The Use of Microfiltration for the Pretreatment of Backwash Water from Sand Filters

被引:0
作者
Wolska, Malgorzata [1 ]
Kabsch-Korbutowicz, Malgorzata [1 ]
Rosinska, Agata [2 ]
Solipiwko-Piescik, Anna [1 ]
Urbanska-Kozlowska, Halina [3 ]
机构
[1] Wroclaw Univ Sci & Technol, Fac Environm Engn, 27 Wybrzeze Wyspianskiego St, PL-50370 Wroclaw, Poland
[2] Czestochowa Tech Univ, Fac Infrastruct & Environm, 60A Brzeznicka St, PL-42200 Czestochowa, Poland
[3] Wroclaw Municipal Water & Sewage Co, Na Grobli 14-16, PL-50421 Wroclaw, Poland
关键词
microfiltration process; psychrophilic bacteria; recirculation; water treatment plants; MEMBRANE; SEDIMENTATION; COAGULATION; REMOVAL;
D O I
10.3390/ma17122819
中图分类号
O64 [物理化学(理论化学)、化学物理学];
学科分类号
070304 ; 081704 ;
摘要
Tests of microfiltration efficiency used for the pretreatment of backwash water from sand filters were conducted at two water treatment plants treating surface water and infiltration water. Microfiltration efficiency was evaluated for three membrane modules: two with polymeric membranes and one with a ceramic membrane. This study showed that the contaminants that limit the reuse of backwash water from both plants by returning them to the water treatment line are mostly microorganisms, including pathogenic species (Clostridium perfringens). Additionally, in the case of backwash water from infiltration water treatment, iron and manganese compounds also had to be removed before its recirculation to the water treatment system. Unexpectedly, organic carbon concentrations in both types of backwash water were similar to those present in intake waters. Microfiltration provided for the removal of organic matter, ranging from 19.9% to 44.5% and from 7.2% to 53.9% for backwash water from the treatments of surface water and infiltration water, respectively. Furthermore, the efficiency of the iron removal from backwash water from infiltration water treatment was sufficient to ensure good intake water quality. On the other hand, manganese concentrations in the backwash water, from infiltration water treatment, pretreated using the microfiltration process exceeded the levels found in the intake water and were, therefore, an additional limiting factor for the reuse of the backwash water. In both types of backwash water, the number of microorganisms, including Clostridium perfringens (a pathogenic one), was a limiting parameter for backwash water reuse without pretreatment. The results of the present study showed the possibility for using microfiltration for the pretreatment of backwash water, regardless of its origin but not as the sole process. More complex technological systems are needed before recirculating backwash water into the water treatment system. The polyvinylidene fluoride (PVDF) membrane proved to be the most effective for DOC and microorganism removal from backwash water.
引用
收藏
页数:16
相关论文
共 34 条
[1]   Innovative System for Recycling of Backwashing Water in Drinking Water Plant [J].
Abdel-Shafy, Hussein, I ;
El-Khateeb, Mohamed A. ;
Manson, Mona S. M. ;
Salem, Mohamed A. ;
Abdel-Shafy, Nancy H. .
EGYPTIAN JOURNAL OF CHEMISTRY, 2020, 63 (03) :885-895
[2]   Analysis of backwash settings to maximize net water production in an engineering-scale ultrafiltration system for water reuse [J].
Alhussaini, Mohammed A. ;
Binger, Zachary M. ;
Souza-Chaves, Bianca M. ;
Amusat, Oluwamayowa O. ;
Park, Jangho ;
V. Bartholomew, Timothy ;
Gunter, Dan ;
Achilli, Andrea .
JOURNAL OF WATER PROCESS ENGINEERING, 2023, 53
[3]   Microfiltration membrane processes: A review of research trends over the past decade [J].
Anis, Shaheen Fatima ;
Hashaikeh, Raed ;
Hilal, Nidal .
JOURNAL OF WATER PROCESS ENGINEERING, 2019, 32
[4]  
[Anonymous], 2015, UN Resolution Adopted by the General Assembly on 25 September 2015. A/RES/70/1
[5]  
Bodzek M., 2009, Eng. Environ. Prot, V12, P5
[6]   Adsorption/Coagulation/Ceramic Microfiltration for Treating Challenging Waters for Drinking Water Production [J].
Campinas, Margarida ;
Viegas, Rui M. C. ;
Coelho, Rosario ;
Lucas, Helena ;
Rosa, Maria Joao .
MEMBRANES, 2021, 11 (02) :1-19
[7]   Biodegradable Dissolved Organic Carbon (BDOC) Removal from Micro-Polluted Water Source Using Ultrafiltration: Comparison with Conventional Processes, Operation Conditions and Membrane Fouling Control [J].
Chen, Ming ;
Shen, Shuhuai ;
Zhang, Fan ;
Zhang, Cong ;
Xiong, Jianglei .
POLYMERS, 2022, 14 (21)
[8]   Aeration-manganese sand filter-ultrafiltration to remove iron and manganese from water: Oxidation effect and fouling behavior of manganese sand coated film [J].
Cheng, Li-Hua ;
Xiong, Zhao-Zhao ;
Cai, Shuo ;
Li, Du-Wang ;
Xu, Xin-Hua .
JOURNAL OF WATER PROCESS ENGINEERING, 2020, 38
[9]   Membrane aging effects on water recovery during full-scale potable reuse: Mathematical optimization of backwashing frequency for constant-flux microfiltration [J].
Cogan, N. G. ;
Ozturk, Deniz ;
Ishida, Kenneth ;
Safarik, Jana ;
Chellam, Shankararaman .
SEPARATION AND PURIFICATION TECHNOLOGY, 2022, 286
[10]   Pre-coagulation coupled with sponge-membrane filtration for organic matter removal and membrane fouling control during drinking water treatment [J].
Deng, Lijuan ;
Huu-Hao Ngo ;
Guo, Wenshan ;
Zhang, Hongwei .
WATER RESEARCH, 2019, 157 :155-166