Pressure Characteristics in the Nitrogen-Sealed Power Transformers under Internal Faults

被引:0
|
作者
Li, Jiansheng [1 ]
Jia, Zheng [2 ]
Wang, Shengquan [1 ]
Liu, Shiming [3 ]
机构
[1] Elect Power Sci Res Inst, State Grid Jiangsu Elect Power Co Ltd, Nanjing 211103, Peoples R China
[2] State Grid Lianyungang Power Supply Co, Lianyungang 222000, Peoples R China
[3] Shandong Univ, Sch Elect Engn, Jinan 250061, Peoples R China
关键词
nitrogen-sealed power transformer; arc energy; dynamic pressure characteristics; tank rupture; PARTIAL DISCHARGE; OIL; TANK; CLASSIFICATION; INSULATION; SIGNALS;
D O I
10.3390/pr12061167
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
The explosion-proof performance is an important index for oil-immersed transformers. The nitrogen-sealed transformer is a new type of transformer with nitrogen gas in the upper space, which can buffer against internal stress increase caused by arc faults. However, the pressure changes in the transformer under internal faults are unclear. The authors of this study propose a method based on finite element simulation to analyze the pressure changes and the stress on the tank. First, the calculation process of arc energy and the pressure of the bubbles caused by the arc are derived. Second, the dynamic pressure wave propagation model and acoustic-solid coupling model are established. Last, the finite element simulation model is built to analyze the pressure characteristics. Taking the winding turn-to-turn and phase-to-phase short circuit faults as the analysis situations, the pressure changes in the 110 kV/20 MVA nitrogen-sealed transformer are simulated. Due to the pressure wave refraction and reflection, the pressure changes show oscillatory characteristics with time after the occurrence of an internal short circuit fault. The pressure wave travels from the arc fault position to the periphery. Compared to the conventional transformer, the pressure changes with slower variations under an internal short circuit fault and the tank suffer less stress, which indicates that the nitrogen-sealed transformer is more effective in the explosion-proof performance.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Internal faults in power transformers
    Jablonski, M.
    Napieralska-Juszczak, E.
    IET ELECTRIC POWER APPLICATIONS, 2007, 1 (01) : 105 - 111
  • [2] Detection of Internal Winding Faults in Power Transformers Based on Graphical Characteristics of Voltage and Current
    Yao, Chenguo
    Zhao, Zhongyong
    Chen, Yu
    Chen, Xiaohan
    Li, Chengxiang
    Li, Wei
    Wang, Jian
    2014 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2014,
  • [3] Modeling and simulation of pressure characteristics of power transformer tanks' internal faults
    Yan, C. (chg.yan@stu.xjtu.edu.cn), 1600, Chinese Society for Electrical Engineering (34):
  • [4] CHARACTERISTICS OF SEALED PARTS UNDER INTERNAL PRESSURE IN SUPER HIGH PRESSURE MERCURY DISCHARGE LAMPS
    Kase, Masahiko
    Sawa, Toshiyuki
    Iwama, Yuichiro
    MECHANICAL PROPERTIES AND PERFORMANCE OF ENGINEERING CERAMICS AND COMPOSITES, 2005, 26 (02): : 157 - 164
  • [5] The characteristics of the sealed parts in super high pressure mercury discharge lamps under internal pressure
    Kase, M
    Sawa, T
    Iwama, Y
    LIGHT SOURCES 2004, 2004, (182): : 223 - 224
  • [6] Modeling, Analysis, and Detection of Internal Winding Faults in Power Transformers
    Asadi, Nahid
    Kelk, Homayoun Meshgin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (06) : 2419 - 2426
  • [7] IMPROVED OPERATION OF DIFFERENTIAL PROTECTION OF POWER TRANSFORMERS FOR INTERNAL FAULTS
    LIU, P
    MALIK, OP
    CHEN, DS
    HOPE, GS
    GUO, Y
    IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (04) : 1912 - 1919
  • [8] Gas Generation of Cellulose Insulation in Palm Fatty Acid Ester and Mineral Oil for Life Prediction Marker in Nitrogen-sealed Transformers
    Tokunaga, Junko
    Koide, Hidenobu
    Mogami, Kenji
    Hikosaka, Tomoyuki
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 420 - 427
  • [9] Enhanced stability of nitrogen-sealed carbon nanotube saturable absorbers under high-intensity irradiation
    Martinez, Amos
    Fuse, Kazuyuki
    Yamashita, Shinji
    OPTICS EXPRESS, 2013, 21 (04): : 4665 - 4670
  • [10] Sensitive Protection of Power Transformers for Internal Inter-Turn Faults
    Wiszniewski, A.
    Rebizant, W.
    Schiel, L.
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 331 - +