Maximizing the Post-Fault Output Voltages of Cascaded H-Bridge STATCOM With Reserved Cell

被引:3
|
作者
Bisht, Nidhi [1 ]
Das, Anandarup [1 ]
机构
[1] Indian Inst Technol Delhi, Dept Elect Engn, New Delhi 110016, India
关键词
Automatic voltage control; Circuit faults; Harmonic analysis; Fault tolerant systems; Reactive power; Capacitors; Topology; STATCOM; cascaded H-bridge converter; fundamental zero-sequence voltage; harmonic voltages; multiple cell fault-tolerant operation; reserved cell; CONVERTER BASED STATCOM; MULTILEVEL CONVERTERS; OPERATION; RIDE; PWM; STRATEGY; INVERTER; DESIGN; DRIVE;
D O I
10.1109/TIA.2023.3314006
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this article, a novel fundamental zero-sequence voltage (FZSV) expression is proposed for fault-tolerant operation of the cascaded H-bridge (CHB) static synchronous compensator (STATCOM) which helps in providing balanced line voltages with single and multiple number of faulty cells. The challenge of balancing the cell capacitor voltages during post-fault conditions due to addition of FZSV is solved by introducing a reserved cell into the circuit of the CHB STATCOM. Additionally, the reserved cell helps to regain the pre-fault rated line voltages of the faulty CHB STATCOM. Furthermore, the post-fault output voltages from the CHB phases are maximized by adding harmonic voltages using a modified max-min algorithm. However, with unequal number of operating cells during post-fault conditions, cancellation of harmonic voltages in the line voltages does not happen naturally. Hence, in the present article, it is proposed to produce compensatory harmonic voltages from the reserved cell. It helps in eliminating the harmonic voltages from the line voltages while maximizing the post-fault output voltages from the CHB STATCOM. The viability of the proposed idea of post-fault operation of the faulty CHB STATCOM with single and multiple number of faulty cells is verified with MATLAB-Simulink software and experimental prototype developed in the laboratory.
引用
收藏
页码:584 / 595
页数:12
相关论文
共 50 条
  • [1] A Coordinated Control Technique for a Faulty Cascaded H-Bridge STATCOM Under Unbalanced Grid Conditions
    Bisht, Nidhi
    Das, Anandarup
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (06) : 4202 - 4212
  • [2] Cascaded H-bridge Based STATCOM With Improved Ride Through Capability of Submodule Failures
    Neyshabouri, Yousef
    Monfared, Kourosh K.
    Iman-Eini, Hossein
    Xiao, Qian
    Farhadi-Kangarlu, Mohammad
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2022, 69 (04) : 4034 - 4045
  • [3] An Improved Fault-Tolerant Control Scheme for Cascaded H-Bridge STATCOM With Higher Attainable Balanced Line-to-Line Voltages
    Xiao, Qian
    Chen, Linglin
    Jin, Yu
    Mu, Yunfei
    Cupertino, Allan Fagner
    Jia, Hongjie
    Neyshabouri, Yousef
    Dragicevic, Tomislav
    Teodorescu, Remus
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2021, 68 (04) : 2784 - 2797
  • [4] Improvement of Post-Fault Performance of a Cascaded H-bridge Multilevel Inverter
    Ouni, Saeed
    Zolghadri, Mohammad Reza
    Khodabandeh, Masih
    Shahbazi, Mahmoud
    Rodriguez, Jose
    Oraee, Hashem
    Lezana, Pablo
    Ulloa Schmeisser, Andres
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (04) : 2779 - 2788
  • [5] A Circuit Topology of Cascaded H-Bridge STATCOM to Operate With Multiple Faulty Bypassed Cells
    Bisht, Nidhi
    Das, Anandarup
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2021, 57 (05) : 5345 - 5355
  • [6] Low-Capacitance Cascaded H-Bridge Multilevel StatCom
    Farivar, Ghias
    Townsend, Christopher David
    Hredzak, Branislav
    Pou, Josep
    Agelidis, Vassilios G.
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (03) : 1744 - 1754
  • [7] A New Fault-Tolerant Strategy for a Cascaded H-Bridge Based STATCOM
    Neyshabouri, Yousef
    Iman-Eini, Hossein
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (08) : 6436 - 6445
  • [8] Comparison of Capacitor Voltages Balancing Methods for Cascaded H-bridge STATCOM
    Abdulveleev, I. R.
    Khramshin, T. R.
    Kornilov, G. P.
    2017 INTERNATIONAL CONFERENCE ON INDUSTRIAL ENGINEERING, APPLICATIONS AND MANUFACTURING (ICIEAM), 2017,
  • [9] Discretized Discontinuous Modulation Strategy for Cascaded H-Bridge StatCom
    Liu, Qingxiang
    Rodriguez, Ezequiel
    Farivar, Glen Ghias
    Pou, Josep
    Leyva, Ramon
    Townsend, Christopher D. D.
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2023, 70 (07) : 7235 - 7245
  • [10] A Fast Filtering Scheme for Capacitor Voltages of a Cascaded H-Bridge Multilevel Converter Based STATCOM
    Farivar, Ghias
    Agelidis, Vassilios G.
    Hredzak, Branislav
    2014 16TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'14-ECCE EUROPE), 2014,