Blocking method with PSO-SVDD for differential protection of power transformer

被引:0
作者
Li, Zongbo [1 ]
Xv, Nuo [1 ]
Chen, Xi [2 ]
Zhang, Yi [3 ]
He, Anyang [4 ]
Jiao, Zaibin [4 ]
机构
[1] Northeast Elect Power Univ, Sch Elect Engn, Jilin 132012, Peoples R China
[2] State Grid Shaanxi Elect Power Econ Technol Res In, Xian 710075, Peoples R China
[3] State Grid Jinan Power Supply Co, Jinan 250012, Peoples R China
[4] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710068, Peoples R China
关键词
Power transformer; Differential protection; Blocking domain; Fine-tuning method; Differential current-excitation voltage curve; INTERNAL FAULTS; INRUSH CURRENT; DISCRIMINATION; IDENTIFICATION; SATURATION;
D O I
10.1016/j.epsr.2024.111016
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Multiple features fusion through artificial intelligence holds the potential to enhance the reliability of transformer protection. However, the existing methods encounter challenges due to the data scarcity of inrush current and internal fault. To address this, the paper proposes a blocking method of non-fault scenarios for differential protection, employing particle swarm optimization-support vector data description (PSO-SVDD). The approach utilizes several geometric features extracted from the differential current-excitation voltage curve (DEC) of normal operation to fully characterize similarities among non-fault scenarios, such as inrush current, and CT saturation caused by external fault. By exclusively utilizing normal operation data to represent all non-fault scenarios, the challenge posed by the scarcity of non-fault data is overcome. PSO-SVDD, selected as a one- class classification algorithm, is trained using geometric features from normal operation data, thereby avoiding the limited availability of fault data. The region inside the SVDD hypersphere serves as the blocking domain of differential protection. Additionally, a fine-tuning method of the feature boundary is introduced to enhance the robustness of the blocking domain by the small sample of scarce scenarios. Before the model is applied to unseen transformers, offline detection using its normal operation data is conducted to evaluate the performance of the blocking domain in. In case of misidentification, the misidentified sample is utilized as the support vector for fine-tuning the feature boundary. In practical application, if iron core saturation or fault scenarios are misidentified, the feature boundary is fine-tuned offline using the misidentified sample with the similar method above. PSCAD simulations and dynamic simulation experiments validate the superior performance of the proposed protection method through the comparison with several existing methods.
引用
收藏
页数:13
相关论文
共 50 条
  • [21] Waveform feature monitoring scheme for transformer differential protection
    Fani, Bahador
    Golshan, Mohamad Esmail Hamedani
    Abyaneh, Hosein Askarian
    JOURNAL OF ZHEJIANG UNIVERSITY-SCIENCE C-COMPUTERS & ELECTRONICS, 2011, 12 (02): : 116 - 123
  • [22] A Novel Signal Localized Convolution Neural Network for Power Transformer Differential Protection
    Murugan, Senthil Kumar
    Simon, Sishaj P.
    Eapen, Rohit Rajan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (02) : 1242 - 1251
  • [23] Transformer Differential Protection by Online Core Modeling and Orthogonal Polynomials
    Khalkhali, Babak
    Sadeh, Javad
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (05) : 2146 - 2153
  • [24] DESIGN AND SIMULATION OF SELF ADAPTIVE DIFFERENTIAL PROTECTION FOR A POWER TRANSFORMER
    Mageshwari, S.
    Sandeep, Konde
    2021 7TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENERGY SYSTEMS (ICEES), 2021, : 454 - 459
  • [25] Power transformer differential protection using current and voltage ratios
    Ali, E.
    Helal, A.
    Desouki, H.
    Shebl, K.
    Abdelkader, S.
    Malik, O. P.
    ELECTRIC POWER SYSTEMS RESEARCH, 2018, 154 : 140 - 150
  • [26] Improved Algorithm for Phase Comparison for Differential Protection of a Power Transformer
    Litvinov I.I.
    Glazyrin V.E.
    Litvinov, I.I. (litvinovii@mail.ru), 1600, Springer Science and Business Media, LLC (51): : 251 - 255
  • [27] Transformer Differential Protection Using Geometrical Structure Analysis of Waveforms
    Fani, B.
    Golshan, M. E. Hamedani
    Saghaian-Nejad, M.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2011, 39 (03) : 204 - 224
  • [28] Rate of Rise of Differential Current Based Protection of Power Transformer
    Bhalja, Het S.
    Bhalja, Bhavesh R.
    Agarwal, Pramod
    2019 IEEE 16TH INDIA COUNCIL INTERNATIONAL CONFERENCE (IEEE INDICON 2019), 2019,
  • [29] Harmonic restraint differential protection of power transformer based MRBFN
    Moravej, Z
    UPEC 2004: 39th International Universitities Power Engineering Conference, Vols 1-3, Conference Proceedings, 2005, : 782 - 788
  • [30] Power transformer differential protection with integral approach
    Bejmert, D.
    Kereit, M.
    Mieske, F.
    Rebizant, W.
    Solak, K.
    Wiszniewski, A.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 118