Experimental Investigation of the Effect of Conductor Temperature on Corona Performance in Overhead Transmission Lines

被引:1
|
作者
Ilunga, Kayumba G. [1 ]
Swanson, Andrew G. [1 ]
Ijumba, Nelson Mutatina [2 ]
Stephen, Robert [1 ]
机构
[1] Univ KwaZulu Natal, Dept Elect Elect & Comp Engn, ZA-4041 Durban, South Africa
[2] Univ Rwanda, African Ctr Excellence Energy Sustainable Dev, Kigali, Rwanda
来源
IEEE ACCESS | 2024年 / 12卷
关键词
Corona; Conductors; Discharges (electric); Temperature measurement; Plasma temperature; Ionization; Transmission line measurements; Voltage control; Conductor temperature; corona discharge; inception voltage; ionization radius; POSITIVE DC CORONA; ELECTROSTATIC PRECIPITATOR; DISCHARGE; CONFIGURATION; AIR; MODEL;
D O I
10.1109/ACCESS.2024.3451980
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The maximum conductor temperature regulates the maximum amount of power that overhead lines can transmit. Excessive line sag and accelerated conductor ageing may occur if this maximum temperature is exceeded. This is particularly true for the most popular steel-reinforced conductors or aluminium anneals, in which high temperatures can cause grease, which is used to prevent corrosion from seeping. High-temperature low-sag conductors have been developed to increase current carrying capacity. In addition to the temperature constraint, overhead transmission lines largely depend on the corona discharge performance. This paper presents experimental results on the investigation of corona performance due to conductor temperature. An experimental configuration that uses a 10 kVA power transformer in cascade with a 10 kVA high current low voltage transformer both connected to the conductor in the corona cage was successfully developed. This configuration allows for heating the conductor while connected to the high voltage and allows for measuring corona current using the screened electrode method of corona cage. The results indicate an increase in corona current with rising conductor temperature, accompanied by a 25% to 32% decrease in inception voltage. The primary factors contributing to these trends were identified as relative air density and the Townsend coefficient. A temperature model incorporating the ionization region was developed to calculate the relative air density accurately. Additionally, To account for the effect of conductor temperature, the well-known surface inception field strength formula proposed by Peek was refined through optimization. Comparisons between the refined Peek's formula and the measured results demonstrated successful alignment. This research enhances our understanding of corona performance with conductor temperature, providing valuable insights for optimizing transmission line design and operation.
引用
收藏
页码:122114 / 122125
页数:12
相关论文
共 50 条
  • [2] CORONA LOSS OF 4-CONDUCTOR EXPERIMENTAL TRANSMISSION LINES
    SUGIMOTO, T
    ELECTRICAL ENGINEERING IN JAPAN, 1965, 85 (01) : 85 - &
  • [3] Conductor optimisation for overhead transmission lines
    Dama, Dipeen
    Muftic, Dzevad
    Vajeth, Riaz
    IEEE Power Engineering Society Inaugural 2005 Conference and Exposition in Africa, 2005, : 410 - 416
  • [4] Conductor optimisation for overhead transmission lines
    Vajeth, R
    Dama, D
    2004 IEEE AFRICON: 7TH AFRICON CONFERENCE IN AFRICA, VOLS 1 AND 2: TECHNOLOGY INNOVATION, 2004, : 589 - 595
  • [5] Validation of a Thermal Model for Overhead Transmission Lines at High Conductor Temperature
    Alvarez, J. Rodriguez
    Anderson, J. Azurza
    Franck, C. M.
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,
  • [6] Corona Effect Influence on the Lightning Performance of Overhead Distribution Lines
    Mestriner, Daniele
    Brignone, Massimo
    APPLIED SCIENCES-BASEL, 2020, 10 (14):
  • [7] Effect of air temperature on DC conductor corona performance in corona cage
    Wang, Wei
    Ding, Yan-Sheng
    Li, Cheng-Rong
    Li, Xiao-Lin
    Luo, Bing
    Yu, Zhuang-Zhuang
    An, Bing
    Wang, Yi-Xu
    Yang, Bo
    Fan, Fei
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (03): : 613 - 617
  • [8] NONDESTRUCTIVE TESTING OF OVERHEAD TRANSMISSION LINES - NUMERICAL AND EXPERIMENTAL INVESTIGATION
    Kulkarni, S.
    Hurlebaus, S.
    REVIEW OF PROGRESS IN QUANTITATIVE NONDESTRUCTIVE EVALUATION, VOLS 28A AND 28B, 2009, 1096 : 1566 - 1571
  • [9] INVESTIGATION OF CORONA PERFORMANCE OF CONDUCTOR BUNDLES FOR 800-KV TRANSMISSION
    BAKER, AC
    COMBER, MG
    OTTOSEN, KE
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (04): : 1117 - 1130
  • [10] COMPARATIVE STUDY OF CORONA PERFORMANCE OF CONDUCTOR BUNDLES FOR 1200 KV TRANSMISSION-LINES
    TRINH, NG
    MARUVADA, PS
    POIRIER, B
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (03): : 940 - 949