Vibration and noise mechanism of a 110 kV transformer under DC bias based on finite element method

被引:3
作者
Li, Ziyang [1 ]
Lang, Xujun [1 ]
Yang, Bo [1 ]
Liu, Xiaolin [1 ]
Wang, Hao [2 ]
Li, Zhang [2 ]
机构
[1] Shandong Elect Power Engn Consulting Inst Co LTD, Jinan 250013, Peoples R China
[2] Shandong Univ, Sch Elect Engn, Jinan 250061, Peoples R China
来源
GLOBAL ENERGY INTERCONNECTION-CHINA | 2024年 / 7卷 / 04期
关键词
Transformer; DC bias; Vibration; Noise;
D O I
10.1016/j.gloei.2024.08.012
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Global energy and environmental issues are becoming increasingly problematic, and the vibration and noise problem of 110 kV transformers, which are the most widely distributed, have attracted widespread attention from both inside and outside the industry. DC bias is one of the main contributing factors to vibration noise during the normal operation of transformers. To clarify the vibration and noise mechanism of a 110 kV transformer under a DC bias, a multi-field coupling model of a 110 kV transformer was established using the finite element method. The electromagnetic, vibration, and noise characteristics during the DC bias process were compared and quantified through field circuit coupling in parallel with the power frequency of AC, harmonic, and DC power sources. It was found that a DC bias can cause significant distortions in the magnetic flux density, force, and displacement distributions of the core and winding. The contributions of the DC bias effect to the core and winding are different at K dc =0.85. At this point, the core approached saturation, and the increase in the core force and displacement slowed. However, the saturation of the core increased the leakage flux, and the stress and displacement of the winding increased faster. The sound field distribution characteristics of the 110 kV transformer under a DC bias are related to the force characteristics. When the DC bias coefficient was 1.25, the noise sound pressure level reached 73.6 dB.
引用
收藏
页码:503 / 512
页数:10
相关论文
共 19 条
[1]   Contribution of inrush current to mechanical failure of power transformers windings [J].
Barros, Rafael M. R. ;
da Costa, Edson G. ;
Araujo, Jalberth F. ;
de Andrade, Filipe L. M. ;
Ferreira, Tarso, V .
HIGH VOLTAGE, 2019, 4 (04) :300-307
[2]   Design optimisation for distance between additional and tap winding in high-voltage transformers [J].
Dawood, Kamran ;
Koseoglu, Ahmet Kerem ;
Komurgoz, Guven .
HIGH VOLTAGE, 2020, 5 (06) :716-723
[3]   Transformer tank vibration modeling as a method of detecting winding deformations -: Part I:: Theoretical foundation [J].
García, B ;
Burgos, JC ;
Alonso, AM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :157-163
[4]  
Garcia B, 2006, Transformer tank vibration modeling as a method of detecting winding deformations-part II: Experimental verification
[5]  
Hammons T.J., 2000, POWER ENG REV IEEE, V20, P10, DOI DOI 10.1109/MPER.2000.819913
[6]   Research on distribution characteristics of vibration signals of ±500 kV HVDC converter transformer winding based on load test [J].
Jiang, Peiyu ;
Zhang, Zhanlong ;
Dong, Zijian ;
Wu, Yongye ;
Xiao, Rui ;
Deng, Jun ;
Pan, Zhicheng .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 132
[7]  
Linsuo Zeng, 2007, International Conference on Electrical Machines and Systems 2007, P1346
[8]  
Liu SX, 2023, 2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA, P149, DOI [10.1109/ICPSASIA58343.2023.10294358, 10.1109/ICPSAsia58343.2023.10294358]
[9]   Localized Surface Vibration and Acoustic Noise Emitted From Laboratory-Scale Transformer Cores Assembled From Grain-Oriented Electrical Steel [J].
Moses, Anthony John ;
Anderson, Philip I. ;
Phophongviwat, Teeraphon .
IEEE TRANSACTIONS ON MAGNETICS, 2016, 52 (10)
[10]   Analysis of Voltage Distribution Characteristics in UHVDC Converter Transformer Winding Based on the Reduced-Scale Model [J].
Pu, Zi-Heng ;
Ruan, Jiang-Jun ;
Du, Zhi-Ye ;
Zhang, Ya-Dong ;
Li, Jin-Liang ;
Xie, Qi-Jia ;
Tan, Dan .
IEEE TRANSACTIONS ON MAGNETICS, 2014, 50 (11)