Comparative Analysis of 500 kV Double-Circuit Transmission Line Electric Field Intensity: Ethiopian Lines Compliance With ICNIRP

被引:1
|
作者
Tefera, Tesfaye Nafo [1 ]
Punekar, Gururaj S. [2 ]
Yassin, Kemal Ibrahim [1 ]
Tuka, Milkias Berhanu [1 ]
机构
[1] Addis Ababa Sci & Technol Univ, Dept Elect & Comp Engn, Addis Ababa 1000, Ethiopia
[2] Natl Inst Technol Karnataka, Dept Elect & Elect Engn, Surathkal 575025, India
来源
IEEE ACCESS | 2024年 / 12卷
关键词
Conductors; Power transmission lines; Poles and towers; Wires; Mathematical models; Electric fields; High-voltage techniques; Radiation protection; CSM; double-circuit 500 kV lines; E-field; INCIRP guideline; phase sequence arrangement; tower configuration; VOLTAGE;
D O I
10.1109/ACCESS.2024.3406902
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The high-intensity electric fields, which are in the vicinity of power transmission lines, have adverse effects on human and other living beings if they are not within the specified limits. The International Commission on Non-ionizing Radiation Protection (INCIRP) specifies guidelines for these E-fields from the perspective of public exposure at the ground level and sets it to 5 kV/m at 50 Hz. Thus, this study was aimed at analyzing and comparing the E-fields intensity of differently configured double-circuit 500 kV transmission lines at a height of 1 m above the ground plane. Charge Simulation Method (CSM) using MATLAB as a programming platform is used for this study. Among the tower configurations studied, a configuration that provided minimum E-fields with minimum ground clearance was identified. From the actual built transmission lines included in the study, vertical lines configuration produces a minimum E-fields intensity of 4.565 kV/m root mean square and fulfills the INCIRP requirement. However, triangular line configuration is the preferable configuration for 500 kV double circuit transmission lines giving the least E-fields at the ground with minimum ground clearance using optimized phase sequence arrangements irrespective of other comparative parameters. Additionally, an evaluation of these line configurations based on the distribution of the conductor surface E-fields was conducted. The study reveals that the E-fields on the surface of the transmission line conductors included in the study remains significantly below the intrinsic breakdown strength of atmospheric air. Therefore, it was anticipated that the designs will remain free from corona discharge under fair weather conditions.
引用
收藏
页码:76359 / 76366
页数:8
相关论文
共 50 条
  • [21] METHOD FOR INCREASING SENSITIVITY OF THE DISTANCE PROTECTION ON A 330 KV DOUBLE-CIRCUIT TRANSMISSION LINE
    Brinkis, K.
    Vanzovich, E.
    Drozd, D.
    Mutule, A.
    LATVIAN JOURNAL OF PHYSICS AND TECHNICAL SCIENCES, 2010, 47 (05) : 15 - 24
  • [22] EHV DOUBLE-CIRCUIT UNTRANSPOSED TRANSMISSION LINE-ANALYSIS AND TESTS
    HESSE, MH
    SABATH, J
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (03): : 984 - &
  • [23] Electric Field Computation and Optimization of Composite Tower in 330 kV Double Circuit Transmission Lines
    Wang, Qingyu
    Peng, Zongren
    Yang, Xi
    Li, Naiyi
    Wang, Jialong
    Liao, Jintao
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 283 - 286
  • [24] Flashover characteristics of upper air clearances and lightning withstand level for ±500 kV DC double-circuit transmission line towers
    Ding, Yujian
    Li, Qingfeng
    Liao, Weiming
    Sun, Zhaoying
    Ge, Dong
    Wang, Xi
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (28): : 114 - 119
  • [25] Design of 500 kV AC double-circuit transmission line on the same tower located at 20 mm heavy icing area
    Zhang, Haiping
    Zhang, Chi
    Wang, Jiangtao
    Zhao, Qingbin
    Ren, Deshun
    Gou, Jie
    Dianwang Jishu/Power System Technology, 2015, 39 (01): : 123 - 129
  • [26] Statistical Analysis of Radio Interference of 1000 kV UHV AC Double-circuit Transmission Lines in Foul Weather
    Xie, Huichun
    Cui, Xiang
    Wan, Baoquan
    Zhang, Jiangong
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2016, 2 (02): : 47 - 55
  • [27] Calculation and Analysis on Unbalanced Currents of Yandun-Tianshan 750kV Double-circuit Transmission Lines
    Wang X.
    Xiang Z.
    Song X.
    Liang S.
    Li S.
    Wang C.
    Fu T.
    Dianwang Jishu/Power System Technology, 2022, 46 (07): : 2842 - 2849
  • [28] Electromagnetic Environmental Impact of 500-kV Double -Circuit Transmission Lines
    Qi Jianzhao
    Electricity, 2011, 22 (01) : 24 - 28
  • [29] Study on lightning performance for ±500 kV DC double circuit transmission lines
    Nie, Dingzhen
    Zhou, Peihong
    Dai, Min
    Wang, Dongmei
    Gaodianya Jishu/High Voltage Engineering, 2007, 33 (01): : 148 - 151
  • [30] Lightning Backflash Performance for ±500kV Double Circuit Transmission Lines
    Lu, Hailiang
    Wen, Xishan
    Zhang, Chengwei
    Tong, Xuefang
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3535 - +