Gaseous contaminant transfer in membrane-based air-to-air energy exchangers

被引:0
作者
Mathews, Ashwin Joseph [1 ]
Krishnan, Easwaran N. [2 ]
Joseph, Albin [1 ]
Annadurai, Gurubalan [3 ]
Fauchoux, Melanie T. [1 ]
Simonson, Carey J. [1 ]
机构
[1] Univ Saskatchewan, Dept Mech Engn, Saskatoon, SK S7N 5A9, Canada
[2] Oak Ridge Natl Lab, Bldg & Transportat Sci Div, Oak Ridge, TN 37830 USA
[3] Indian Inst Technol, Dept Energy Sci & Engn, Mumbai 400076, India
基金
加拿大自然科学与工程研究理事会;
关键词
Membrane-based air-to-air energy exchanger; Contaminant transfer; Exhaust air transfer ratio; Membranes; Indoor air quality; Gaseous contaminants; VOCs; WATER-VAPOR; GAS; PERMEATION; VENTILATION; TRANSPORT; SORPTION; VOLUME;
D O I
10.1016/j.enbuild.2024.114428
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Membrane-based air-to-air energy exchangers (M-AAEEs) transfer heat and moisture between building exhaust air and fresh ventilation air streams through a membrane, thereby reducing the energy required for conditioning the fresh ventilation air. Energy exchangers are typically used in buildings with relatively clean building exhaust air, such as office buildings and schools. Recently interest in using energy exchangers in a wider range of buildings has grown, to reduce the energy consumption associated with the heating, ventilating, and airconditioning (HVAC) systems in these buildings. However, if the building exhaust air is not clean, as would be the case for laboratories or factories, new risks are encountered when using energy exchangers. It is possible that gaseous contaminants in the exhaust air may also transfer along with the moisture through the membranes, contaminating the incoming fresh ventilation air. Current test standards provide a test procedure to determine the contamination of the fresh ventilation air by measuring the transfer of an inert tracer gas in an energy exchanger. However, the tracer gas test may not represent the transfer of common indoor air contaminants due to differences in their transport properties. Therefore, in this study, an experimental facility is developed to determine the transfer of seven different contaminants through two membranes (porous and dense) at different flow rates. Contaminant transfer is quantified using a parameter called the exhaust contaminant transfer ratio (ECTR), which gives the fraction of the contaminants transferred from the exhaust air to the fresh ventilation air. A theoretical model based on the effectiveness-number of transfer units (epsilon-NTU) correlation and moisture transfer resistance of the membrane is presented to determine transfer through porous membranes and validated with experimental results. The major contribution of this paper is that it presents a simple method to predict the transfer of different contaminants through a porous membrane based on the moisture transfer resistance of the membrane at different operating conditions. It is found that as contaminant diffusivity decreases, ECTR generally also decreases, and as the flow rate increases, ECTR decreases, which is consistent with the predictions from the correlation.
引用
收藏
页数:17
相关论文
共 61 条
  • [1] Structural Characterization of Thin-Film Polyamide Reverse Osmosis Membranes
    Albo, Jonathan
    Hagiwara, Hideaki
    Yanagishita, Hiroshi
    Ito, Kenji
    Tsuru, Toshinori
    [J]. INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2014, 53 (04) : 1442 - 1451
  • [2] [Anonymous], 2021, ASHRAE HANDBOOK FUNDAMENTALS SI EDITION
  • [3] [Anonymous], 2020, Standard 84 -Method of Testing Air-to-Air Heat/Energy Exchangers
  • [4] ANSI/ASHRAE, 2020, 55 ANSIASHRAE
  • [5] ASHRAE, 2022, ASHRAE Positions on Infectious Aerosols
  • [6] ASHRAE, 2018, 1780-TRP, 'Test method to evaluate cross-contamination of gaseous contaminant within total energy recovery wheels
  • [7] ASME/ANSI, 1998, Performance Test Code 19.1 Test Uncertainty: Instruments and Apparatus
  • [8] Baker R.W, 2012, Membrane Technology and Applications
  • [9] Bergman T. L., 2011, FUNDAMENTALS HEAT MA, DOI DOI 10.1109/TKDE.2004.30
  • [10] Beriault D.A., 2011, MSc thesis