Optimized gap positions for improved leakage impedance in dry-type transformer design

被引:3
作者
Dawood, Kamran [1 ]
Tursun, Semih [1 ]
机构
[1] Astor Enerji, Ankara, Turkiye
关键词
Dry type transformer; Finite element analysis; Gaps; Leakage impedance; Numerical technique; Optimization; REACTANCE;
D O I
10.1016/j.rineng.2024.102632
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The power and distribution transformers must be properly designed to operate in a variety of conditions and manufactured following all applicable international standards to provide a reliable energy supply to consumers. The transformer can fail if it is improperly designed, and it cannot withstand the short-circuit condition if the short-circuit current is not calculated properly. Short-circuit current can be easily calculated by evaluating the leakage impedance. Customers can also demand the transformer companies to increase or decrease the leakage impedance. This paper evaluates the effect of the gap's position in the four different sections of the high voltage winding on the leakage impedance of the two-winding transformer and proposes effective design options for minimizing the leakage impedance. The accuracy of the finite element models was also investigated using an experimental laboratory transformer model specially designed for optimizing the leakage impedance. The experimental and finite element methods results show that the leakage impedance can be changed to the desired value and limits and easily assessed by the finite element analysis technique. The results indicate that even with the same use of the winding and core material, there was a considerable difference in the leakage impedance for each of the conditions.
引用
收藏
页数:7
相关论文
共 26 条
[1]   Contribution to power transformers leakage reactance calculation using analytical approach [J].
Alves, Bruno S. ;
Kuo-Peng, Patrick ;
Dular, Patrick .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 105 :470-477
[2]   Finite element analysis of natural frequencies of the FGM porous cooling plate with cutouts: A multilayered FGM approach [J].
Amir, Mohammad ;
Lim, Jaehyeong ;
Kim, Sang-Woo ;
Lee, Soo-Yong .
RESULTS IN ENGINEERING, 2023, 20
[3]   Influence of winding angles on hoop stress in composite pressure vessels: Finite element analysis [J].
Azeem, Mohammad ;
Ya, Hamdan H. ;
Alam, Mohammad Azad ;
Kumar, Mukesh ;
Sajid, Zubair ;
Gohery, Scott ;
Maziz, Ammar ;
Gemi, Lokman ;
Abdullah, S. I. B. Syed ;
Khan, Sanan H. .
RESULTS IN ENGINEERING, 2024, 21
[4]   Analytic formulation for the calculation of leakage reactance in wound-core transformers [J].
Castaneda Hernandez, Russby Liliana ;
Diaz Florez, Guillermo Andres ;
Perez Gelves, Jhon Jairo ;
Esteban Mombello, Enrique .
INTERNATIONAL JOURNAL OF APPLIED ELECTROMAGNETICS AND MECHANICS, 2021, 65 (02) :197-213
[5]  
Dahl O.G.C., 1925, Transactions of the American Institute of Electrical Engineers, VXLIV, P785, DOI [10.1109/T-AIEE.1925.5061166, DOI 10.1109/T-AIEE.1925.5061166]
[6]  
Dawood Kamran, 2024, Journal of King Saud University - Engineering Sciences, V36, P572, DOI [10.1016/j.jksues.2022.06.002, 10.1016/j.jksues.2022.06.002]
[7]   Influence of Core's window height on leakage reactance of power transformers [J].
Dawood, Kamran ;
Tursun, Semih .
RESULTS IN ENGINEERING, 2023, 20
[8]   Optimization and analysis of tapping position on leakage reactance of a two winding transformer [J].
Dawood, Kamran ;
Sonmez, Olus ;
Komurgoz, Guven .
ALEXANDRIA ENGINEERING JOURNAL, 2023, 69 :363-369
[9]  
Dawood K, 2023, J ELECTR ENG TECHNOL, V19, P351
[10]   Analysis and optimization of leakage impedance in a transformer with additional winding: A numerical and experimental study [J].
Dawood, Kamran ;
Isik, Fatih ;
Komurgoz, Guven .
ALEXANDRIA ENGINEERING JOURNAL, 2022, 61 (12) :11291-11300