Experimental study on the immersion liquid cooling performance of high-power data center servers

被引:25
作者
Huang, Yongping [1 ]
Liu, Bin [2 ]
Xu, Shijie [1 ]
Bao, Chujin [3 ]
Zhong, Yangfan [4 ]
Zhang, Chengbin [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
[2] Zhejiang Chuangfu Hitech New Mat Co Ltd, Quzhou 324000, Zhejiang, Peoples R China
[3] Zhejiang Immertech Co Ltd, Hangzhou 310000, Zhejiang, Peoples R China
[4] Alibaba Cloud Comp Co Ltd, Shenzhen 518100, Guangdong, Peoples R China
基金
中国国家自然科学基金;
关键词
Single-phase immersion liquid cooling; High-power; Data center;
D O I
10.1016/j.energy.2024.131195
中图分类号
O414.1 [热力学];
学科分类号
摘要
Highly dense and integrated data centers face key challenges of realizing efficient cooling and improved energy efficiency. To overcome these challenges, this study experimentally investigated the flow and heat transfer characteristics of single-phase immersion liquid cooling (SPILC) systems. The influence of two opposite coolant flow directions on the SPILC performance was examined. Furthermore, a correlation mechanism between coolant thermal properties and SPILC performance was established, along with a control chart for regulating the working conditions of SPILC systems. The results indicate that compared to a pro-gravity flow, an anti-gravity flow scheme reduces the chip case temperature and thermal resistance by 33.8% and 55.6%, respectively, while decreasing the power usage effectiveness (PUE) by 1.4%. Using coolant with the lowest viscosity reduces the chip case temperature and thermal resistance by 9.3% and 10.5%, respectively, while decreasing the PUE by 0.4%. Moreover, the cooling water temperature has a greater impact on the performance of SPILC systems than the volume flow rate of coolants. Additionally, this paper provides control charts for the cooling water temperature and coolant flow rate to improve the PUE while ensuring the safe operation of SPILC systems, with the highest chip temperature and total electricity consumption as indicators.
引用
收藏
页数:16
相关论文
共 33 条
[1]   Water immersion cooling of high power density electronics [J].
Birbarah, Patrick ;
Gebrael, Tarek ;
Foulkes, Thomas ;
Stillwell, Andrew ;
Moore, Alexandra ;
Pilawa-Podgurski, Robert ;
Miljkovic, Nenad .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 147
[2]   Thermal performance evaluation of electronic fluorinated liquids for single-phase immersion liquid cooling [J].
Chen, Xi ;
Huang, Yongping ;
Xu, Shijie ;
Bao, Chujin ;
Zhong, Yangfan ;
Chen, Yongping ;
Zhang, Chengbin .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2024, 220
[3]   Design of a single-phase immersion cooling system through experimental and numerical analysis [J].
Cheng, Chin-Chi ;
Chang, Po-Chun ;
Li, Hsing-Chieh ;
Hsu, Fu-, I .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 160
[4]   Thermal Performance and Efficiency of a Mineral Oil Immersed Server Over Varied Environmental Operating Conditions [J].
Eiland, Richard ;
Fernandes, John Edward ;
Vallejo, Marianna ;
Siddarth, Ashwin ;
Agonafer, Dereje ;
Mulay, Verrendra .
JOURNAL OF ELECTRONIC PACKAGING, 2017, 139 (04)
[5]   Immersion Cooling Heats Up [J].
Greengard, Samuel .
COMMUNICATIONS OF THE ACM, 2022, 65 (06) :24-26
[6]   Optical characterization and durability of immersion cooling liquids for high concentration III-V photovoltaic systems [J].
Han, Xinyue ;
Guo, Yongjie ;
Wang, Qian ;
Phelan, Patrick .
SOLAR ENERGY MATERIALS AND SOLAR CELLS, 2018, 174 :124-131
[7]   Experimental investigation of a data-centre cooling system using a new single-phase immersion/liquid technique [J].
Hnayno, Mohamad ;
Chehade, Ali ;
Klaba, Henryk ;
Polidori, Guillaume ;
Maalouf, Chadi .
CASE STUDIES IN THERMAL ENGINEERING, 2023, 45
[8]   A review of data centers as prosumers in district energy systems: Renewable energy integration and waste heat reuse for district heating [J].
Huang, Pei ;
Copertaro, Benedetta ;
Zhang, Xingxing ;
Shen, Jingchun ;
Lofgren, Isabelle ;
Ronnelid, Mats ;
Fahlen, Jan ;
Andersson, Dan ;
Svanfeldt, Mikael .
APPLIED ENERGY, 2020, 258
[9]   Natural and forced convection heat transfer characteristics of single-phase immersion cooling systems for data centers [J].
Huang, Yongping ;
Ge, Junlei ;
Chen, Yongping ;
Zhang, Chengbin .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2023, 207
[10]   Performance investigation of a biomimetic latent heat thermal energy storage device for waste heat recovery in data centers [J].
Huang, Yongping ;
Deng, Zilong ;
Chen, Yongping ;
Zhang, Chengbin .
APPLIED ENERGY, 2023, 335