Thermal behaviour of a transformer mineral oil-tank surface under incipient turn-to-turn short-circuit fault

被引:0
|
作者
Chen, Si [1 ]
Luo, Yingting [2 ]
Sheng, Gehao [1 ]
Jiang, Junfei [2 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, 800 Dongchuan Rd, Shanghai 200240, Peoples R China
[2] Guangdong Power Grid Co Ltd, Elect Power Res Inst, Guangzhou, Peoples R China
关键词
temperature distribution; temperature measurement; thermal analysis; transformer windings; AGING ASSESSMENT MODEL; FUNDAMENTAL APPROACH;
D O I
10.1049/smt2.12200
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A slight turn-to-turn short-circuit fault in the incipient stage does not trigger fuse protection, and the regular transmission and transformation functions of the transformer within the power grid are not affected very much by the incipient turn-to-turn short-circuit fault. Therefore, the incipient turn-to-turn short-circuit faults are often undetected, resulting in massive accidents. Incipient turn-to-turn short-circuit faults lead to localized overheating in the transformer, which changes the transformer's oil-tank surface temperature (OTST). A thermal simulation model (TSM) is presented. Based on the TSM, OTST data with different load rates and fault parameters are collected. The steady-state and transient characteristics of OTST are analysed by extracting the OTST feature vector and the temperature difference of specific regions. The results show that the growth of the heat production value of faulty coils causes a rise in the OTST; higher faulty coils' locations lead to wider OTST differences; the temperature difference's area S can follow the incipient short-circuit fault in the first 20 min after it occurs, which is faster than the top oil temperature. This study gives insight into the thermal behaviour of OTST, assisting in fault detection and location at the incipient fault stage. This paper proposed a thermal simulation model of the oil-immersed transformer and analysed the oil-tank surface's steady-state and transient thermal behaviours under incipient turn-to-turn short-circuit faults. The oil-tank surface temperature (OTST) feature vector b is proposed to show the overall thermal behaviour of the oil-tank surface, and the temperature difference of the specific regions TF(S, hF) is analysed to show the local thermal behaviour. The proposed dynamic analysis and steady-state methods of analysing the thermal behaviour of OTST can help guide online monitoring and fault detection of transformers. image
引用
收藏
页码:310 / 323
页数:14
相关论文
共 50 条
  • [21] Effective Mathematical Model of Synchronous Machine with Turn-to-turn Short-circuit of Rotor Winding for Adaptive Methods of Identification
    Polishchuk, V., I
    Baratova, K., V
    2019 INTERNATIONAL CONFERENCE ON INDUSTRIAL ENGINEERING, APPLICATIONS AND MANUFACTURING (ICIEAM), 2019,
  • [22] Research on inter-turn short-circuit fault of power transformer by using third harmonic
    Su, Zhonghuan
    Luo, Longfu
    IET RENEWABLE POWER GENERATION, 2023, 17 (11) : 2791 - 2800
  • [23] Analysis of Parameters and Characteristics of Inter-turn Short-circuit Fault on Primary Side of Transformer
    Ye Z.
    Gou J.
    Cai J.
    Zeng W.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (21): : 213 - 220
  • [24] Analysis of Turn-to-Turn Fault on Split-Winding Transformer Using Coupled Field-Circuit Approach
    Yang, Cunxiang
    Ding, Yiwei
    Qiu, Hongbo
    Xiong, Bin
    PROCESSES, 2021, 9 (08)
  • [25] Brushless Synchronous Generator Turn-to-Turn Short Circuit Fault Detection Using Multilayer Neural Network
    Tun, Pyae Phyo
    Kumar, Padmanabhan Sampath
    Pratama, Ryan Arya
    Liu Shuyong
    2018 ASIAN CONFERENCE ON ENERGY, POWER AND TRANSPORTATION ELECTRIFICATION (ACEPT), 2018,
  • [26] Method for measuring AC impedance of generator rotor and effects on decision of turn-to-turn short circuit fault
    Yang, H.
    Zhao, H.
    Dianli Xitong Zidonghue/Automation of Electric Power Systems, 2001, 25 (11):
  • [27] Study on Magnetic Field Distribution of Turn-to-turn short-circuit of Dry-type Air-core Reactor
    Song, Han
    Zou, Liang
    Han, Zhiyun
    Zhao, Tong
    Yang, Xiaoshuai
    PROCEEDINGS OF 2017 CHINA INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC 2017), 2017, : 515 - 520
  • [28] Conceptual Approach to Permanent Magnet Synchronous Motor Turn-to-Turn Short Circuit and Uniform Demagnetization Fault Diagnosis
    Yu, Yinquan
    Yuan, Chun
    Zeng, Dequan
    Carbone, Giuseppe
    Hu, Yiming
    Yang, Jinwen
    ACTUATORS, 2024, 13 (12)
  • [29] Inter-turn short-circuit fault location for transformer winding based on traveling wave analysis
    Liu, Da
    Peng, Minfang
    Wan, Xun
    Li, Zhuoxin
    Shen, Mei'e
    Yi Qi Yi Biao Xue Bao/Chinese Journal of Scientific Instrument, 2015, 36 (09): : 2091 - 2096
  • [30] Inter turn short-circuit fault research on generator rotor windings
    Li, YG
    Li, HM
    Zhu, L
    Zhao, H
    ICEMS'2001: PROCEEDINGS OF THE FIFTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS I AND II, 2001, : 357 - 360