Partial Discharge Characterization of HFO(E) Gas Using Ultra-High Frequency (UHF) Antenna for Medium Voltage Switchgear Application

被引:1
作者
Ahmed, Rizwan [1 ]
ABD-Rahman, Rahisham [1 ]
Ullah, Zahid [2 ]
Ullah, Rahmat [3 ]
Yousof, Mohd Fairouz Mohd [1 ]
Ullah, Kaleem [4 ]
机构
[1] Univ Tun Hussein Onn Malaysia, Fac Elect & Elect Engn, Batu Pahat 86400, Malaysia
[2] Politecn Milan, Dipartimento Elettron Informaz & Bioingn, I-20133 Milan, Italy
[3] Cardiff Univ, Adv High Voltage Engn Res Ctr, Sch Engn, Cardiff CF10 3AT, Wales
[4] UET Peshawar, Dept Elect Energy Syst, CASE, Peshawar 25000, Pakistan
关键词
Partial discharges; gas insulated switchgear; SF6; gas dielectrics; ultra high-frequency antenna; INSULATION; DEFECTS; DESIGN; HFCT;
D O I
10.1109/ACCESS.2024.3411059
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The most frequent and dangerous hazard to the electrical insulation of high voltage (HV) and high field (HF) equipment is partial discharges (PD). The development of PD activity is both a cause and an indicator of insulation degradation, which could ultimately lead to insulation breakdown. For electrical power equipment to operate safely and dependably, continuous and efficient PD monitoring must be conveniently performed to prevent associated damages and any harm to electrical power equipment. This work presents the design of a new UHF antenna for detecting PD in medium-voltage gas-insulated applications. The working frequency band of the proposed UHF antenna is 370 MHz-1300 MHz, which translates into a total bandwidth of 930 MHz UHF frequency band. Over the whole operating frequency of the antenna, the return loss is less than -10dB. Recently, an eco-friendly insulating gas, HFO1336mzz(E), is considered to be a good substitute for sulfur hexafluoride (SF6) in medium-voltage gas-insulated equipment (MV-GIE). The HFO(E) gas in a mixture with CO2 can reach the dielectric strength of SF6 gas. Hence, the HFO(E)/CO2 gas mixture's partial discharge properties are systematically investigated in this research work. In particular, a detailed examination focuses on the partial discharge extinction voltage (PDEV) and partial discharge inception voltage (PDIV) under varying electric field conditions at different gas pressure levels and mixing ratios. The PDIV of the HFO(E)/CO2 gas mixture exhibited a linear-saturation rising pattern with both mixing ratio and gas pressure, mirroring the trend observed in SF6 when the HFO(E) gas concentration ranged between 25% and 30%.
引用
收藏
页码:81196 / 81205
页数:10
相关论文
共 32 条
[1]   Application of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment [J].
Alvarez, Fernando ;
Garnacho, Fernando ;
Ortego, Javier ;
Angel Sanchez-Uran, Miguel .
SENSORS, 2015, 15 (04) :7360-7387
[2]   Detection and Classification of Defects in Ceramic Insulators using RF Antenna [J].
Anjum, Shaharyar ;
Jayaram, Shesha ;
El-Hag, Ayman ;
Jahromi, Ali Naderian .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) :183-190
[3]  
[Anonymous], 2000, IEC Std 60270:2000+AMD1:2015 CSV
[4]   Unknown PD distinction in HVAC/HVDC by antenna-sensor with pulse sequence analysis [J].
Azam, S. M. Kayser ;
Othman, Mohamadariff ;
Illias, Hazlee Azil ;
Latef, Tarik Abdul ;
Fahmi, Daniar ;
Raymond, Wong Jee Keen ;
Mahadi, Wan Nor Liza Wan ;
Hossain, K. M. Zakir ;
Aziz, M. Z. A. Abd. ;
Ababneh, Ahmad .
ALEXANDRIA ENGINEERING JOURNAL, 2024, 91 :457-471
[5]   Internal UHF antenna for partial discharge detection in GIS [J].
Bin, Feng ;
Wang, Feng ;
Sun, Qiuqin ;
Lin, Shu ;
Xie, Yaoheng ;
Fan, Min .
IET MICROWAVES ANTENNAS & PROPAGATION, 2018, 12 (14) :2184-2190
[6]   Vapor-liquid equilibrium measurements for 5 binary mixtures involving HFO-1336mzz(E) at temperatures from 313 to 353 K and pressures up to 2.735 MPa [J].
Boonaert, Eric ;
Valtz, Alain ;
Brocus, Julien ;
Coquelet, Christophe ;
Beucher, Yannick ;
De Carlan, Florence ;
Fourmigue, Jean-Marie .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 114 :210-220
[7]   Application of UHF Sensors in Power System Equipment for Partial Discharge Detection: A Review [J].
Chai, Hua ;
Phung, B. T. ;
Mitchell, Steve .
SENSORS, 2019, 19 (05)
[8]   A low-profile flexible planar monopole antenna for biomedical applications [J].
Islam, Md Shazzadul ;
Azam, S. M. Kayser ;
Hossain, A. K. M. Zakir ;
Ibrahimy, Muhammad I. ;
Motakabber, S. M. A. .
ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH, 2022, 35
[9]   The excitation of UHF signals by partial discharges in GIS [J].
Judd, MD ;
Farish, O ;
Hampton, BF .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1996, 3 (02) :213-228
[10]  
Kothe D. C., 2020, P VDE HIGH VOLT TECH, P1