hao
    Shen, Cheng
    Fu, Xu
    BUILDINGS, 2024, 14 (05)
  • [7] Experimental study on a loop thermosyphon cooling system in data centers using CO2 as a working Fluid, especially thermal environment and energy-saving effect
    Ding, Tao
    Cao, Han Wen
    He, Zhi Guang
    Wu, Jun Da
    Li, Zhen
    APPLIED THERMAL ENGINEERING, 2020, 175
  • [8] Study on multi-scale thermal management optimization for the configuration of a free cooling fan wall data center
    Zhou, Qiaoxinyi
    Mao, Ruiyong
    Wu, Li
    Chen, Jing
    Zhou, Jiri
    Zhang, Zujing
    APPLIED THERMAL ENGINEERING, 2025, 265
  • [9] An experimental study on applying PCMs to disaster-relief prefabricated temporary houses for improving internal thermal environment in summer
    Wang, Caixia
    Huang, Xiao
    Deng, Shiming
    Long, Enshen
    Niu, Jianlei
    ENERGY AND BUILDINGS, 2018, 179 : 301 - 310
  • [10] Vortex-enhanced thermal environment for air-cooled data center: An experimental and numerical study
    Xiong, Xin