A Multi-Terminal Current Differential Protection Setting Method for Fully Weak-Infeed Distribution Networks Based on Restricted Enumeration Method

被引:2
|
作者
Li, Botong [1 ]
Chen, Fahui [2 ]
Li, Bin [2 ]
Zhang, Jing [2 ]
Ji, Xiaotong [3 ]
Xiao, Fan [4 ]
Hong, Qiteng [5 ]
机构
[1] Tianjin Univ, Minist Educ, Key Lab Smart Grid, Tianjin 300072, Peoples R China
[2] Tianjin Univ, Sch Elect Engn & Automat, Tianjin 300072, Peoples R China
[3] State Grid Hubei Elect Power Co Ltd, Wuhan 430077, Peoples R China
[4] State Grid Hubei Elect Power Co Ltd, Elect Power Res Inst, Wuhan 430077, Peoples R China
[5] Univ Strathclyde, Dept Elect & Elect Engn, Glasgow City G1 1XW, Scotland
关键词
Fully weak-infeed distribution networks; multi-terminal current differential protection; restricted enumeration method; multi-terminal errors; energy router; multi-point T connection; inverter-interfaced distributed generators; GENERALIZED ALPHA PLANE; ENERGY ROUTER;
D O I
10.1109/TSG.2023.3319484
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the high penetration connection of inverter-interfaced distributed generators and the increasing application of large-capacity energy routers, fully weak-infeed distribution networks consisting entirely of power-electronized weak-infeed power sources are set to become one of the fundamental forms of future distribution networks. For fully weak-infeed distribution networks, multi-terminal current differential protection is considered an optional or even preferred line protection scheme. In this paper, a multi-terminal current differential protection setting method for fully weak-infeed distribution networks is proposed based on the restricted enumeration method. To address the impact of data synchronization errors and measurement errors of multi-terminal current on differential current, the problem of determining the maximum differential current superimposed with the multi-terminal current phasor errors is transformed into a high-dimensional non-convex optimization problem. The distribution law of the global optimal solution in the non-convex constraint space is deeply studied and analyzed, and a restricted enumeration method is proposed that can quickly solve the protection setting value, thereby solving the problem of multi-terminal current differential protection setting. The accuracy and rapidity of the proposed method are verified by comparing the calculation accuracy and time consumption of the restricted enumeration method and the exhaustive search. It is shown that the proposed multi-terminal differential protection setting method exhibits sufficient reliability and sensitivity in fully weak-infeed distribution networks, as verified through simulation analysis using a fully weak-infeed distribution network model built in PSCAD/EMTDC.
引用
收藏
页码:2570 / 2585
页数:16
相关论文
共 47 条
  • [1] A Virtual Multi-Terminal Current Differential Protection Scheme for Distribution Networks With Inverter-Interfaced Distributed Generators
    Han, Bowen
    Li, Haifeng
    Wang, Gang
    Zeng, Dehui
    Liang, Yuansheng
    IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (05) : 5418 - 5431
  • [2] Method for Detecting Intrusive Sensor Data by Enhanced Multi-terminal Differential Protection
    Coats, David
    Nuqui, Reynaldo
    2018 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2018,
  • [3] A protection method for multi-terminal HVDC system based on fuzzy approach
    Sahu, Upma
    Yadav, Anamika
    Pazoki, Mohammad
    METHODSX, 2023, 10
  • [4] Multi-Terminal Wireless Differential Protection Method for Offshore Wind Power Collection Lines
    Chen, Fufeng
    Xue, Mingjun
    Qiu, Yutao
    Yang, Lingang
    Chen, Qi
    Yu, Chunlin
    Yang, Liming
    Zou, Lei
    IEEE ACCESS, 2024, 12 : 58789 - 58800
  • [5] Fault Location Method for Multi-terminal Flexible DC Distribution Network Based on Control and Protection Coordination
    Liu K.
    Ren Z.
    Wang Y.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (08): : 3458 - 3466
  • [6] Transient current curvature based protection for multi-terminal flexible DC distribution systems
    Wang, Congbo
    Jia, Ke
    Bi, Tianshu
    Xuan, Zhenwen
    Zhu, Rui
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (15) : 3484 - 3492
  • [7] Online contingency analysis method for multi-terminal DC distribution networks with renewable resources
    Chen, Pengwei
    Xiao, Xiangning
    Baran, Mesut
    Wang, Xiaochu
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (08) : 1305 - 1314
  • [8] Pilot Protection Method for Multi-terminal Flexible DC Distribution Network Based on Correlation of High-frequency Power
    Chen S.
    Huang W.
    Tai N.
    Yu F.
    Zhu Z.
    Li C.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (19): : 150 - 159
  • [9] Fast pilot protection method of multi-terminal hybrid HVDC line based on time-domain differential convolution power
    Li H.
    Chu B.
    Liang Y.
    Deng C.
    Wang G.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2023, 43 (06): : 175 - 182
  • [10] A Day-ahead and Intraday Coordinated Energy Management Method for Active Distribution Networks Based on Multi-terminal Flexible Distribution Switch
    Sun F.
    Ma J.
    Yu M.
    Wei W.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (03): : 778 - 789