The critical discontinuity of vertical temperature distribution along window opening height from intermediate-scale compartment fire

被引:1
作者
Zhou, Biao [1 ]
Zhou, Hongru [1 ]
Yoshioka, Hideki [2 ]
Wang, Kai [1 ]
Guo, Yige [1 ]
Tao, Zhenxiang [1 ]
Jiang, Chenyang [1 ]
Cui, Kai [1 ]
机构
[1] China Univ Min & Technol Beijing, Sch Emergency Management & Safety Engn, Beijing 100083, Peoples R China
[2] Univ Tokyo, Fac Engn, Dept Architecture, Tokyo 1138654, Japan
基金
美国国家科学基金会;
关键词
Window spill plume; Over-ventilation; The critical temperature discontinuity; Intermediate-scale compartment fires; Building fire; HEAT; WALL;
D O I
10.1016/j.csite.2024.104665
中图分类号
O414.1 [热力学];
学科分类号
摘要
The fire plume spilled from a window is believed to be one of the main fire sources with respect to a building fa & ccedil;ade fire, which happened previously in China. To have a deep understanding of vertical temperature distribution at window opening is of significance. In the current contribution, a series of compartment fire tests under over-ventilation were conducted with a 1.35 m x 1.35 m x 1.35 m compartment to clarify the critical discontinuity position (H D ) by varying window opening sizes, opening aspect and heat release rate (HRR). Temperature history at the window openings were recorded by a thermocouple net. A theoretical calculation method of H D is detailed according to the compartment configuration. It is found that the critical discontinuity area is observed apparently along the window opening height, which has a big temperature difference. By the comparison of experimental and theoretical results, the constant comprehensive coefficient of 1.68, 1.92 and 3.85 of 300 kW, 600 kW and 900 kW are got for an engineered empirical prediction model are proposed, respectively. It provides an insight for the understanding of critical temperature discontinuity and reference for engineering calculations.
引用
收藏
页数:12
相关论文
共 33 条
[1]   Heat and moisture transfer in sol-gel treated cotton fabrics [J].
Alongi, Jenny ;
Malucelli, Giulio .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2013, 111 (01) :459-465
[2]  
[Anonymous], 2015, JIS A 1310 standard test
[3]   Heat release rate calculation in oxygen consumption calorimetry [J].
Chow, W. K. ;
Han, S. S. .
APPLIED THERMAL ENGINEERING, 2011, 31 (2-3) :304-310
[4]   A new correlation for gas temperature inside a burning enclosure [J].
Delichatsios, Michael A. ;
Lee, Yee-Ping ;
Tofilo, Piotr .
FIRE SAFETY JOURNAL, 2009, 44 (08) :1003-1009
[5]  
Gupta V., 2021, INT J HIGH RISE BUIL, V10, P345, DOI DOI 10.21022/IJHRB.2021.10.4.345
[6]   The effect of the sideward wind on the temperature inside a compartment and the spill plume from the window [J].
He, Mingming ;
Li, Linjie ;
Duan, Junrui ;
Hu, Haowei ;
Ji, Jie .
JOURNAL OF BUILDING ENGINEERING, 2023, 75
[7]   Experimental and theoretical study on the characteristics of the spill plume in a compartment fire with high-low opposing openings [J].
Ji, Jie ;
He, Mingming ;
Li, Linjie ;
Zhou, Yuanlong .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2023, 187
[8]  
Karlsson B, 2000, Enclosure fire dynamics, Vfirst
[9]   The physics of the outflow from the opening of an enclosure fire and re-examination of Yokoi's correlation [J].
Lee, Yee-Ping ;
Delichatsios, M. A. ;
Ohmiya, Yoshifumi .
FIRE SAFETY JOURNAL, 2012, 49 :82-88
[10]   Heat fluxes on opposite building wall by flames emerging from an enclosure [J].
Lee, Yee-Ping ;
Delichatsios, M. A. ;
Ohmiya, Yoshifumi ;
Wakatsuki, Kaoru ;
Yanagisawa, Akito ;
Goto, Daisuke .
PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2009, 32 :2551-2558