Study on efficient heating method by solar coupled air source heat pump system with phase change heat storage in severe cold region

被引:13
作者
Gao, Jinshuang [1 ,2 ]
Li, Sheng [1 ,2 ]
Wu, Fan [1 ,2 ]
Jiang, Long [1 ,2 ]
Zhao, Yazhou [1 ,2 ]
Zhang, Xuejun [1 ,2 ]
机构
[1] Zhejiang Univ, Inst Refrigerat & Cryogen, Coll Energy Engn, Hangzhou 310027, Peoples R China
[2] Zhejiang Univ, Jiaxing Res Inst, Key Lab Clean Energy & Carbon Neutral Zhejiang Pro, 1300 Dongshengxi Rd China, Jiaxing 314051, Peoples R China
基金
中国国家自然科学基金;
关键词
Air source heat pump; Solar energy; Phase change heat storage; System control; THERMAL STRATIFICATION; VAPOR INJECTION; ENERGY; OPTIMIZATION; COMPRESSOR; PERFORMANCE; PCM;
D O I
10.1016/j.apenergy.2024.123206
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In order to reduce carbon emissions and promote the development of sustainable buildings, it is essential to combine solar energy with air source heat pumps. Nonetheless, challenges persist regarding the intermittent and unstable nature of solar energy, coupled with the limited utilization of air source heat pumps in colder climates. Actually, the benefits of the two technologies could be combined to create one of the most efficient heating systems for extremely cold regions by utilizing phase change material for heat storage. This study centers on a heating system that couples dual heat sources for enhanced efficiency. The system utilizes phase change materials for heat storage and introduces an effective operational control strategy. Furthermore, influence of various critical parameters on the composite system is explored. The experiment demonstrated that average power consumption of the compressor is 1.87 kW, which is 21.1% lower and the average coefficient of performance of the system is 5.42, exceeding the original system by 143.0%. Furthermore, the novel system requires just 1.8 h to finish heat storage, which is shortened to 32.7% of the previous system. The enhanced system has now become more efficient and user-friendly, while also boasting improved functionality in low-temperature environments. These improvements are particularly advantageous when the heating system is deployed in regions with severely cold climates.
引用
收藏
页数:14
相关论文
共 37 条
[1]   The development of a finned phase change material (PCM) storage system to take advantage of off-peak electricity tariff for improvement in cost of heat pump operation [J].
Agyenim, Francis ;
Hewitt, Neil .
ENERGY AND BUILDINGS, 2010, 42 (09) :1552-1560
[2]   The simulation of performance of seasonal heat storage coupled to solar-assisted heat pump in Jordan [J].
Al-Dabbas M.A.A. .
Applied Solar Energy, 2009, 45 (2) :83-92
[3]   Numerical modeling and optimization of thermal stratification in solar hot water storage tanks for domestic applications: CFD study [J].
Bouhal, T. ;
Fertahi, S. ;
Agrouaz, Y. ;
El Rhafiki, T. ;
Kousksou, T. ;
Jamil, A. .
SOLAR ENERGY, 2017, 157 :441-455
[4]   Towards low carbon homes - A simulation analysis of building-integrated air-source heat pump systems [J].
Cabrol, Loic ;
Rowley, Paul .
ENERGY AND BUILDINGS, 2012, 48 :127-136
[5]  
Cleland A.C., 1986, Int. J. Refrige., V9, P346, DOI [10.1016/0140-7007(86)90006-X, DOI 10.1016/0140-7007(86)90006-X]
[6]   Does heat pumps perform energy efficiently as we expected: Field tests and evaluations on various kinds of heat pump systems for space heating [J].
Deng, Jiewen ;
Wei, Qingpeng ;
Liang, Mei ;
He, Shi ;
Zhang, Hui .
ENERGY AND BUILDINGS, 2019, 182 :172-186
[7]   Experimental investigation on storage-type heat pump system for efficient supply in cold region [J].
Gao, J. S. ;
Wu, F. ;
Jiang, L. ;
Fan, Y. B. ;
Yu, M. ;
Wang, Z. W. ;
Zhang, X. J. .
ENERGY CONVERSION AND MANAGEMENT, 2022, 268
[8]   Study on the performance of solar-assisted transcritical CO2 heat pump system with phase change energy storage suitable for rural houses [J].
Han, Zongwei ;
Bai, Chenguang ;
Ma, Xiao ;
Li, Biao ;
Hu, Honghao .
SOLAR ENERGY, 2018, 174 :45-54
[9]   Experimental study of enhancing heating performance of the air-source heat pump by using a novel heat recovery device designed for reusing the energy of the compressor shell [J].
Huang, Bi ;
Jian, Qifei ;
Luo, Lizhong ;
Zhao, Jing .
ENERGY CONVERSION AND MANAGEMENT, 2017, 138 :38-44
[10]   Evaluation of phase change thermal storage in a cascade heat pump [J].
Huang, Ransisi ;
Mahvi, Allison ;
James, Nelson ;
Kozubal, Eric ;
Woods, Jason .
APPLIED ENERGY, 2024, 359