Research on Inversion Model of Winding Hot Spot Temperature of 10-kV Oil-Immersed Three-Dimensional Coiled Core Transformer

被引:0
|
作者
Chen, Qianyi [1 ,2 ]
Chen, Shaonan [1 ]
Huang, Weixiang [1 ,2 ]
Zhang, Wei [1 ,2 ]
Li, Kewen [1 ]
机构
[1] Guangxi Power Grid Co Ltd, Elect Power Res Inst, Nanning 530023, Peoples R China
[2] Guangxi Power Grid Equipment Monitoring & Diag Eng, Nanning 530023, Peoples R China
来源
IEEE ACCESS | 2024年 / 12卷
关键词
Oil insulation; Temperature measurement; Windings; Power transformer insulation; Oils; Mathematical models; Current transformers; Immersion cooling; Power electronics; Oil-immersed transformer; temperature fluid field; streamline extraction; hot spot temperature inversion; power equipment status monitoring;
D O I
10.1109/ACCESS.2023.3305254
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Realizing online monitoring of the hot spot temperature of grid mounted transformer windings is a challenge for the power industry. The heat exchange process between the internal heat source area and the external field area of the transformer is the direct cause of the temperature increase of the transformer shell. In this paper, based on the numerical coupling calculation of temperature - fluid field of 10kV oil immersed solid coiled iron core transformer, the typical heat flow streamline is extracted, and the measurable temperature characteristic points strongly correlated to the winding hot spot temperature are selected in the heat dissipation area of the shell, and the inversion model of the transformer winding hot spot temperature is established. This article verifies the effectiveness of the simulation results and the accuracy of the inversion model through the multi condition temperature rise test of transformer. The maximum error between the calculated steady-state temperature rise of each temperature measurement point in the simulation model and the test value is no more than 3 degrees C, the simulation calculation results are in good agreement with the test results, and the average absolute error of the inversion model winding hot spot temperature inversion is 2.67 %, the maximum temperature difference is less than 3 degrees C. This research provides an effective method for online monitoring of the hot spot temperature of the winding of a 10kV oil-immersed three-dimensional coil iron core transformer, and provides a reference for the state detection of grid mounted transformers.
引用
收藏
页码:97691 / 97700
页数:10
相关论文
共 10 条
  • [1] A Method for Hot Spot Temperature Prediction of a 10 kV Oil-Immersed Transformer
    Deng, Yongqing
    Ruan, Jiangjun
    Quan, Yu
    Gong, Ruohan
    Huang, Daochun
    Duan, Cihan
    Xie, Yiming
    IEEE ACCESS, 2019, 7 : 107380 - 107388
  • [2] Establishment and Verification of 10kV Oil Immersed Transformer Winding Hot Spot Temperature Inversion Model Based on Streamline Analysis
    Deng Y.
    Ruan J.
    Dong X.
    Huang D.
    Zhang C.
    Xian R.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (08): : 3191 - 3203
  • [3] Research on the Relationship between Hot Spot Transient Temperature Rise and Ambient Temperature of Oil-immersed Transformer
    Li, Chenlong
    Wang, Zhaoxin
    Fan, Lixin
    Wang, Yongqiang
    Chu, Haijun
    PROCEEDINGS OF 2018 IEEE 4TH INFORMATION TECHNOLOGY AND MECHATRONICS ENGINEERING CONFERENCE (ITOEC 2018), 2018, : 782 - 786
  • [4] 3D modeling of winding hot spot temperature in oil-immersed transformers
    Reza Kebriti
    S. M. Hassan Hossieni
    Electrical Engineering, 2022, 104 : 3325 - 3338
  • [5] 3D modeling of winding hot spot temperature in oil-immersed transformers
    Kebriti, Reza
    Hossieni, S. M. Hassan
    ELECTRICAL ENGINEERING, 2022, 104 (05) : 3325 - 3338
  • [6] Dynamic Inversion Method of Hot Spot Temperature of Oil-immersed Transformer Based on Combination of Multiphysics Simulation and Neural Network Algorithm
    Ni Z.
    Sheng G.
    Zhang L.
    Wang F.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (06): : 2466 - 2477
  • [7] RESEARCH ON HOT SPOT TEMPERATURE INVERSION METHOD OF OIL-IMMERSED TRANSFORMER BASED ON MULTI-PHYSICAL FIELD COUPLING OF MAGNETIC-THERMAL-FLUID
    Gu, Lingyun
    Yuan, Fating
    Zhang, Naiyue
    Bai, Xuefeng
    Zhang, Xin
    Gao, Wenpeng
    Wu, Yan
    Bai, Zhixin
    THERMAL SCIENCE, 2025, 29 (1A): : 199 - 213
  • [8] Three-dimensional Magnetic Field Model Order Reduction and Loss Analysis of 110 kV Oil-immersed Transformer Based on Twin Builder
    Zhang Z.
    Liu D.
    Gao C.
    Liu Y.
    Liu G.
    Gaodianya Jishu/High Voltage Engineering, 2024, 50 (03): : 941 - 951
  • [9] RESEARCH ON TEMPERATURE RISE CALCULATION AND HOT SPOT TEMPERATURE INVERSION METHOD FOR OIL IMMERSED TRANSFORMER BASED ON MAGNETIC-THERMAL-FLUID
    Yuan, Fating
    Zhang, Naiyue
    Shi, Wenyu
    Gu, Lingyun
    Zeng, Jihao
    Tang, Bo
    THERMAL SCIENCE, 2024, 28 (4B): : 3307 - 3323
  • [10] Oil-immersed transformer online hot spot temperature monitoring and accurate life lose calculation based on fiber Bragg grating sensor technology
    Zhang, Xin
    Huang, Ronghui
    Huang, Weizhao
    Yao, Shenjing
    Hou, Dan
    Zheng, Min
    2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,