A study of the response of reinforced concrete frames with and without masonry infill walls to earthquake motions

被引:6
作者
Monical, Jonathan [1 ,3 ]
Pujol, Santiago [2 ]
机构
[1] Tohoku Univ, Dept Architecture & Bldg Sci, Sendai, Japan
[2] Univ Canterbury, Dept Civil Engn, Christchurch, New Zealand
[3] 980-8579 Engn Lab Complex Bldg,6-6-11-1220, Sendai, Japan
基金
美国国家科学基金会;
关键词
Masonry; Infill; Walls; Reinforced concrete; Earthquake; Seismic Response; Drift Demand Drift Capacity; Strengthening; Repair; Retrofit; R/C FRAMES; RC FRAMES; BEHAVIOR; BUILDINGS;
D O I
10.1016/j.istruc.2024.106345
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In developing countries prone to frequent earthquakes, it is common practice to use masonry infill walls as partitions in reinforced concrete frame buildings. Frames with infill have smaller drift demands and smaller drift capacities relative to similar frames without infill. Whether the relative reduction in drift demand offsets the plausible reduction in drift capacity remains open to discussion. This investigation provides experimental evidence on drift demands and drift capacities for both frames with and frames without infill. To make fair comparisons, only experiments where sets of nominally identical reinforced concrete frames, at least one frame with no infill and at least one frame with infill, are considered. Because many static experiments provide evidence for the reduction in drift capacity caused by infill, the objective of the dynamic experiments described in this study is to quantify the reduction in drift demand attributed to infill. Results of dynamic tests show that frames with infill drifted no more than one-third the amount similar frames without infill drifted in simulated base motions of the same intensity. Results of static tests show that the smallest drift capacities of frames with infill were approximately one-half of the drift capacities of similar frames without infill. These two experimental observations indicate that infill reduces drift demand more than it reduces drift capacity suggesting an overall beneficial effect of the infill. Field data were used to test this idea. Based on surveys of low-rise school buildings, RC frames with more full-height infill walls tend to have less earthquake damage than frames with less infill. A convenient method to quantify the amount of infill walls in buildings is computing wall ratios defined as the ratio of crosssectional area of masonry infill walls on ground floor to total floor area above ground floor. Projections of the field data suggest that infill wall ratios of at least 0.5% in both directions of a building reduce the likelihood of severe structural damage by 300% compared with smaller ratios. The use of infill presents an inexpensive yet effective retrofit technique, even if only for temporary use, for strengthening buildings vulnerable to earthquake damage.
引用
收藏
页数:16
相关论文
共 35 条
[1]   Quasi-Static Testing of RC Infilled Frames and Confined Stone-Concrete Bearing Walls [J].
Al-Nimry, Hanan S. .
JOURNAL OF EARTHQUAKE ENGINEERING, 2014, 18 (01) :1-23
[2]  
Alwashali H, 2020, BULL N Z SOC EARTHQ, V53, P13
[3]   Experimental observations on the in-plane behaviour of masonry wall infilled RC frames; focusing on deformation limits and backbone curve [J].
Alwashali, Hamood ;
Torihata, Yuta ;
Jin, Kiwoong ;
Maeda, Masaki .
BULLETIN OF EARTHQUAKE ENGINEERING, 2018, 16 (03) :1373-1397
[4]   NGA-West2 Database [J].
Ancheta, Timothy D. ;
Darragh, Robert B. ;
Stewart, Jonathan P. ;
Seyhan, Emel ;
Silva, Walter J. ;
Chiou, Brian S. -J. ;
Wooddell, Katie E. ;
Graves, Robert W. ;
Kottke, Albert R. ;
Boore, David M. ;
Kishida, Tadahiro ;
Donahue, Jennifer L. .
EARTHQUAKE SPECTRA, 2014, 30 (03) :989-1005
[5]  
[Anonymous], 2016, 2016 Taiwan (Meinong) Earthquake
[6]  
[Anonymous], 2018, Buildings Surveyed after the 2017 Mexico City Earthquakes
[7]  
Baran M, 2010, INT J PHYS SCI, V5, P1981
[8]   Seismic strengthening of low-rise reinforced concrete frame structures with masonry infill walls: Shaking-table test [J].
Benavent-Climent, A. ;
Ramirez-Marquez, A. ;
Pujol, S. .
ENGINEERING STRUCTURES, 2018, 165 :142-151
[9]  
Blackard B., 2009, ACI Special Publication, V9
[10]   Lateral Load Behavior of an Open-Ground-Story RC Building with AAC Infills in Upper Stories [J].
Bose, Supratik ;
Rai, Durgesh C. .
EARTHQUAKE SPECTRA, 2016, 32 (03) :1653-1674