Analysis of multiple-faults of high-voltage circuit breakers based on non-negative matrix decomposition

被引:1
作者
Zhou, Yongrong [1 ,2 ]
Ma, Zhaoxing [3 ]
Chen, Hao [4 ]
Wang, Ruihua [3 ]
机构
[1] State Key Lab Technol & Equipment Def Power Syst O, Nanjing 211106, Peoples R China
[2] Nari Grp Co Ltd, Nanjing 211106, Peoples R China
[3] Qingdao Univ Technol, Sch Informat & Control Engn, Qingdao 266520, Peoples R China
[4] State Grid Nanjing Power Supply Co, Nanjing 210000, Peoples R China
来源
GLOBAL ENERGY INTERCONNECTION-CHINA | 2024年 / 7卷 / 02期
基金
中国国家自然科学基金;
关键词
High voltage circuit breaker; Signal separation; Monitor; Multiple faults; Power system; SPATIAL COVARIANCE MATRICES; FACTORIZATION; ALGORITHM;
D O I
10.1016/j.gloei.2024.04.006
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
High-voltage circuit breakers are the core equipment in power networks, and to a certain extent, are related to the safe and reliable operation of power systems. However, their core components are prone to mechanical faults. This study proposes a component separation method to detect multiple mechanical faults in circuit breakers that can achieve online real -time monitoring. First, a model and strategy are presented for obtaining mechanical voiceprint signals from circuit breakers. Subsequently, the component separation method was used to decompose the voiceprint signals of multiple faults into individual component signals. Based on this, the recognition of the features of a single-fault voiceprint signal can be achieved. Finally, multiple faults in high-voltage circuit breakers were identified through an experimental simulation and verification of the circuit breaker voiceprint signals collected from the substation site. The research results indicate that the proposed method exhibits excellent performance for multiple mechanical faults, such as spring structures and loose internal components of circuit breakers. In addition, it provides a reference method for the real -time online monitoring of high-voltage circuit breakers.
引用
收藏
页码:179 / 189
页数:11
相关论文
共 29 条
[1]   Underdetermined blind source separation using sparse representations [J].
Bofill, P ;
Zibulevsky, M .
SIGNAL PROCESSING, 2001, 81 (11) :2353-2362
[2]   Improving Diagnostic Performance of High-Voltage Circuit Breakers on Imbalanced Data Using an Oversampling Method [J].
Chen, Lei ;
Wan, Shuting ;
Dou, Longjiang .
IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (04) :2704-2716
[3]  
Chen Y Y, 2021, Chinese High Technology Letters, V31, P559
[4]   Radiometric Monitoring Technique for High-Voltage Circuit Breakers [J].
de Oliveira, Adriano Costa ;
da Costa, Edson Guedes ;
Rene Serres, Alexandre Jean ;
dos Santos Sousa, Herbet Filipe ;
Ferreira, Tarso Vilela ;
de Santana, Henrique Nunes .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (04) :1656-1665
[5]  
[豆龙江 Dou Longjiang], 2022, [电工技术学报, Transactions of China Electrotechnical Society], V37, P6420
[6]   A Novel Arcing Power-Based Algorithm for Condition Monitoring of Electrical Wear of Circuit Breaker Contacts [J].
Feizifar, Behnam ;
Usta, Omer .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) :1060-1068
[7]  
[关永刚 Guan Yonggang], 2018, [高压电器, High Voltage Apparatus], V54, P10
[8]   低压直流断路器脱扣器脱扣效果检测装置设计 [J].
侯磊 ;
常征 ;
蔡毅 ;
庞凝 ;
王伊晓 ;
杨鑫 .
电测与仪表, 2023, 60 (04) :155-159+175
[9]  
Hou L, 2023, Electrical Measurement & Instrumentation, V60, P175
[10]   Learning the parts of objects by non-negative matrix factorization [J].
Lee, DD ;
Seung, HS .
NATURE, 1999, 401 (6755) :788-791