Is Hot IT a False Economy? An Analysis of Server and Data Center Energy Efficiency as Temperatures Rise

被引:3
作者
Clement, Stephen [1 ]
Burdett, Kat [1 ]
Rteil, Nour [2 ]
Wynne, Astrid [1 ]
Kenny, Rich [1 ]
机构
[1] Techbuyer, Harrogate HG2 8PB, England
[2] Interact, Harrogate HG1 5DH, England
来源
IEEE TRANSACTIONS ON SUSTAINABLE COMPUTING | 2024年 / 9卷 / 03期
关键词
Servers; Data centers; Temperature distribution; Cooling; Temperature measurement; Green computing; Hardware; energy efficiency; sustainable computing; server benchmarking; power consumption; inlet temperature; ASHRAE climate zones; data center cooling; environmental impact; TECHNOLOGY;
D O I
10.1109/TSUSC.2023.3336801
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
As demand for digital services grows, there is need to improve efficiency and reduce the environmental impact of data centers. The largest energy consumer in any data center is the IT, followed by the systems dedicated to cooling. Aiming to improve efficiency, and driven by metrics like PUE, there is a trend towards running data centers hotter to reduce the cooling energy. There is little research investigating the effect this will have on the IT beyond failure rates. To ensure overall efficiency is improving, we must view the data center as a system of systems, taking a holistic view rather than focusing on individual sub-systems. In this paper we use industry standard benchmarks and a wind-tunnel to profile typical enterprise IT. We analyze the effect of environmental conditions on IT efficiency, showing minor increases in temperature or pressure impact the efficiency of servers. Using an idealized, simulated data center case study we show that the interaction between cooling systems, server behavior and local climate are non-trivial and increasing temperatures has potential to worsen efficiency.
引用
收藏
页码:482 / 493
页数:12
相关论文
共 45 条
[1]  
Acton P., 2022, Tech. Rep.JRC128184
[2]  
Airedale, 2020, Airedale, Tech.Rep.
[3]   Failure Analysis of Direct Liquid Cooling System in Data Centers [J].
Alkharabsheh, Sami ;
Puvvadi, Udaya L. N. ;
Ramakrishnan, Bharath ;
Ghose, Kanad ;
Sammakia, Bahgat .
JOURNAL OF ELECTRONIC PACKAGING, 2018, 140 (02)
[4]  
[Anonymous], 2012, 3 JOINT WOSP SIPEW I
[5]  
[Anonymous], 2008, Thermal Guidelines for Data Processing Environments
[6]  
[Anonymous], 2022, London data exchange
[7]  
[Anonymous], 2007, ENERGY STANDARD BUIL
[8]  
[Anonymous], 2011, Tech. Rep.
[9]  
[Anonymous], 2016, Energy Standard for Buildings Except Low-Rise Residential Buildings,ANSI/ASHRAE/IESStd.90.12016,
[10]  
[Anonymous], 2018, Liquid cooling total cost of ownership