摘要
Electric power system network is evolving rapidly towards a more flexible, robust and secured interconnected network which can provide better power quality within a competitive environment commonly known as deregulated power system (DPS). For safeguarding DPS, energy storage systems (ESSs) and an efficient control method are required to maintain equilibrium between load demand and generated power known as automatic generation control (AGC). This study highlights an attempt of performance comparison of several hybrid ESSs (HESSs) for AGC of multi-area multi-source power system under deregulated scenario. The considered system comprises of thermal, hydro and gas (THG) generating units in each area of a two-area DPS. A cascade optimal controller-fractional order derivative (COC-FOD) is suggested for AGC performance advancement and its performance is compared with optimal controller (OC). A nature inspired salp swarm algorithm (SSA) is utilized to optimise secondary FOD controller gains while primary OC is designed via full state feedback control approach. The time domain analysis and bode plot reveal the eminence of COC-FOD over OC by returning 66 % lower value of cost function, 24 % lower undershoot, 98 % lower overshoot, at least 24 % lesser rise time for area frequency deviation, and 30 % greater stability margins with comparable settling time and lesser number of oscillations. The performances of various HESSs like ultra-capacitor (UC) + redox flow battery (RFB), superconducting magnetic energy storage (SMES) + RFB and flywheel energy storage (FES) + RFB in the attendance of OC and COC-FOD controller are compared and performance of COC-FOD in the presence of SMES+RFB is found superior to other HESS combinations by giving 75 % lesser value of cost function and at least 43 % lesser undershoot for area frequency deviation compared to the scenario where COC-FOD is simulated without ESSs. To present a more realistic scenario, system nonlinearities are considered. Finally, COC-FOD controller proved its resilience and efficacy by providing satisfactory stabilized performance under wide variations in the system parameters.
引用
收藏
页数:18
相关论文
共 50 条
  • [21] Performance Comparison of FOA Optimized Several Classical Controllers for Multi-area Multi-sources Power System
    Acharyulu, B. V. S.
    Swamy, S. K.
    Mohanty, Banaja
    Hota, P. K.
    SOFT COMPUTING IN DATA ANALYTICS, SCDA 2018, 2019, 758 : 417 - 426
  • [22] Review of Automatic Generation Control For Multi Source Interconnected Power System Under Deregulated Environment
    Daraz, Amil
    Malik, Suheel Abdullah
    ul Haq, Altaf
    2018 4TH INTERNATIONAL CONFERENCE ON POWER GENERATION SYSTEMS AND RENEWABLE ENERGY TECHNOLOGIES (PGSRET-2018), 2018, : 430 - 434
  • [23] Optimal design of fuzzy PID controller for deregulated LFC of multi-area power system via mine blast algorithm
    Ahmed Fathy
    Ahmed M. Kassem
    Almoataz Y. Abdelaziz
    Neural Computing and Applications, 2020, 32 : 4531 - 4551
  • [24] Multi-Area Load Frequency Control in a Deregulated Power System Using Optimal Output Feedback Method
    Sadeh, Javad}
    Rakhshani, Elyas
    2008 5TH INTERNATIONAL CONFERENCE ON THE EUROPEAN ELECTRICITY MARKET, VOLS 1 AND 2, 2008, : 681 - +
  • [25] LFC performance advancement of two-area RES penetrated multi-source power system utilizing CES and a new CFOTID controller
    Arya, Yogendra
    Ahmad, Rafeque
    Nasiruddin, Ibraheem
    Ahmer, Mohammad Faraz
    JOURNAL OF ENERGY STORAGE, 2024, 87
  • [26] Effect of TCPS, SMES, and DFIG on load frequency control of a multi-area multi-source power system using multi-verse optimized fuzzy-PID controller with derivative filter
    Kumar, Amit
    Suhag, Sathans
    JOURNAL OF VIBRATION AND CONTROL, 2018, 24 (24) : 5922 - 5937
  • [27] Combined Voltage and Frequency Control of a Multi-Area Multi-Source System Using SFLA Optimized TID Controller
    Babu, Naladi Ram
    Sahu, Devesh Kumar
    Saikia, Lalit Chandra
    Ramoji, Satish Kumar
    2019 IEEE 16TH INDIA COUNCIL INTERNATIONAL CONFERENCE (IEEE INDICON 2019), 2019,
  • [28] Quasi oppositional harmony search algorithm based controller tuning for load frequency control of multi-source multi-area power system
    Shankar, G.
    Mukherjee, V.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 75 : 289 - 302
  • [29] Performance Improvement of AGC Using Novel Controllers in a Multi-Area Solar Thermal System under Deregulated Environment
    Rajendran, Madhuvanthani
    Govindasamy, Sundar
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2024, 52 (06) : 847 - 862
  • [30] Design of Optimal Sliding mode Controller for Load Frequency Control in Multi-area Deregulated Thermal System
    Kumar, T. Anil
    Ramana, N. Venkata
    2012 INTERNATIONAL CONFERENCE ON EMERGING TRENDS IN ELECTRICAL ENGINEERING AND ENERGY MANAGEMENT (ICETEEEM - 2012), 2012, : 44 - 51