Effect of Voltage Waveform Steepness on Partial Discharge and Charge Distribution of Oil-Pressboard Insulation

被引:1
|
作者
Zhu, Ran [1 ]
He, Dongxin [1 ]
Li, Shuqi [1 ]
Wang, Xuliang [1 ]
Gu, Yuanli [1 ]
Zhai, Yuhui [1 ]
Ma, Longfei [1 ]
Wang, Liangkai [2 ]
Liu, Hongshun [1 ]
Li, Qingquan [1 ]
机构
[1] Shandong Univ, Shandong Prov Key Lab UHV Transmiss Technol & Equi, Jinan 250061, Peoples R China
[2] Yantai Power Supply Co State Grid, Yantai 264001, Peoples R China
基金
中国国家自然科学基金;
关键词
Partial discharges; Voltage; Harmonic analysis; Power transformer insulation; Oil insulation; Valves; Power harmonic filters; Oil-pressboard insulation; partial discharge; pulse voltage; space charge; voltage waveform steepness; ELECTRIC-FIELD;
D O I
10.1109/TDEI.2024.3371425
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The oil-pressboard insulation on the valve side of the converter transformer is subjected to the steep rising edge pulse voltage caused by commutation in actual operating conditions. The steep rising edge pulse voltage will aggravate insulation degradation and easily lead to insulation failure. However, the effect of voltage waveform steepness on insulation degradation is rarely considered directly in the current research. In this article, the actual voltage waveform of the main insulation on the converter transformer valve side is analyzed, and its harmonic content is determined. The experiments under steep rising edge pulse voltage and superimposed harmonics voltage are set up, and partial discharge pattern and space charge distribution are collected. The steeper the voltage waveform is, the narrower the phase distribution of the discharge pulse is, and the larger the maximum discharge quantity is. There is obvious charge accumulation inside the oil-impregnated pressboard under the steep rising edge electric field. The increase of waveform steepness makes the charge not easy to migrate under the externally applied electric field, and the retention effect is enhanced, resulting in an increase in charge accumulation. Moreover, the steepness of the voltage waveform becomes larger, and the charge injection is accelerated under the pulse voltage. The collision, trapping, and detrapping of high-energy electrons release more energy, which is more likely to cause insulation damage and form more traps. The increase of traps leads to charge accumulation, which results in electric field distortion and further promotes the generation of partial discharge. Based on the above analysis, the influence of voltage waveform steepness on oil-pressboard insulation failure is obtained, which provides a theoretical basis for insulation structure optimization and condition assessment of converter transformer.
引用
收藏
页码:1224 / 1232
页数:9
相关论文
共 50 条
  • [1] Study on partial discharge and charge accumulation characteristics of oil-pressboard insulation under DC superimposed harmonic voltage
    Li, Shuqi
    Wang, Qiang
    He, Dongxin
    Wang, Liangkai
    Li, Qingquan
    Si, Wen
    HIGH VOLTAGE, 2023, 8 (06) : 1215 - 1224
  • [2] Partial Discharge Characteristics of Fast Developing Discharge in Oil-pressboard Insulation
    Xu Z.
    Yang L.
    Wei Y.
    Cheng L.
    Zhao X.
    Yang X.
    Jiang Y.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (21): : 7529 - 7539
  • [3] Study on Development Characteristics of Partial Discharge in Oil-Pressboard Insulation under Constant DC Voltage
    Zhang, Chengjie
    Li, Yuan
    Yang, Senhong
    Li, Ranran
    ENERGIES, 2023, 16 (10)
  • [4] Correlation between Dielectric Loss and Partial Discharge of Oil-Pressboard Insulation
    Li, Yan
    Li, Min
    Xie, Jun
    SYMMETRY-BASEL, 2021, 13 (05):
  • [5] Behavior of Acoustic Partial Discharge Signal in Oil-Pressboard Insulation System
    Kundu, Prasanta
    Kishore, N. K.
    Sinha, A. K.
    IEEE REGION 10 COLLOQUIUM AND THIRD INTERNATIONAL CONFERENCE ON INDUSTRIAL AND INFORMATION SYSTEMS, VOLS 1 AND 2, 2008, : 114 - 119
  • [6] Effect of Cellulose Impurities on Partial Discharges in Oil-pressboard Insulation under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Ding, Yuqin
    Zhao, Yi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2271 - 2273
  • [7] Effect of Electrode Configurations and Gap Spacings on Partial Discharge Characteristics of Oil-Pressboard Insulation System
    Thirumurugan, C.
    Kumbhar, G. B.
    Oruganti, R.
    2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 428 - 431
  • [8] PD pulse waveform and charge distribution in oil-pressboard insulation with needle-plate model at positive DC voltage: Their characteristics and relationship
    Li, Simeng
    Li, Qingquan
    He, Dongxin
    Liu, Hongshun
    Wang, Peijin
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 112 : 252 - 261
  • [9] Effect of Temperature on Creeping Flashover Voltage of Nanofilled Oil-Pressboard Insulation
    Ibrahim, Mohamed E.
    Nassar, Alyaa A.
    Izzularab, Mohamed A.
    Abd-Elhady, Amr M.
    IEEE ACCESS, 2020, 8 : 227222 - 227231
  • [10] Influence of Fiber Impurities on DC Partial Discharge Process in Oil-pressboard Insulation
    Li, Yuan
    Zhang, Qiaogen
    Gao, Meng
    Ni, Heli
    Zhao, Yi
    Liu, Guangqi
    Wang, Ke
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,