Simulation and Calculation of Temperature Field and Current-Carrying Capacity of Power Cables under Different Laying Methods

被引:0
作者
Nie, Yongjie [1 ]
Chen, Daoyuan [1 ]
Zheng, Shuai [2 ]
Xu, Xiaowei [1 ]
Wang, Xilian [2 ]
Wu, Zhensheng [2 ]
机构
[1] Yunnan Power Grid Co Ltd, Elect Power Res Inst, Kunming 650217, Peoples R China
[2] Beijing Jiaotong Univ, Sch Elect Engn, Beijing 100044, Peoples R China
关键词
current-carrying capacity; temperature field; power cable; different laying methods; double-point chordal interception method;
D O I
10.3390/en17184611
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Precisely determining how cables distribute their current-carrying capacity and temperature field is crucial for the dependable and cost-effective functioning of power grids. Firstly, the power cable structure and the advantages and disadvantages of different laying methods are analyzed in detail. Secondly, the theoretical model of current-carrying capacity calculation and temperature field of power cables, including heat convection, heat conduction, and heat radiation, is constructed, and the method for calculating cable current-carrying capacity, relying on the double-point chordal interception method, is suggested. Then, the COMSOL multiphysics 6.2 finite element simulation software is utilized to create a simulation model that aligns with the real cable laying technique. Finally, the current-carrying capacity and temperature field of power cables are simulated and analyzed for different arrangements of power cables in three laying modes, namely directly buried, row pipe, and trench. The simulation results show that the cable laying method greatly affects the cable's carrying capacity; the more centralized the cable distribution, the smaller the flow. The method can be realized in different ways of laying power cables in the real-time rapid calculation of flow as the actual laying of power cables has an important reference and reference significance.
引用
收藏
页数:17
相关论文
共 28 条
[21]  
[王启隆 Wang Qilong], 2022, [高压电器, High Voltage Apparatus], V58, P157
[22]  
Wang Youyuan, 2010, Electric Power Automation Equipment, V30, P24
[23]   ±500 kV高压直流XLPE电缆温度分布及其影响因素研究 [J].
吴晶晶 ;
陈丽安 ;
严有祥 ;
赵鹏 .
高压电器, 2023, 59 (02) :113-119
[24]   Simulation analysis of carrying capacity of tunnel cable in different laying ways [J].
Xu, Xiaoming ;
Yuan, Qiuqi ;
Sun, Xudong ;
Hu, Donghai ;
Wang, Jing .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 130 :455-459
[25]  
Yang Y., 2023, Electr. Power Autom. Equip, V33, P139
[26]  
Zhang Hongliang, 2021, High Voltage Engineering, V47, P2117, DOI 10.13336/j.1003-6520.hve.20200310012
[27]   Research on the Improvement of Cable Ampacity in Dense Cable Trench [J].
Zhang, Han ;
Yu, Shangyu ;
Liu, Zhenguo ;
Cheng, Xiangmao ;
Zeng, Yanqi ;
Shu, Jian ;
Liu, Gang .
ENERGIES, 2024, 17 (11)
[28]   Conductor Temperature Monitoring of High-Voltage Cables Based on Electromagnetic-Thermal Coupling Temperature Analysis [J].
Zhang, Yuting ;
Yu, Fuhao ;
Ma, Zhe ;
Li, Jian ;
Qian, Jiang ;
Liang, Xiaojiao ;
Zhang, Jianzhong ;
Zhang, Mingjiang .
ENERGIES, 2022, 15 (02)