Operating Room Air May Harbor Pathogens: The Role of an Ultraviolet Air Filtration Unit

被引:0
作者
Fernandez-Rodriguez, Diana [1 ,2 ]
Tarabichi, Saad [3 ]
Golankiewicz, Krystal [1 ]
Zappley, Nicolina [1 ]
Parvizi, Javad [4 ]
机构
[1] Thomas Jefferson Univ, Rothman Inst, Dept Orthoped Surg, Philadelphia, PA USA
[2] Univ Nacl Autonoma Mexico, Fac Med, Mexico City, Mexico
[3] Mayo Clin Arizona, Dept Orthopaed Surg, Phoenix, AZ USA
[4] Acibadem Univ Hosp, Int Joint Ctr, Istanbul, Turkiye
关键词
surgical site infection; arthroplasty; operating room; sterilization; contamination; SURGICAL SITE INFECTIONS; CONTAMINATION; JOINT; SURGERY; HIP; VENTILATION; REPLACEMENT; RADIATION; QUALITY; CARE;
D O I
10.1016/j.arth.2024.05.072
中图分类号
R826.8 [整形外科学]; R782.2 [口腔颌面部整形外科学]; R726.2 [小儿整形外科学]; R62 [整形外科学(修复外科学)];
学科分类号
摘要
Background: One important factor for the prevention of surgical site infections is ultraclean air in the operating room (OR). Still, the direct sterilization potential of most technologies, especially in a dynamic clinical setting, is not well understood. We aimed to determine and compare the microbial presence from the inlet and outlet flow of a filtration unit with crystalline ultraviolet-C (C-UVC) light. Methods: A prospective study was conducted at a single institution, where primary total joint arthroplasty and spine surgeries were performed. The OR was fitted with a positive ventilation system. In addition, a filtration unit with a C-UVC sterilizing light was placed in the OR. The inlet and outlet air flows were swabbed simultaneously and compared. Swabs were processed for culture and next-generation sequencing. Results: The mean length of the surgical procedures sampled was 68 +/- 13 minutes. Overall, 19 out of 200 (9.5%) swabs isolated microorganisms. Inlet air swabs were positive at a higher rate (16 versus 3%; P < .01) compared to the outlet air swabs. A wide variety of Gram-positive, Gram-negative, and anaerobic bacteria were isolated, but fungi were only recovered from inlet air swabs. The detection of microorganisms was also higher when more door openings were performed (32.5 +/- 7.1 versus 27.9 +/- 5.6; P < .01). Conclusions: Air swabs mainly isolated microorganisms from the inlet flow to the filtration unit with a CUVC light. The sterilizing unit counteracted factors affecting the air quality in the OR, namely door openings, surgical personnel, and tissue combustion. (c) 2024 Elsevier Inc. All rights are reserved, including those for text and data mining, AI training, and similar technologies.
引用
收藏
页码:2857 / 2862
页数:6
相关论文
共 50 条
  • [21] Potential sources of operating room air contamination: a preliminary study
    Brock-Utne, J. G.
    Ward, J. T.
    Jaffe, R. A.
    JOURNAL OF HOSPITAL INFECTION, 2021, 113 : 59 - 64
  • [22] Numerical simulation on air distribution and aerosol transportation in operating room with unidirectional flow system under operational condition
    Wang, Ang
    Ding, Lili
    Tan, Mei-Lan
    Shi, Su-Juan
    Zhou, Bin
    JOURNAL OF BUILDING ENGINEERING, 2023, 80
  • [23] Hygiene aspects of multidrug-resistant pathogens in the operating room and intensive care unit
    Schuler, F.
    Lanckohr, C.
    Pillukat, M. Hendrik
    Scherf, R.
    Mellmann, A.
    ANAESTHESIST, 2019, 68 (05): : 329 - 338
  • [24] Hygiene aspects of multidrug-resistant pathogens in the operating room and intensive care unit
    Schuler, F.
    Lanckohr, C.
    Pillukat, M. Hendrik
    Scherf, R.
    Mellmann, A.
    GEFASSCHIRURGIE, 2019, 24 (04): : 347 - 358
  • [25] Forced-air warming blowers: An evaluation of filtration adequacy and airborne contamination emissions in the operating room
    Albrecht, Mark
    Gauthier, Robert L.
    Belani, Kumar
    Litchy, Mark
    Leaper, David
    AMERICAN JOURNAL OF INFECTION CONTROL, 2011, 39 (04) : 321 - 328
  • [26] The Role of the Hospital Environment in Preventing Healthcare-Associated Infections Caused by Pathogens Transmitted through the Air
    Jacob, Jesse T.
    Kasali, Altug
    Steinberg, James P.
    Zimring, Craig
    Denham, Megan E.
    HERD-HEALTH ENVIRONMENTS RESEARCH & DESIGN JOURNAL, 2013, 7 : 74 - 98
  • [27] The effect of door opening on air-mixing in a positively pressurized room: Implications for operating room air management during the COVID outbreak
    Bhattacharya, Arup
    Ghahramani, Ali
    Mousavi, Ehsan
    JOURNAL OF BUILDING ENGINEERING, 2021, 44
  • [28] Do surgeons and surgical facilities disturb the clean air distribution close to a surgical patient in an orthopedic operating room with laminar airflow?
    Cao, Guangyu
    Storas, Madeleine C. A.
    Aganovic, Amar
    Stenstad, Liv-Lnger
    Skogas, Jan Gunnar
    AMERICAN JOURNAL OF INFECTION CONTROL, 2018, 46 (10) : 1115 - 1122
  • [29] Operating room ventilation systems: recovery degree, cleanliness recovery rate and air change effectiveness in an ultra-clean area
    Lans, J. L. A.
    Mathijssen, N. M. C.
    Bode, A.
    van den Dobbelsteen, J. J.
    van der Elst, M.
    Luscuere, P. G.
    JOURNAL OF HOSPITAL INFECTION, 2022, 122 : 115 - 125
  • [30] The impact of air change rate on the air quality of surgical microenvironment in an operating room with mixing ventilation
    Zhang, Yixian
    Cao, Guangyu
    Feng, Guohui
    Xue, Kai
    Pedersen, Christoffer
    Mathisen, Hans Martin
    Stenstad, Liv-Inger
    Skogas, Jan Gunnar
    JOURNAL OF BUILDING ENGINEERING, 2020, 32