Combined Data-Driven and Model-Driven Location of Lightning Strikes: Application to Meshed HVDC Grids

被引:0
作者
Verrax, Paul [1 ]
Kieffer, Michel [2 ]
Milhiet, Louis [1 ]
Raison, Bertrand [3 ]
机构
[1] Supergrid Inst, F-69100 Villeurbanne, France
[2] Univ Paris Saclay, Lab Signaux & Syst, CNRS, Cent Supelec, F-91192 Paris, France
[3] Univ Grenoble Alpes, Inst Engn, CNRS, Grenoble INP, F-38000 Grenoble, France
关键词
Lightning strikes; fault location; data-driven approach; model-driven approach; TRANSMISSION; SIMULATION;
D O I
10.1109/TPWRS.2023.3288887
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This article addresses the low-delay location of faults due to lightning strikes using single-ended measurements in High Voltage Direct Current (HVDC) grids. A combined data-driven and model-driven approach is used to estimate the fault location iteratively. No prior knowledge of the voltage evolution at the fault location is required. Once the first wavefront due to a fault is detected at some observation location of the HVDC grid, the measurements are fed to a model of the propagation of transient waves along the lines. The model is parameterized by the estimated fault location. As a result, a model of the waveform samples starting from the second wavefront is obtained. The measured and modeled waveform samples are then compared to update the estimate of the fault location. The performance of the proposed approach is evaluated via simulations, including field measurements of lightning currents. Typical location accuracy of 300 m is obtained by considering observations performed at 1 MHz over an observation time interval of less than 1.5 ms.
引用
收藏
页码:3811 / 3824
页数:14
相关论文
共 36 条
[1]  
[Anonymous], 2009, CIGRE WG B2/B4/C1.17
[2]  
[Anonymous], 2013, WG C4.407
[3]  
[Anonymous], 2010, HighVoltage Test Techniques-Part 1: General Definitions and Test Requirements IEC Standard, 60060-1
[4]  
[Anonymous], 1991, CIGRE WG01 SC33
[5]  
[Anonymous], 2021, WG B5.52
[6]   Selective Nonunit Protection Technique for Multiterminal VSC-HVDC Grids [J].
Bertho, Rui, Jr. ;
Lacerda, Vinicius A. ;
Monaro, Renato M. ;
Vieira, Jose C. M. ;
Coury, Denis V. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) :2106-2114
[7]  
Brantl C., 2019, P CIGRE S
[8]   Impact of Propagation Losses on Fault Location Accuracy in Full Transient-Based Methods [J].
Cozza, Andrea ;
He, Shao-Yin ;
Xie, Yan-Zhao .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (01) :383-396
[9]  
De Almeida S. A. B., 2009, P IEEE 6 INT C EUR E, P1
[10]  
Dijkstra EW., 1959, Numer. Math, P287, DOI DOI 10.1007/BF01386390