MITIGATION OF POWER QUALITY PROBLEMS IN STEEL PLANTS USING STATIC SYNCHRONOUS COMPENSATOR

被引:0
作者
Djeghader, Yacine [1 ]
Bousnoubra, Choayb [1 ]
Allele, Selma [1 ]
机构
[1] Univ Mohamed Cherif Messaadia, LEER Lab, Souk Ahras, Algeria
来源
REVUE ROUMAINE DES SCIENCES TECHNIQUES-SERIE ELECTROTECHNIQUE ET ENERGETIQUE | 2024年 / 69卷 / 03期
关键词
Electrical arc furnace (EAF); Flicker; Fuzzy logic controller (FLC); Harmonics; Power quality; Static synchronous compensator (STATCOM); Steel plant;
D O I
10.59277/RRST-EE.2024.69.3.6
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper focuses on mitigating various power quality issues from electric arc furnaces (EAF) in steel plants, including voltage flicker, sag, swell, and harmonics. Arc furnaces are recognized as one of the industry's most nonlinear electrically polluting loads. The proposed solution in this article to address all power quality issues caused by EAF is implementing a flexible power supply strategy known as a static synchronous compensator (STATCOM) for injecting reactive energy into the electrical grid. In this study, an experimental model of EAF is utilized based on real measurements of the variation of arc resistance and arc reactance during the melting phase. The pulse width modulation (PWM) technique is employed for current tracking feedback control to generate the required reactive current. A fuzzy logic controller (FLC) is employed for the DC bus.
引用
收藏
页码:293 / 297
页数:5
相关论文
共 14 条
[1]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[2]   FUZZY LOGIC CONTROLLED STATCOM WITH A SERIES COMPENSATED TRANSMISSION LINE ANALYSIS [J].
Arockiaraj, Sesaiya ;
Manikandan, Bairavan Veerayan ;
Bhuvanesh, Ananthan .
REVUE ROUMAINE DES SCIENCES TECHNIQUES-SERIE ELECTROTECHNIQUE ET ENERGETIQUE, 2023, 68 (03) :307-312
[3]  
Daou N, 2019, REV ROUM SCI TECH-EL, V64, P391
[4]  
Djeghader Y, 2008, International Review of Modelling and Simulations (IREMOS), P173
[5]  
Djeghader Y., 2009, Journal of Electrical Engineering (JEE), V9, P25
[6]  
Gavrilas M, 2021, REV ROUM SCI TECH-EL, V66, P21
[7]   Improvement of electrical arc furnace operation with an appropriate model [J].
Hocine, Labar ;
Yacine, Djeghader ;
Kamel, Bounaya ;
Samira, Kelaiaia Mounia .
ENERGY, 2009, 34 (09) :1207-1214
[8]  
Hooshmand R, 2008, J ELECTR ENG-SLOVAK, V59, P195
[9]   A control system for dc arc furnaces for power quality improvements [J].
Lazaroiu, G. C. ;
Zaninelli, D. .
ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (12) :1498-1505
[10]   Fuzzy logic controller for three-level shunt active filter compensating harmonics and reactive power [J].
Saad, S. ;
Zellouma, L. .
ELECTRIC POWER SYSTEMS RESEARCH, 2009, 79 (10) :1337-1341