Investigation of Arc Dynamic Behavior Change Induced by Various Parameter Configurations for C4F7N/CO2 Gas Mixture

被引:1
作者
Wang, Wen [1 ]
Yan, Xianglian [1 ]
Liu, Beiyang [1 ]
Bian, Yalin [1 ]
机构
[1] China Elect Power Res Inst, Beijing 100192, Peoples R China
关键词
C4F7N/CO2; arc dynamic behavior; magnetohydrodynamic-based arc model; non-recombination feature; PERFORMANCE; INSULATION; MODELS; SF6;
D O I
10.3390/en17143485
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This study investigates the feasibility of using a mixture of C4F7N/CO2 gases as an eco-friendly arcing medium for high-voltage circuit breakers, comparing its performance to that of conventional SF6 gas. An existing magnetohydrodynamic (MHD)-based arc model is modified to incorporate the non-recombination characteristics of C4F7N. The temperature, pressure, and velocity distributions of the arc throughout the whole arcing process are systematically analyzed. First, the differences in multi-physical fields induced by the C4F7N non-recombination feature are highlighted. The effects of varying the C4F7N concentration from 4% to 10% in the C4F7N/CO2 gas mixture on the arc behavior are also computationally studied. The results indicate significant differences in the arc-extinguishing performance between C4F7N/CO2 and SF6 under identical operating conditions. The potential of using C4F7N/CO2 as a viable alternative to SF6 in circuit breaker applications may need further design efforts to optimize key components such as the driving mechanism and nozzle. Moreover, as the concentration of C4F7N increases, the gas mixture exhibits improved flow field characteristics, suggesting that a higher volume concentration of C4F7N enhances the gas's short-circuit current interruption capabilities.
引用
收藏
页数:16
相关论文
共 29 条
  • [1] Chen Q.L., 2023, P 2023 4 INT S INS D, P149
  • [2] Calculation of the interruption capability of SF6-CF4 and SF6-C2F6 mixtures .1. Plasma properties
    Chervy, B
    Riad, H
    Gleizes, A
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 1996, 24 (01) : 198 - 209
  • [3] A comparison of three radiation models for the calculation of nozzle arcs
    Dixon, CM
    Yan, JD
    Fang, MTC
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2004, 37 (23) : 3309 - 3318
  • [4] CURRENT-ZERO ARC MODEL BASED ON FORCED-CONVECTION
    FANG, MTC
    BRANNEN, D
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 1979, 7 (04) : 217 - 229
  • [5] CURRENT-ZERO BEHAVIOR OF AN SF(6) GAS-BLAST ARC .2. TURBULENT-FLOW
    FANG, MTC
    ZHUANG, Q
    GUO, XJ
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1994, 27 (01) : 74 - 83
  • [6] Forster P., 2021, EARTHS ENERGY BUDGET
  • [7] C4F7N/CO2混合气体在中压负荷开关中的开断性能实验研究
    付鲁军
    邵先军
    辛昭昭
    谢成
    [J]. 高压电器, 2020, 56 (08) : 86 - 91
  • [8] Gautschi D., 2016, Application of a Fluoronitrile Gas in GIS and GIL as an Environmental Friendly Alternative to SF>6
  • [9] Kieffel Y., 2016, P 2016 IEEE INT C DI, P54
  • [10] Kieffel Y, 2015, 2015 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), P379