Research on the countermeasures of the single-phase-to-earth faults in flexibly grounded distribution networks

被引:2
|
作者
Ren, Xiaofeng [1 ,2 ]
Bai, Yunhao [1 ]
Dai, Yongzheng [1 ]
Liang, Rui [1 ]
Gao, Hailong [2 ]
Su, Lingdong [2 ]
Zhang, Xiao [2 ]
Kong, Lingchang [3 ]
Zhang, Peng [1 ]
机构
[1] China Univ Min & Technol, Sch Elect Engn, Xuzhou 221116, Jiangsu, Peoples R China
[2] State Grid Xuzhou Power Supply Co, Xuzhou 221005, Jiangsu, Peoples R China
[3] Kehua Data Co Ltd, Xiamen 361000, Fujian, Peoples R China
关键词
Flexible grounding; Distribution network; Fault feeder detection; Fault disposal; LINE SELECTION;
D O I
10.1016/j.aej.2024.04.020
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In a neutral, flexible, grounded distribution network, the phenomenon that a single-phase ground fault with high impedance connected in parallel with a low resistance can result in a relatively lower zero-sequence current flowing through the faulty feeder. This zero-sequence current can make it a challenge to use zero-sequence protection schemes to accurately identify and effectively protect the faulty feeder. In terms of the aforementioned challenge, based on the zero-sequence equivalent circuit of a single-phase-to-earth fault, this paper conducts an investigation on the phase difference between the zero-sequence current and the non-fault phase line voltage at power frequency in flexible grounding distribution network with different grounded conditions, both before and after the introduction of a parallel low-resistor connection. Subsequently, a criterion for selecting the faulty feeder is developed based on the observed phase difference characteristics following the implementation of the parallel low-resistor connection. Furthermore, a disposal strategy for single-phase-to-earth faults is formulated, which takes fault resistance estimation into account. To validate the proposed method, a simulation model of a flexible grounding distribution network is implemented with PSCAD/EMTDC. The effectiveness and reliability of this method in multiple scenes, including the initial fault conditions, sampling frequency, and distributed generation (DG), are proved through simulation results.
引用
收藏
页码:68 / 79
页数:12
相关论文
共 50 条
  • [21] A novel single-phase-to-earth fault line method in small current grounding systems
    Jiao Shangbin
    Guo Jingwen
    Li Yunjun
    Xiao Ting
    PROCEEDINGS OF THE 38TH CHINESE CONTROL CONFERENCE (CCC), 2019, : 7310 - 7315
  • [22] Technique for differentiation between ferroresonance and single-phase-to-earth fault in isolated neutral point system
    Qi, Zheng
    Dong, Di
    Yang, Yihan
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (01): : 55 - 58
  • [23] Detection of resistive single-phase earth faults in a compensated power-distribution system
    Leitloff, V
    Feuillet, R
    Griffel, D
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 1997, 7 (01): : 65 - 73
  • [24] Single-phase-to-earth fault detection for high voltage transmission line based on wavelet analysis
    Yang, Zhuan
    Dong, Aihua
    FRONTIERS OF MANUFACTURING SCIENCE AND MEASURING TECHNOLOGY, PTS 1-3, 2011, 230-232 : 559 - 563
  • [25] Technology of fault line selection for single-phase-to-earth fault in small current grounding system
    Li, Bo
    NONLINEAR DYNAMICS, 2012, 67 (03) : 2111 - 2122
  • [26] Artificial neural networks for single phase fault detection in resonant grounded power distribution systems
    Assef, Y
    Bastard, P
    Meunier, M
    1996 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE PROCEEDINGS, 1996, : 566 - 572
  • [27] Earth Fault Location for Non-Directly Grounded Distribution Networks
    Pang, Qingle
    Wang, Yangjie
    Wang, Yanqian
    Cao, Tong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (02) : 706 - 717
  • [28] Technology of fault line selection for single-phase-to-earth fault in small current grounding system
    Bo Li
    Nonlinear Dynamics, 2012, 67 : 2111 - 2122
  • [29] Location Method Based on Fuzzy Entropy for Single Phase to Ground Faults in Non-effectively Grounded Distribution Network
    Li, Lin
    Gao, Houlei
    Liu, Zhen
    Yuan, Tong
    2023 IEEE BELGRADE POWERTECH, 2023,
  • [30] Detection and experimental investigation of open conductor and single-phase earth return faults in distribution systems
    Esmail, Ehab M.
    Elgamasy, Mahmoud M.
    Kawady, Tamer A.
    Taalab, Abdel-Maksoud, I
    Elkalashy, Nagy, I
    Elsadd, Mahmoud A.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 140