Experimental Study of Clamping Pressure during Step Loading of Power Transformer with and without Prior Energisation

被引:1
作者
Madshaven, Inge [1 ]
Enoksen, Henrik [1 ]
Lundgaard, Lars E. [1 ]
Jaufer, Stefan [2 ]
Krause, Christoph [2 ]
Prasnikar, Borut [3 ]
Mjelve, Asgeir [4 ]
机构
[1] SINTEF Energy Res, N-7034 Trondheim, Norway
[2] Weidmann Elect Technol AG, CH-8640 Rapperswil, Switzerland
[3] Kolektor Etra doo, Ljubljana 1231, Slovenia
[4] Elvia AS, N-0275 Oslo, Norway
关键词
power transformer; clamping pressure; transformer energisation; transformer loading; short-circuit performance; on-line measurements;
D O I
10.3390/en17122898
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The electrification of society, increasing renewable energy sources and mobility charging lead to new loading patterns for power transformers. Dynamic load conditions induce enhanced mechanical stress on the transformers' windings, potentially causing degradation of the solid insulation over time and compromising the transformer's short-circuit withstand capability. Thermal expansion of the windings, caused by losses in the copper conductors, occurring as the transformer is loaded, increases the stress. Conversely, magnetic losses in the core and tie plate expansion contribute to a reduction in stress. This paper presents the effect of step changes in core losses and copper losses by on-line measurements of the clamping pressure, to better understand the mechanical stresses acting upon the solid insulation cellulose materials. Energisation is found to decrease the clamping pressure following warming up of the transformer, and loading the transformer increased the pressure as the windings increased in temperature. The converse effect was found when unloading and de-energising. The on-line monitoring system provides a new and important step towards ensuring the short-circuit performance of power transformers.
引用
收藏
页数:12
相关论文
共 17 条
[1]  
[Anonymous], 2006, Standard IEC 60076-5
[2]  
Bertagnolli G., 1996, Short-Circuit Duty of Power Transformers, P33
[3]  
CIGRE WG A2.37, 2015, TB 642Transformer Reliability Survey
[4]  
CIGRE WG A2.53, 2020, TB 812Advances in the Interpretation of Transformer Frequency Response Analysis (FRA)
[5]   A path of power transformers failure under multiple short-circuit impacts [J].
Jin, Mingkai ;
Chen, Weijiang ;
Xu, Weijie ;
Li, Jiaxun ;
Zhao, Yi ;
Zhang, Qiaogen ;
Wen, Tao .
ELECTRIC POWER SYSTEMS RESEARCH, 2024, 229
[6]  
Karsai K., 1987, LARGE POWER TRANSFOR
[7]   The impact of drying and oil impregnation conditions and of temperature cycles on the clamping force of power transformer windings [J].
Krause, C ;
Goetz, W ;
Heinrich, B .
CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, :350-353
[8]  
Krause C., 1999, P CIGRE SC 12 TRANSF
[9]   Aging of oil-impregnated paper in power transformers [J].
Lundgaard, LE ;
Hansen, W ;
Linhjell, D ;
Painter, TJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :230-239
[10]  
Madshaven I, 2022, 2022 7TH INTERNATIONAL ADVANCED RESEARCH WORKSHOP ON TRANSFORMERS (ARWTR 2022), P115, DOI 10.23919/ARWtr54586.2022.9959909