Automatic device arrangement and wiring for fire alarm systems in metro stations: A case study

被引:0
|
作者
Jin, Ruiying [1 ]
Li, Junjie [1 ]
Wang, Hongxin [1 ]
Gu, Jiefan [2 ]
Li, Yuancheng [1 ]
Chen, Junyu [1 ]
Xu, Peng [1 ]
Lin, Ting [3 ]
Lyu, Wei [3 ]
机构
[1] Tongji Univ, Sch Mech Engn, Shanghai, Peoples R China
[2] Tongji Univ, Coll Architecture & Urban Planning, Shanghai, Peoples R China
[3] Fuzhou Rail Transit Design Inst Co, Fuzhou, Peoples R China
来源
关键词
Design optimization; Building information model; Fire alarm system; Wire layout; Obstacle avoidance; OPTIMIZATION; DESIGN; GENERATION; ALGORITHM;
D O I
10.1016/j.jobe.2024.110617
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Fire alarm systems in metro stations play an important role in safeguarding lives and properties. The design process for these systems is complex and time-consuming due to the diversity of device types, wide distribution of device locations, and numerous compulsory design codes. This paper proposes an automatic design framework for fire alarm systems aimed at enhancing design efficiency. The framework includes five automated processes: information preprocessing, device arrangement, system loop generation, device wiring, and result generation. By converting the computer-aided design (CAD) results into building information models (BIM), building information and related professional device information are obtained, addressing the need for fire alarm system (FAS) design to integrate with multiple disciplines. The process can also automatically arrange FAS devices according to design specifications. Optimization algorithms, such as Ant Colony Algorithm and Prim Algorithm, are used to determine the device connection order and solve the problems of obstacle avoidance and orthogonal connections between two points. Compared to traditional design methods, the proposed automatic design framework for fire alarm systems in metro stations can not only satisfy the mandatory design requirements but also avoid the cumbersome and repetitive design process, providing new solutions for designers. Additionally, it can reduce wire length and save on construction costs. Using a real metro station as a case study, it is calculated that the automatic design can save between 8 % and 48 % of the wire length.
引用
收藏
页数:26
相关论文
共 50 条
  • [1] Fire and Life Safety Systems at Delhi Metro Underground Stations
    Gupta, Anoop Kumar
    Singh, Abdhesh Kumar
    Jain, Rajesh Kumar
    2017 ASHRAE ANNUAL CONFERENCE PAPERS, 2017,
  • [2] Noise pollution contours in metro stations (case study of Tehran metro)
    Forouhid, Amir Esmael
    Ilkah, Mohammad
    Mahmoudi, Jafar
    JOURNAL OF MEASUREMENTS IN ENGINEERING, 2021, 9 (04) : 193 - 206
  • [3] Study of emergency exit choice behaviour at metro stations in fire evacuation
    Mandal, Tarapada
    Rao, K. Ramachandra
    Tiwari, Geetam
    TRAFFIC AND GRANULAR FLOW 2022, TGF 2022, 2024, 443 : 163 - 170
  • [4] Simulation Study on Emergency Evacuation of Metro Stations in Fire Degradation Mode
    Xi Jiaojiao
    Li Jin
    2018 INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS AND CONTROL ENGINEERING (ISPECE 2018), 2019, 1187
  • [5] Efficient video-equipped fire detection approach for automatic fire alarm systems
    Kang, Myeongsu
    Tung, Truong Xuan
    Kim, Jong-Myon
    OPTICAL ENGINEERING, 2013, 52 (01)
  • [6] On the assessment of the escalator capacity in metro stations. Bucharest metro case study
    Dept. of Transport, Traffic and Logistics, University Politehnica of Bucharest, Romania
    不详
    UPB Sci Bull Ser D, 4 (59-70):
  • [7] Analysis of unwanted fire alarm: Case study
    Dept. of Build. Services Engrg., Hong Kong Polytechnic Univ., Hong Kong, Hong Kong
    J Archit Eng, 2 (62-65):
  • [8] Metro Stations Classification Based on Clustering Analysis-A Case Study of Beijing Metro
    Lu, Dongliang
    He, Min
    Shuai, Chunyan
    CICTP 2019: TRANSPORTATION IN CHINA-CONNECTING THE WORLD, 2019, : 1707 - 1717
  • [9] Reduction of false alarm rate in automatic forest fire infrared surveillance systems
    Briz, S
    de Castro, AJ
    Aranda, JM
    Meléndez, J
    López, F
    REMOTE SENSING OF ENVIRONMENT, 2003, 86 (01) : 19 - 29
  • [10] Study on the effectiveness of visual alarm devices used in fire alarm systems installed in industrial facilities
    Tepinski, Jaroslaw
    Popielarczyk, Tomasz
    Sowa, Tomasz
    PRZEMYSL CHEMICZNY, 2020, 99 (07): : 1036 - 1040