Experimental investigation on the condensation heat transfer coefficient and frictional pressure drop of R-513A and R-134a in commercial refrigeration tubes

被引:3
作者
Arkadumnuay, Thana [1 ]
Manova, Stephen [1 ]
Leunanonchai, Witsawat [1 ]
Asirvatham, Lazarus Godson [2 ]
Wongwises, Somchai [1 ,3 ]
机构
[1] King Mongkuts Univ Technol Thonburi KMUTT, Fac Engn, Dept Mech Engn, Fluid Mech Thermal Engn & Multiphase Flow Res Lab, Bangkok 10140, Thailand
[2] Karunya Inst Technol & Sci, Ctr Res Mat Sci & Thermal Management CRMS & TM, Dept Mech Engn, Coimbatore 641114, Tamil Nadu, India
[3] Natl Sci & Technol Dev Agcy NSTDA, Pathum Thani 12120, Thailand
关键词
Micro -fin tube; Condensation; Heat transfer; Frictional pressure drop; R-513A; LOW GWP REFRIGERANT; 2-PHASE FLOW PATTERN; HORIZONTAL SMOOTH; R134A; R513A; HFC-134A; R1234YF;
D O I
10.1016/j.ijheatmasstransfer.2024.125735
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental investigation to determine the average heat transfer coefficient (hav) and frictional pressure drop (Delta PF) characteristic of R-513A and R-134a in a smooth tube (ST) and micro-fin tube (MFT) is carried out. A 2500 mm long counter-flow tube-in-tube heat exchanger made of copper is used for conducting experiments. The ST and MFT with inner diameters (Di) of 6.74 and 6.82 mm, respectively, are experimentally tested for various operating conditions such as saturation temperatures (Tsat = 40 to 50 degrees C), heat fluxes (q" =9.8 to 19.6 kW/m2), mass fluxes (G = 575 to 770 kg/m2s) and average vapor qualities (xav = 0.2 to 0.9). The influence of q", G, and Tsat on hav and Delta PF are discussed. First, a comparison between R-513A and R-134a in an ST showed maximum reductions of 16 and 20 % in hav and Delta PF, respectively for R-513A, when compared to R-134a. Second, the MFT, due to its higher heat transfer area, resulted in 69 % and 120 % enhancements in hav and Delta PF, respectively, compared to that of an ST. Hence, the findings of this research provide information that is currently useful to the thermal industries, affirming that R-513A can be a suitable long-term alternative refrigerant.
引用
收藏
页数:16
相关论文
共 43 条
[11]   Experimental investigation on the flow condensation of R450A, R515B, and R1234ze(E) in a 7.0 mm OD micro-fin tube [J].
Diani, Andrea ;
Liu, Yuce ;
Wen, Jian ;
Rossetto, Luisa .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 196
[12]   Condensation of an Azeotropic Mixture inside 2.5 mm ID Minitubes [J].
Diani, Andrea ;
Rossetto, Luisa .
FLUIDS, 2020, 5 (04)
[13]   R513A condensation heat transfer inside tubes: Microfin tube vs. smooth tube [J].
Diani, Andrea ;
Brunello, Pierfrancesco ;
Rossetto, Luisa .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 152
[14]   Low GWP refrigerants condensation inside a 2.4 mm ID microfin tube [J].
Diani, Andrea ;
Campanale, Manuela ;
Cavallini, Alberto ;
Rossetto, Luisa .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 86 :312-321
[15]   R1234yf condensation inside a 3.4 mm ID horizontal microfin tube [J].
Diani, Andrea ;
Cavallini, Alberto ;
Rossetto, Luisa .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 75 :178-189
[16]  
Dittus F. W., 1930, U CALIF BERKELEY PUB, V2, P443, DOI [DOI 10.1016/0735-1933(85)90003-X, 10.1016/0735-1933(85)90003-X]
[17]   Condensation in horizontal tubes, part 1: two-phase flow pattern map [J].
El Hajal, J ;
Thome, JR ;
Cavallini, A .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2003, 46 (18) :3349-3363
[18]  
Gaithersburg M.D., 1998, NIST Standard Reference Database Version 6.01
[19]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[20]   Experimental two-phase heat transfer coefficient and frictional pressure drop inside mini-channels during condensation with R1234yf and R134a [J].
Illan-Gomez, F. ;
Lopez-Belchi, A. ;
Garcia-Cascales, J. R. ;
Vera-Garcia, F. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 51 :12-23