Transient Stability Analysis for Grid-Tied VSG Considering High-Order Nonlinear Interactions Between Active and Reactive Power Control Loops

被引:2
|
作者
Li, Xilin [1 ]
Feng, Pan [1 ]
Tian, Zhen [1 ]
Huang, Meng [1 ]
Shu, Sirui [1 ,2 ]
Zha, Xiaoming [1 ]
Hu, Pan
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Hubei Key Lab Power Equipment & Syst Secur Integr, Wuhan 430072, Peoples R China
[2] State Grid Hubei Econ Res Inst, Wuhan 430077, Peoples R China
关键词
Transient analysis; Power system stability; Damping; Stability criteria; Iterative methods; Voltage; Nonlinear dynamical systems; Equal area criterion; high-order systems; iterative approximation; transient stability; virtual synchronous generators; VIRTUAL SYNCHRONOUS GENERATORS; SYNCHRONIZATION STABILITY;
D O I
10.1109/TPEL.2024.3377806
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transient stability issues of power converter systems have attracted much attention. Generally, the converter systems behave in high-order nonlinear dynamics due to multiple cascaded control loops, which become obstacles for transient stability analysis. Considering the dynamic coupling between active power and reactive power control loops, the grid-tied virtual synchronous generators (VSG) system is a third-order nonlinear system. Including the equal area criterion (EAC), many conventional methods are only applicable to second-order systems and cannot fully capture damping effects. To fill this gap, a novel iterative EAC method is proposed to handle the transient stability of the third-order VSG system. First, an implicit relationship from the output voltage to the power angle is derived by integral substitution. From energy aspects, the dynamic relations between voltage, power angle, and frequency are approximated by algebraic equations through iterative calculation. The impact of nonlinear damping is also fully captured quantitatively. Both conservatism and quantity of computation are improved compared with previous studies. Furthermore, the critical clearing angles under different disturbance forms and degrees are derived. In addition, some discussions about current limiters' influence and different controller parameters' influence are given. Simulation and hardware-in-the-loop experiments based on RT-Lab are conducted to verify the accuracy of the proposed method.
引用
收藏
页码:6974 / 6988
页数:15
相关论文
共 40 条
  • [21] A Day and Night Operational Quasi-Z Source Multilevel Grid-Tied PV Power System to Achieve Active and Reactive Power Control
    Liang, Weihua
    Liu, Yitao
    Peng, Jianchun
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2021, 36 (01) : 474 - 492
  • [22] Interval type-2 fuzzy logic controller based grid-tied solar PV inverter with active and reactive power control
    Venkatasamy, B.
    Kalaivani, L.
    JOURNAL OF INTELLIGENT & FUZZY SYSTEMS, 2022, 43 (03) : 2299 - 2314
  • [23] Dynamic Reactive Power Allocation Method of Power Grid with High-Permeability PV Considering Transient Voltage Stability
    Li, Yangyang
    Yang, Dongfeng
    Liu, Chuang
    Guo, Dongbo
    Gu, Yichen
    Li, Jiahe
    ENERGIES, 2024, 17 (05)
  • [24] Dynamic reactive power planning method for power grid with high permeability wind power and photovoltaic considering transient voltage stability
    Xu Y.
    Jiang W.
    Wang P.
    Mi L.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2022, 42 (08): : 79 - 88
  • [25] Active/Reactive Power Control of PV Grid-tied NPC Inverter Using 3-D Space Vector Modulation in abc Coordinate
    Tafti, Hossein Dehghani
    Maswood, Ali I.
    Roomi, Muhammad M.
    2015 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT ASIA), 2015,
  • [26] Modeling and control of a single-phase grid-tied medium-frequency isolated converter for active and reactive power management in photovoltaic applications
    Viera-Diaz, Rosa Iris
    Gonzalez-Garcia, Mario
    Alvarez-Salas, Ricardo
    Miranda, Homero
    Leon-Ruiz, Yuniel
    Cardenas, Victor
    MATHEMATICS AND COMPUTERS IN SIMULATION, 2024, 223 : 380 - 393
  • [27] Power System Transient Stability Analysis Using High-Order Taylor Expansion Systems
    Wang, Bin
    Xu, Xin
    Sun, Kai
    2019 IEEE TEXAS POWER AND ENERGY CONFERENCE (TPEC), 2019,
  • [28] Virtual Armature Resistance-Based Control for Fault Current Limiting in a High-Order VSG and the Impact on Its Transient Stability
    Carletti, Daniel
    Amorim, Thiago
    Encarnacao, Lucas
    ENERGIES, 2023, 16 (12)
  • [29] Investigation of multifunctional grid-tied PV inverter with even and odd order harmonic mitigation using active and harmonic power weight control strategy
    Sharma, Surender Kumar
    Gali, Vijayakumar
    Gupta, Sunil Kumar
    ENERGY SYSTEMS-OPTIMIZATION MODELING SIMULATION AND ECONOMIC ASPECTS, 2024,
  • [30] Stability analysis of the high-order nonlinear extended state observers for a class of nonlinear control systems
    Gao, Ke
    Song, Jia
    Yang, Erfu
    TRANSACTIONS OF THE INSTITUTE OF MEASUREMENT AND CONTROL, 2019, 41 (15) : 4370 - 4379